ATV 32 fault codes

ASF [Angle Error]
- Probable cause: Incorrect speed loop setting for [Sync. mot.] (SYn) when the reference passes through 0.
+ Remedy: Check speed loop parameters and motor phases. Ensure maximum current allowed by the drive is not exceeded.
brF [Brake feedback]
- Probable cause: Brake feedback contact mismatch with brake logic control or brake not stopping motor quickly enough.
+ Remedy: Check feedback and brake logic control circuits, mechanical state of the brake, and brake linings.
CrF1 [Precharge]
- Probable cause: Charging relay control fault or damaged charging resistor.
+ Remedy: Turn the drive off and on again, check internal connections, contact Schneider Electric Product Support.
EEF1 [Control Eeprom]
- Probable cause: Internal memory fault in the control block.
+ Remedy: Check electromagnetic compatibility, reset and return to factory settings, contact Schneider Electric Product Support.
EEF2 [Power Eeprom]
- Probable cause: Internal memory fault in the power card.
+ Remedy: Same as EEF1.
FCF1 [Output contactor stuck]
- Probable cause: Output contactor remains closed despite opening conditions being met.
+ Remedy: Check contactor, wiring, and feedback circuit.
HdF [IGBT desaturation]
- Probable cause: Short-circuit or grounding at the drive output.
+ Remedy: Check cables connecting the drive to the motor and motor insulation.
ILF [Internal communication link]
- Probable cause: Communication interruption between option card and drive.
+ Remedy: Check electromagnetic compatibility, connections, replace option card, contact Schneider Electric Product Support.
InF1 [Rating error]
- Probable cause: Power card differs from the stored card.
+ Remedy: Check the reference of the power card.
InF2 [Incompatible PB]
- Probable cause: Power card incompatible with the control block.
+ Remedy: Check the reference and compatibility of the power card.
InF3 [Internal serial link]
- Probable cause: Communication interruption between internal cards.
+ Remedy: Check internal connections, contact Schneider Electric Product Support.
InF4 [Internal manufacturing zone]
- Probable cause: Inconsistent internal data.
+ Remedy: Recalibrate the drive (performed by Schneider Electric Product Support).
InF6 [Internal fault option]
- Probable cause: Installed option not recognized by the drive.
+ Remedy: Check the reference and compatibility of the option.
InF9 [Internal current measurement]
- Probable cause: Incorrect current measurements.
+ Remedy: Replace current sensors or power card, contact Schneider Electric Product Support.
InFA [Internal mains circuit]
- Probable cause: Input stage not operating correctly.
+ Remedy: Contact Schneider Electric Product Support.
InFb [Internal temperature sensor]
- Probable cause: Drive temperature sensor not operating correctly.
+ Remedy: Replace drive temperature sensor, contact Schneider Electric Product Support.
InFE [Internal CPU]
- Probable cause: Internal microprocessor fault.
+ Remedy: Turn off and reset, contact Schneider Electric Product Support.
OCF [Overcurrent]
- Probable cause: Incorrect parameters in [SETTINGS] (SEt-) and [MOTOR CONTROL] (drC-) menus, high inertia or load, mechanical locking.
+ Remedy: Check parameters, motor/drive/load size, mechanism state, decrease [Current limitation] (CLI), increase switching frequency.
SAFF [Safe function fault]
- Probable cause: Exceeded debounce time, SS1 trip threshold exceeded, wrong configuration.
+ Remedy: Check safety functions configuration, contact Schneider Electric Product Support.
SCF1 [Motor Short Circuit]
- Cause: Short-circuit or grounding at the drive output.
+ Remedy:
- Check the cables connecting the drive to the motor and the motor insulation.
- Reduce the switching frequency.
- Connect chokes in series with the motor.
- Check the adjustment of the speed loop and brake.
- Increase the [Time to restart] (ttr) parameter.
- Increase the switching frequency.
SCF3 [Ground Short Circuit]
- Cause: Significant earth leakage current at the drive output if several motors are connected in parallel.
+ Remedy:
- Check the cables connecting the drive to the motor and the motor insulation.
- Reduce the switching frequency.
- Connect chokes in series with the motor.
- Check the adjustment of the speed loop and brake.
- Increase the [Time to restart] (ttr) parameter.
- Reduce the switching frequency.
SOF [Overspeed]
- Cause: Instability or driving load too high.
+ Remedy:
- Check the motor, gain, and stability parameters.
- Add a braking resistor.
- Check the size of the motor/drive/load.
- Check the parameter settings for the [FREQUENCY METER] (FqF-) function if it is configured.
SPF [Speed Feedback Loss]
- Cause: Signal on "Pulse input" missing if the input is used for speed measurement.
+ Remedy:
- Check the wiring of the input cable and the detector used.
tnF [Auto-tuning]
- Cause: Special motor or motor whose power is not suitable for the drive. Motor not connected to the drive. Motor not stopped.
+ Remedy:
- Check that the motor/drive are compatible.
- Check that the motor is present during auto-tuning.
- If an output contactor is being used, close it during auto-tuning.
- Check that the motor is stopped during the tune operation.
bLF [Brake Control]
- Cause: Brake release current not reached.
+ Remedy:
- Check the drive/motor connection.
- Check the motor windings.
- Check the [Brake release I FW] (Ibr) and [Brake release I Rev] (Ird) settings.
- Apply the recommended settings for [Brake engage freq] (bEn).
CnF [Communication Network]
- Cause: Communication interruption on communication card.
+ Remedy:
- Check the environment (electromagnetic compatibility).
- Check the wiring.
- Check the time-out.
- Replace the option card.
- Contact Schneider Electric Product Support.
COF [CANopen Communication]
- Cause: Communication interruption on the CANopen® bus.
+ Remedy:
- Check the communication bus.
- Check the time-out.
- Refer to the CANopen® User's manual.
EPF1 [External Fault-LI/Bit]
- Cause: Event triggered by an external device, depending on the user.
+ Remedy:
- Check the device which caused the trip and reset.
EPF2 [External Fault Communication]
- Cause: Event triggered by a communication network.
+ Remedy:
- Check for the cause of the trip and reset.