Hi everyone,

General Troubleshooting Method for VAT20 General Electric VFD

Is the power supply voltage reaching the L1 and L2 terminals? (Is the charge indicator lit?)
    Check if the power supply is on.
    Turn OFF the power supply and then turn it ON.
    Verify the power voltage level again.
    Check if the mounting screw is tightened.

Is there voltage output from output terminals T1, T2, and T3?
    Turn OFF the power supply and then turn it ON.

Is the load too heavy for the motor to start?
    Reduce the load to start the motor.

Is there any abnormal condition in the inverter?
    Check if a forward or reverse instruction is loaded.
    Examine and correct the wiring according to troubleshooting instructions.

Is the analog frequency setting loaded?
    Check if the wiring of the analog frequency input signal is correct.
    Is the operating mode setting correct?
    Verify the voltage of the frequency input setting is correct.

Is the wiring correct at output terminals T1, T2, and T3?
    Operate with the digital panel.

Is the motor running in reverse direction?
    Check if the wiring for forward and reverse signals is correct.
    Ensure the wiring is appropriate for the motor's U, V, and W terminals.

Is the wiring for the analog frequency input correct?
    Examine and correct the wiring.
    Is the operating mode setting correct?
    Examine and correct the wiring.

Is the motor operating speed stable?
    Is the load too heavy?
    Check the operating mode setting of the operating panel.
    Are the motor specifications (poles, voltage) correct?
    Reduce the load.
    Is the gear ratio correct?
    Re-verify the motor specifications.

Is the motor operating speed too high or too low?
    Is the voltage on the motor side excessively low?
    Is the maximum output frequency setting correct?
    Re-verify the maximum output frequency.

Is the load too heavy?
    Reduce the load.
    Is the load variation too large?
    Increase the capacity of the inverter and motor.

Is there abnormal speed variation in operation?
    Is the input power supply stable and steady?
    Install an AC reactor on the power supply input side.

Error Codes, Descriptions, and Solutions for VAT20 General Electric VFD:

OL1 - Motor Overload
    Cause: 1. Load is too heavy 2. Inappropriate V/F pattern setting 3. Inappropriate Fn_18 setting
    Solution: 1. Increase motor capacity 2. Set for an appropriate V/F curve 3. Set Fn_18 according to the instruction

OL2 - Inverter Overload
    Cause: 1. Load is too heavy 2. Inappropriate V/F pattern setting
    Solution: 1. Increase inverter capacity 2. Set for an appropriate V/F curve

OCS - Temporary Overcurrent at Start-up
    Cause: 1. Motor winding short-circuited with the outer casing 2. Motor connection cable short-circuited with the ground 3. Transistor module damaged
    Solution: 1. Examine the motor 2. Examine the wiring 3. Replace the transistor module

OCA - Overcurrent during Acceleration
    Cause: 1. Acceleration time setting too short 2. Inappropriate selection of V/F characteristic 3. Applied motor capacity exceeds inverter capacity
    Solution: 1. Set a longer acceleration time 2. Set for an appropriate V/F curve 3. Replace and install with another inverter of suitable capacity

OCC - Overcurrent at Constant Speed
    Cause: 1. Temporary change in load 2. Temporary change in power supply
    Solution: 1. Examine the load configuration 2. Install an inductor on the power supply input side

OCd - Overcurrent during Deceleration
    Cause: Deceleration setting too short
    Solution: Set for a longer deceleration time

OCb - Overcurrent during Braking
    Cause: DC Braking frequency, braking voltage, or braking time setting too long
    Solution: Set to reduce the settings of Fn_15, Fn_16, or Fn_17

OVC - Overvoltage during Operation/Deceleration
    Cause:1. Deceleration time setting too short or inertial load too large 2. Power supply voltage too variable
    Solution: 1. Set for a longer deceleration time 2. Install an inductor on the power supply input side 3. Increase inverter capacity

LVC - Insufficient Voltage Level during Operation
    Cause: 1. Power supply voltage too low 2. Power supply voltage too variable
    Solution: 1. Improve the quality of the power supply 2. Set for a longer acceleration time 3. Increase inverter capacity 4. Install a reactor on the power supply input side

OHC - Overheating of Heat Insulation during Operation
    Cause: 1. Load too heavy 2. Ambient temperature too high or ventilation inadequate
    Solution: 1. Examine the load 2. Increase inverter capacity 3. Improve ventilation

SP0 - Stop at Zero Speed
    Cause: Occurs when Fn_11 = 0, Fn_7= 0, and frequency setting < 1 Hz or when Fn_11 = 1, Fn_7 < (Fn_6/100), and frequency setting < (Fn_6/100)

SP2 - Keypad Emergency Stop
    Cause: When the inverter is set to external operation mode (Fn_10=1), pressing the STOP key on the keypad during operation causes the inverter to stop according to the Fn_14 setting, and SP2 flashes after stopping. To restart the machine, turn the RUN switch to OFF and then ON.

E.S - External Emergency Stop
    Cause: When the external emergency stop signal is activated through the multifunction input terminal, the inverter slows down and stops. After the inverter stops, E.S. flashes (see the instruction for Fn_19 for details).

b.b - External BASE BLOCK
    Cause: When the external BASE BLOCK signal is activated through the multifunction terminal, the inverter output immediately stops, and b.b. flashes as an indicator (see the instruction for Fn_19 for details).

LOC - Locked Motor Direction
    Cause: 1. Attempting to reverse when Fn_22 = 1 2. Attempting to set Fn_22 to 1 while Fn_04 = 1
    Solution: 1. Set Fn_22 to 0 2. Set Fn_04 to 0

Er1 - Keypad Operation Error
    Cause: 1. Pressing the  or  keys when Fn_11=1 or during sp1 operation 2. Attempting to change Fn_29 3. Attempting to change a parameter that cannot be changed during operation (see the parameter list)
    Solution: 1. Use the  or  keys to set the frequency setting after Fn_11=0 2. Do not change Fn_29 3. Change in stop mode

Er2 - Parameter Setting Error
    Cause: 1. Fn_6 ≤ Fn_7
    Solution: 1. Set Fn_6 > Fn_7

+ Ge Vat20 User manuals >

+ Ge Vat20 Fault Codes 1 >

+ Ge Vat20 Fault Codes 2 >


+ General Electric 2. Main page >

+ VFD Homepage > 


-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  03.01.2013