ATV 31 fault codes 2
ObF - Overvoltage during deceleration
- This error occurs when there is braking that is too sudden or the driving load is too high.
- Increase the deceleration time, install a braking resistor if necessary, and activate the brA function if it is compatible with the application.
OHF - Drive overheated
- This error is triggered when the drive temperature is too high.
- Check the motor load, the drive ventilation, and the environment. Wait for the drive to cool down before restarting.
OLF - Motor overload
- This error is caused by excessive motor current or an incorrect value of parameter rSC.
- Check the ItH setting (motor thermal protection), the motor load, and wait for the drive to cool down before restarting. Measure rSC again for accuracy.
OPF - Motor phase loss
- This error occurs when there is a loss of one phase at the drive output, a downstream contactor is open, the motor is not connected or the motor power is too low, or there is instantaneous instability in the motor current.
- Check the connections from the drive to the motor, set OPL to OAC if a downstream contactor is being used, test on a low power motor or without a motor to deactivate motor phase loss detection, and check and optimize the UFr, UnS, and nCr parameters and perform auto-tuning with tUn.
OSF - Overvoltage
- This error is caused by a line voltage that is too high or a disturbed line supply.
- Check the line voltage to resolve this issue.
PHF - Line phase failure
- This error occurs when the drive is incorrectly supplied, a fuse is blown, there is a failure of one phase, a 3-phase ATV31 is used on a single-phase line supply, or there is an unbalanced load.
- Check the power connection and the fuses, reset, use a 3-phase line supply, and disable the fault by setting IPL to nO.
SLF - Modbus fault
- This error is caused by an interruption in communication on the Modbus bus, or when the remote terminal is enabled (LCC = YES) and the terminal is disconnected.
- Check the communication bus, refer to the product-specific documentation, and check the link with the remote terminal to resolve this issue.
CFF - Configuration fault
- This error occurs when the current configuration is inconsistent.
- To resolve this, return to factory settings or call up the backup configuration if it is valid. Refer to the FCS parameter in the I-O-, drC-, CtL-, or FUn- menu for guidance.
CFI - Configuration fault via serial link
- This error is triggered by an invalid configuration loaded into the drive via the serial link.
- Check the configuration that was previously loaded and load a consistent configuration to resolve the issue.
USF - Undervoltage
- This error occurs when the line supply is too low, there is a transient voltage dip, or the load resistor is damaged.
- Check the voltage and the voltage parameter to resolve this issue. The USF trip threshold varies depending on the model of the ATV31:
- - ATV31ppppM2: 160V
- - ATV31ppppM3X: 160V
- - ATV31ppppN4: 300V
- - ATV31ppppS6X: 430V
- If the issue persists, consider replacing the drive.