Toshiba S9 Fault codes 1
OC1 (0001) - Overcurrent during Acceleration:
+ The acceleration time is too short.
+ The V/F setting is incorrect.
+ A restart signal is sent to the motor after a brief stop.
+ A special motor (e.g., with low impedance) is used.
Solutions:
+ Increase the acceleration time.
+ Check the V/F parameter.
+ Use F301 (auto-restart) and F302 (ride-through control).
+ Increase the carrier frequency with F303.
OC2 (0002) - Overcurrent during Deceleration:
+ The deceleration time is too short.
Solutions:
+ Increase the deceleration time.
OC3 (0003) - Overcurrent during Operation:
+ The load fluctuates suddenly.
+ The load is in an abnormal condition.
Solutions:
+ Reduce load fluctuations.
+ Check the load (operated machine).
OCR (0005) - Arm Overcurrent at Start-up:
+ A main circuit element is defective.
Solutions:
+ Make a service call.
OCL (0004) - Overcurrent on the Load Side at Start-up:
+ The insulation of the output main circuit or motor is defective.
+ The motor impedance is too low.
Solutions:
+ Check the cables and wires for defective insulation.
OP1 (000A) - Overvoltage during Acceleration:
+ The input voltage fluctuates abnormally.
+ The power supply has a capacity of 200kVA or more.
+ A power factor improvement capacitor is opened or closed.
+ A system using a thyristor is connected to the same power distribution line.
+ A restart signal is input to the rotating motor after a momentary stop.
Solutions:
+ Insert a suitable input reactor.
+ Use F301 (auto-restart) and F302 (ride-through control).
OP2 (000B) - Overvoltage during Deceleration:
+ The deceleration time is too short (Regenerative energy is too large).
+ F304 (dynamic braking resistor activation) is off.
+ F305 (overvoltage limit operation) is off.
+ The input voltage fluctuates abnormally.
- The power supply has a capacity of 200kVA or more.
- A power factor improvement capacitor is opened or closed.
- A system using a thyristor is connected to the same power distribution line.
Solutions:
+ Increase the deceleration time.
+ Install a suitable dynamic braking resistor.
+ Enable F304 (dynamic braking selection).
+ Enable F305 (overvoltage limit operation).
+ Insert a suitable input reactor.
OP3 (000C) - Overvoltage during Constant-Speed Operation:
+ The input voltage fluctuates abnormally.
- The power supply has a capacity of 200kVA or more.
- A power factor improvement capacitor is opened or closed.
- A system using a thyristor is connected to the same power distribution line.
+ If the motor is in a regenerative state, the load causes the motor to run at a frequency higher than the inverter output frequency.
Solutions:
+ Insert a suitable input reactor.
+ Install a dynamic braking resistor.
OL1 (000D) - Inverter Overload:
+ The acceleration time is too short.
+ The DC braking amount is too low.
+ The V/F setting is incorrect.
+ A restart signal is input to the motor after a momentary stop.
+ The load is too large.
Solutions:
+ Increase the acceleration time.
+ Reduce the DC braking amount and time.
+ Check the V/F parameter setting.
+ Use F301 (auto-restart) and F302 (ride-through control).
+ Use an inverter with a larger rating.
OL2 (000E) - Motor Overload:
+ The V/F setting is incorrect.
+ The motor is locked up.
+ Low-speed operation is performed continuously.
+ An excessive load is applied to the motor.
Solutions:
+ Check the V/F parameter setting.
+ Check the load (operated machine).
+ Adjust to a load that the motor can withstand during operation in a low-speed range.
EPHO (0009) - Output Phase Failure:
+ A phase failure occurred in the output line of the main circuit.
Solutions:
+ Check the main circuit output line, motor, etc., for phase failure.
+ Enable F605 (output phase failure detection).
EPHI (0008) - Input Phase Failure:
+ A phase failure occurred in the input line of the main circuit.
Solutions:
+ Check the main circuit input line for phase failure.
+ Enable F608 (input phase failure detection).
+ VFD Main page -
"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us." 08.03.2013Your shopping cart is empty!