ATV 21 fault codes 2
- OL1 (Drive Overload): The drive is overloaded. Possible causes include too short acceleration time, too high DC injection current level, incorrect setting of parameter Pt, starting into a rotating load, or an excessively large load. Solutions include increasing acceleration time parameters (ACC or F500), reducing the setting of parameters F251 and/or F252, selecting the correct setting for parameter Pt, enabling catch on the fly (parameter F301), setting parameter F302 to 2, or using a drive with a higher power rating.
- OL2 (Motor Overload): The motor is overloaded. This can be due to incorrect setting of parameter Pt, a jammed motor, continuous low-speed operation, or excessive load applied to the motor. Solutions include selecting the correct setting for parameter Pt, checking the load, and adjusting parameter OLN to the overload level that the motor can withstand during low-speed operation.
- OP1 (Overvoltage During Acceleration): Overvoltage occurs during acceleration. Causes include abnormally fluctuating input voltage, a power network greater than 200 kVA, power factor capacitor switching, SCR switching on the power network, starting into a rotating load, or intermittent output phase fault. Solutions include installing a line reactor, enabling catch on the fly (parameter F301), setting parameter F302 to 2, and determining and rectifying the cause of the missing output phase.
- OP2 (Overvoltage During Deceleration): Overvoltage occurs during deceleration. Causes include too short deceleration time, overhauling load, abnormally fluctuating input voltage, a power network greater than 200 kVA, power factor capacitor switching, SCR switching on the power network, starting into a rotating load, or intermittent output phase fault. Solutions include increasing deceleration time parameters (DEC or F501), enabling parameter F305, installing a line reactor, checking the input and output circuits for phase failure and rectifying, and enabling catch on the fly (parameter F301).
- OP3 (Overvoltage During Constant Speed Operation): Overvoltage occurs during constant speed operation. Causes include abnormally fluctuating input voltage, a power network greater than 200 kVA, power factor capacitor switching, SCR switching on the power network, regenerative drive operation, or intermittent output phase fault. Solutions include installing a line reactor, checking the input and output circuits for phase failure and rectifying.
- Ot (Overtorque Fault): The calculated motor torque has reached the level set by parameter F616. Solutions include adjusting the settings of parameters F615 and F616 as needed and verifying machine operation.
- SOUt (Permanent Magnet Motor Pulls Out of Synchronism): The permanent magnet motor is out of synchronism. Causes include a jammed motor, output phase loss, or impact load. Solutions include checking the load and correcting the jammed condition, and checking the condition of the motor and load wiring.
- UC (Underload Fault): The measured motor current has dropped below the level set by parameter F611. Solutions include checking parameters F610–612 for the correct settings.
- UPI (DC Bus Undervoltage Fault): The input voltage is too low. Solutions include checking the input voltage and rectifying the problem, selecting the correct setting for parameter F627, enabling catch on the fly (parameter F301), and setting parameter F302 to 2.
- Atn1 (Auto-tuning): Auto-tuning is in process. This is normal if the message disappears after a few seconds.
- CLr (Clear command acceptable): This message is displayed after the STOP key is pressed while an error code is displayed. Press the STOP key again to clear the fault.
- db (DC braking): DC braking is in process. The alarm code goes off in several seconds if no problem occurs.
- E-17 (Graphic display terminal error): A graphic display terminal key has been held down for more than 20 seconds, or a key may not be operating properly. Release the key. If the error does not clear, replace the drive.
- EI (Exceeded display digits): The number of digits entered for values such as frequencies is more than 4. Lower the frequency free-unit magnification (F702).
- EOFF (Emergency stop command acceptable): The operation panel is used to stop the operation in automatic control or remote control mode. Press the STOP key for an emergency stop. To cancel, press any other key.
- Err1 (Frequency point setting error alarm): The frequency setting signals at points 1 and 2 are set too close to each other. Set them apart from each other.
- h999 (Integral input power): Integral input power is more than 999.99 kWh. Press and hold down the key for 3 seconds or more when power is off or when the input terminal function CKWH is turned on or displayed.
- H999 (Integral output power): Integral output power is more than 999.99 kWh. Press and hold down the key for 3 seconds or more when power is off or when the input terminal function CKWH is turned on or displayed.
- HEAd/End (Display of first/last data items): The first and last data item in the auh data group is displayed. Press the MODE key to exit the data group.
- H1LO (Parameter adjustment error): During programming, a value was entered that exceeds the maximum or minimum value of the parameter. Enter a value within the bounds of the parameter.
- InIt (Parameters in the process of initialization): Parameters are being initialized to default values. This is normal if the message disappears after several seconds.
- LStp (Auto-stop because of continuous operation at the lower-limit frequency): The automatic stop function selected with F256 was activated. To deactivate, increase the frequency command above the lower-limit frequency LL+F391 or turn off the operation command.
- NOFF (Line supply undervoltage fault): The phase-to-phase input voltage is too low. Measure the main circuit supply voltage. If the voltage is normal, the drive requires repair.
- OFF (ST terminal OFF): The ST-CC (run permissive) circuit is open. Close the ST-CC circuit.
- rtrY (Restart in process): The drive is in the process of restart after a momentary stop. The drive is operating normally if it restarts after several seconds.
- StOp (Momentary power failure slowdown stop prohibition function activated): The slowdown stop prohibition function set with F302 (momentary power failure ride-through operation) is activated. To restart operation, reset the drive or input an operation signal again.
Pre-alarm Codes:
- C (Current Limit): The drive is at current limit. Refer to parameters F601 and F185.
- P (DC bus overvoltage): The drive is approaching an overvoltage fault due to a high supply line, regenerative motor braking, or a combination of these. Refer to parameters F305 and F626.
- L (Motor overload alarm): The motor overload timer has reached or exceeded 50% of its fault level.
- H (Drive overheating alarm): The drive is approaching an overheating fault.
To reset the drive after a fault condition, clear the cause of the fault trip before resetting. The drive can be reset by turning off the power, through an external signal, with the Stop key on the display terminal, or by a fault clear signal from a remote communication device. For overload functions (OL1 or OL2), the drive cannot be reset by inputting a reset signal from an external device or with the Stop key on the display terminal if the calculated cooling time has not expired (30 seconds for OL1, 120 seconds for OL2).