Unidrive SP Fault codes 3
EnC15 Drive encoder fault: The number of periods per revolution calculated from encoder data during auto-configuration is either less than 2 or greater than 50,000
- The linear motor pole pitch/encoder ppr setup is incorrect or out of parameter range (e.g., Pr 5.36 = 0 or Pr 21.31 = 0).
- The encoder may be faulty.
EnC16 Drive encoder fault: EnDat encoder - The number of communication bits per period for a linear encoder exceeds 255
- Select a different type of encoder.
- The encoder may be faulty.
EnC17 Drive encoder fault: The periods per revolution obtained during auto-configuration for a rotary SINCOS encoder is not a power of two
- Select a different type of encoder.
- The encoder may be faulty.
ENP.Er Data error from the electronic nameplate stored in the selected feedback device
- Replace the feedback device.
Et External trip
- Check terminal 31 signal.
- Check the value of Pr 10.32.
- Enter 12001 in Pr xx.00 and check the parameter controlling Pr 10.32.
- Ensure that Pr 10.32 or Pr 10.38 (=6) are not being controlled by serial communications.
HF01 Data processing error: CPU address error
- Hardware fault - return the drive to the supplier.
HF02 Data processing error: DMAC address error
- Hardware fault - return the drive to the supplier.
HF03 Data processing error: Illegal instruction
- Hardware fault - return the drive to the supplier.
HF04 Data processing error: Illegal slot instruction
- Hardware fault - return the drive to the supplier.
HF05 Data processing error: Undefined exception
- Hardware fault - return the drive to the supplier.
HF06 Data processing error: Reserved exception
- Hardware fault - return the drive to the supplier.
HF07 Data processing error: Watchdog failure
- Hardware fault - return the drive to the supplier.
HF08 Data processing error: Level 4 crash
- Hardware fault - return the drive to the supplier.
HF09 Data processing error: Heap overflow
- Hardware fault - return the drive to the supplier.
HF10 Data processing error: Router error
- Hardware fault - return the drive to the supplier.
HF11 Data processing error: EEPROM access failure
- Hardware fault - return the drive to the supplier.
HF12 Data processing error: Main program stack overflow
- Hardware fault - return the drive to the supplier.
HF13 Data processing error: Software incompatible with hardware
- Hardware or software fault - return the drive to the supplier.
HF17 Multi-module system thermistor short circuit or open circuit
- Hardware fault - return the drive to the supplier.
HF18 Multi-module system interconnect cable error
- Hardware fault - return the drive to the supplier.
HF19 Temperature feedback multiplexing failure
- Hardware fault - return the drive to the supplier.
HF20 Power stage recognition: Serial code error
- Hardware fault - return the drive to the supplier.
HF21 Power stage recognition: Unrecognized frame size
- Hardware fault - return the drive to the supplier.
HF22 Power stage recognition: Multi-module frame size mismatch
- Hardware fault - return the drive to the supplier.
HF23 Power stage recognition: Multi-module voltage or current rating mismatch
- Hardware fault - return the drive to the supplier.
HF24 Power stage recognition: Unrecognized drive size
- Hardware fault - return the drive to the supplier.
HF25 Current feedback offset error
- Hardware fault - return the drive to the supplier.
HF26 Soft start relay failed to close, soft start monitor failure, or braking IGBT short circuit at power-up
- Hardware fault - return the drive to the supplier.
HF27 Power stage thermistor 1 fault
- Hardware fault - return the drive to the supplier.
HF28 Power stage thermistor 2 fault, or internal fan fault (size 3)
- Hardware fault - return the drive to the supplier.
HF29 Control board thermistor fault
- Hardware fault - return the drive to the supplier.
HF30 DCCT wire break trip from power module
- Hardware fault - return the drive to the supplier.
HF31 Internal capacitor bank fan failure (size 4 and larger) or a module has not powered up in a multi-module parallel drive
- Check the AC or DC power supply to all modules in the multi-module parallel drive.
- If the AC or DC power supply is present, or if this is a single drive, then there is a hardware fault - return the drive to the supplier.
HF32 Power stage: Identification and trip information serial code error
- Hardware fault - return the drive to the supplier.