ATV 71 Fault codes 2

- InF1 (Rating error)
Description: The power card is different from the card stored.
Cause: There may be a mismatch between the power card and the stored configuration.
+ Solution: Check the reference of the power card.

- InF2 (Incompatible PB)
Description: The power card is incompatible with the control card.
Cause: There may be a compatibility issue between the power card and the control card.
+ Solution: Check the reference of the power card and its compatibility.

- InF3 (Internal serial link)
Description: Communication fault between the internal cards.
Cause: There could be an issue with the internal connections.
+ Solution: Check the internal connections. Inspect/repair the drive.

- InF4 (Internal-mftg zone)
Description: Internal data inconsistent.
Cause: There may be a calibration issue.
+ Solution: Recalibrate the drive (performed by Schneider Electric Product Support).

- InF6 (Internal - fault option)
Description: The option installed in the drive is not recognized.
Cause: There may be a compatibility issue with the installed option.
+ Solution: Check the reference and compatibility of the option.

- InF7 (Internal-hard init.)
Description: Initialization of the drive is incomplete.
Cause: The drive may not have completed its initialization process.
+ Solution: Turn off and reset the drive.

- InF8 (Internal-ctrl supply)
Description: The control power supply is incorrect.
Cause: There may be an issue with the control section power supply.
+ Solution: Check the control section power supply.

- InF9 (Internal- I measure)
Description: The current measurements are incorrect.
Cause: There could be an issue with the current sensors or the power card.
+ Solution: Replace the current sensors or the power card. Inspect/repair the drive.

- InFA (Internal-mains circuit)
Description: The input stage is not operating correctly.
Cause: There could be an issue with the input stage of the drive.
+ Solution: Perform diagnostic tests via the [1.10 DIAGNOSTICS] menu. Inspect/repair the drive.

- InFb (Internal- th. sensor)
Description: The drive temperature sensor or the braking unit's temperature sensor is not operating correctly.
Cause: There could be an issue with the temperature sensors.
+ Solution: Replace the drive temperature sensor or the braking unit's temperature sensor as needed. Inspect/repair the drive or the braking unit. If there is no braking unit connected to the drive, disable the monitoring of this fault by the [Brake res. fault Mgt.] (bUb) parameter on page 241.

- InFC (Internal-time meas.)
Description: Fault on the electronic time measurement component.
Cause: There could be an issue with the time measurement component.
+ Solution: Inspect/repair the drive.

- InFE (internal- CPU)
Description: Internal microprocessor fault.
Cause: There could be an issue with the drive's microprocessor.
+ Solution: Turn off and reset the drive. Inspect/repair the drive.  