ATV 56 fault codes 2

GROUND FAULT [1]

Cause: Short circuit of phase to earth or grounding on the output of the drive controller.
Troubleshooting:
- Remove all power, check connecting cables and motor insulation with the drive controller disconnected.
- Use drive controller diagnostics (refer to Chapter 5).

MEMORY FAILURE [2]
Cause: EEPROM memory storage fault.
Troubleshooting:
- Recall factory or customer settings using the keypad.

AUTO-TEST FAIL [2]

Cause: Main control board failure.
Troubleshooting:
- Remove all power, check control board connections with the drive controller disconnected.
- Replace the main control board.

CONTROL SUPPLY [2]

Cause: CL1/CL2 not connected.
Troubleshooting:
- Check the connection of CL1 and CL2.

OVERSPEED

Cause: Output frequency is 20% above the Maximum Frequency parameter setting (no tachometer present).
Troubleshooting:
- Check the load base speed and power rating, compare with the operating speed and drive controller/motor power rating.
- Check the setting of damping and bandwidth (if used) adjustments.

DYNAMIC BRAKE

Causes:
- DB transistor short circuit.
- DB resistor short or open-circuited.
- Braking resistor thermal contact tripped.
Troubleshooting:
- Remove all power, check connecting cables and DB resistor with the drive controller disconnected.
- Use drive controller self-diagnostics (refer to Chapter 5).
- Check dynamic brake connections and change the resistor if necessary.

LINK FAULT

Causes:
- Internal fault.
- Software execution stopped.
Troubleshooting:
- Note the LED sequence on the drive controller:
- FAULT, CAUTION, POWER all illuminated, or
- CAUTION, POWER illuminated.
- Cycle power.
- If the fault persists, replace the keypad or main control board.

SEQUENCE T. OUT (Sequence Time out)

Cause: Sequence input not received after Run command within programmed time (Bypass function).

Troubleshooting:
- Check the connection between the user-supplied contact and logic input, ensuring it is connected to the programmed input.
- Verify the operation of the contact.
- Verify the operation of external control sequencing.

PROCESS TIME OUT

Cause: Process input not received after Run command within programmed time (Bypass function).
Troubleshooting:

- Check the connection between the user-supplied contact and logic input, ensuring it is connected to the programmed input.
- Verify the operation of the contact.
- Verify the operation of the process.

TRANS. SHORT C. or GF (Transistor Short Circuit)

Cause: Transistor is in short circuit.
Troubleshooting:
- Contact the local service representative.

OPEN TRANSISTOR

Cause: Transistor has failed open.
Troubleshooting:
- Contact the local service representative.

OUT. PHASE LOSS

Causes:
- Motor power rating too small for the controller.
- Output phases disconnected.
Troubleshooting:
- Ensure the motor power rating is > 45% of the controller power rating.
- Check output power conductors and connectors for lack of continuity.
- Check output contactor sequencing.

OVERSPEED (Without tachometer)

Cause: Output frequency is 20% above the Maximum Frequency parameter setting.
Troubleshooting:
- Check the load base speed and power rating, compare with the operating speed and drive controller/motor power rating.

OVERSPEED (With tachometer)

Causes:

- Incorrect adjustment of tachometer feedback.
- Machine overload.
- No tachometer signal.
- Tachometer polarity incorrect.
Troubleshooting:
- Check feedback.
- Check the load base speed and power rating, compare with the operating speed and drive controller/motor power rating.
- Check the tachometer connection.
- Check the tachometer polarity.

CUSTOM. FAULT

Cause: User-defined.
Troubleshooting:

- Dependent on user setting.

FEEDBACK LOSS

Cause: No tachometer feedback signal.
Troubleshooting:

- Check tachometer wiring.