Ge VAT20 fault codes 2
Hi everyone,
Is the power supply voltage reaching the L1 and L2 terminals? (Is the charge indicator lit?)
Check if the power supply is on.
Turn OFF the power supply and then turn it ON.
Verify the power voltage level again.
Check if the mounting screw is tightened.
Is there voltage output from output terminals T1, T2, and T3?
Turn OFF the power supply and then turn it ON.
Is the load too heavy for the motor to start?
Reduce the load to start the motor.
Is there any abnormal condition in the inverter?
Check if a forward or reverse instruction is loaded.
Examine and correct the wiring according to troubleshooting instructions.
Is the analog frequency setting loaded?
Check if the wiring of the analog frequency input signal is correct.
Is the operating mode setting correct?
Verify the voltage of the frequency input setting is correct.
Is the wiring correct at output terminals T1, T2, and T3?
Operate with the digital panel.
Is the motor running in reverse direction?
Check if the wiring for forward and reverse signals is correct.
Ensure the wiring is appropriate for the motor's U, V, and W terminals.
Is the wiring for the analog frequency input correct?
Examine and correct the wiring.
Is the operating mode setting correct?
Examine and correct the wiring.
Is the motor operating speed stable?
Is the load too heavy?
Check the operating mode setting of the operating panel.
Are the motor specifications (poles, voltage) correct?
Reduce the load.
Is the gear ratio correct?
Re-verify the motor specifications.
Is the motor operating speed too high or too low?
Is the voltage on the motor side excessively low?
Is the maximum output frequency setting correct?
Re-verify the maximum output frequency.
Is the load too heavy?
Reduce the load.
Is the load variation too large?
Increase the capacity of the inverter and motor.
Is there abnormal speed variation in operation?
Is the input power supply stable and steady?
Install an AC reactor on the power supply input side.
Error Codes, Descriptions, and Solutions for VAT20 General Electric VFD:
OL1 - Motor Overload
Cause: 1. Load is too heavy 2. Inappropriate V/F pattern setting 3. Inappropriate Fn_18 setting
Solution: 1. Increase motor capacity 2. Set for an appropriate V/F curve 3. Set Fn_18 according to the instruction
OL2 - Inverter Overload
Cause: 1. Load is too heavy 2. Inappropriate V/F pattern setting
Solution: 1. Increase inverter capacity 2. Set for an appropriate V/F curve
OCS - Temporary Overcurrent at Start-up
Cause: 1. Motor winding short-circuited with the outer casing 2. Motor connection cable short-circuited with the ground 3. Transistor module damaged
Solution: 1. Examine the motor 2. Examine the wiring 3. Replace the transistor module
OCA - Overcurrent during Acceleration
Cause: 1. Acceleration time setting too short 2. Inappropriate selection of V/F characteristic 3. Applied motor capacity exceeds inverter capacity
Solution: 1. Set a longer acceleration time 2. Set for an appropriate V/F curve 3. Replace and install with another inverter of suitable capacity
OCC - Overcurrent at Constant Speed
Cause: 1. Temporary change in load 2. Temporary change in power supply
Solution: 1. Examine the load configuration 2. Install an inductor on the power supply input side
OCd - Overcurrent during Deceleration
Cause: Deceleration setting too short
Solution: Set for a longer deceleration time
OCb - Overcurrent during Braking
Cause: DC Braking frequency, braking voltage, or braking time setting too long
Solution: Set to reduce the settings of Fn_15, Fn_16, or Fn_17
OVC - Overvoltage during Operation/Deceleration
Cause:1. Deceleration time setting too short or inertial load too large 2. Power supply voltage too variable
Solution: 1. Set for a longer deceleration time 2. Install an inductor on the power supply input side 3. Increase inverter capacity
LVC - Insufficient Voltage Level during Operation
Cause: 1. Power supply voltage too low 2. Power supply voltage too variable
Solution: 1. Improve the quality of the power supply 2. Set for a longer acceleration time 3. Increase inverter capacity 4. Install a reactor on the power supply input side
OHC - Overheating of Heat Insulation during Operation
Cause: 1. Load too heavy 2. Ambient temperature too high or ventilation inadequate
Solution: 1. Examine the load 2. Increase inverter capacity 3. Improve ventilation
SP0 - Stop at Zero Speed
Cause: Occurs when Fn_11 = 0, Fn_7= 0, and frequency setting < 1 Hz or when Fn_11 = 1, Fn_7 < (Fn_6/100), and frequency setting < (Fn_6/100)
SP2 - Keypad Emergency Stop
Cause: When the inverter is set to external operation mode (Fn_10=1), pressing the STOP key on the keypad during operation causes the inverter to stop according to the Fn_14 setting, and SP2 flashes after stopping. To restart the machine, turn the RUN switch to OFF and then ON.
E.S - External Emergency Stop
Cause: When the external emergency stop signal is activated through the multifunction input terminal, the inverter slows down and stops. After the inverter stops, E.S. flashes (see the instruction for Fn_19 for details).
b.b - External BASE BLOCK
Cause: When the external BASE BLOCK signal is activated through the multifunction terminal, the inverter output immediately stops, and b.b. flashes as an indicator (see the instruction for Fn_19 for details).
LOC - Locked Motor Direction
Cause: 1. Attempting to reverse when Fn_22 = 1 2. Attempting to set Fn_22 to 1 while Fn_04 = 1
Solution: 1. Set Fn_22 to 0 2. Set Fn_04 to 0
Er1 - Keypad Operation Error
Cause: 1. Pressing the or keys when Fn_11=1 or during sp1 operation 2. Attempting to change Fn_29 3. Attempting to change a parameter that cannot be changed during operation (see the parameter list)
Solution: 1. Use the or keys to set the frequency setting after Fn_11=0 2. Do not change Fn_29 3. Change in stop mode
Er2 - Parameter Setting Error
Cause: 1. Fn_6 ≤ Fn_7
Solution: 1. Set Fn_6 > Fn_7