ATV 12 Fault Codes index
CrF1 Precharge: Charging relay control fault or charging resistor damaged; switch the drive off and on, check the connections and stability of the main power supply, and contact your Schneider Electric representative if necessary. (continued >>)
InFI Unknown Drive Rating: The power board differs from the stored board; contact your Schneider Electric representative.(continued >>)
InF2 Unknown or Incompatible Power Board: The power board is not compatible with the control board; contact your Schneider Electric representative.(continued >>)
InF3 Internal Serial Link: Communication interruption between internal boards; contact your Schneider Electric representative.(continued >>)
InF4 Invalid Industrialization Zone: Inconsistent internal data; contact your Schneider Electric representative.(continued >>)
InF9 Current Measurement Circuit: Current measurement is incorrect due to a hardware circuit fault; contact your Schneider Electric representative.(continued >>)
InFb Internal Thermal Sensor Fault: The temperature sensor is faulty, or there is a short/open circuit in the drive; contact your Schneider Electric representative.(continued >>)
InFE Internal CPU: Internal microprocessor fault; switch the drive off and on, and contact your Schneider Electric representative if the fault persists.(continued >>)
OCF Overcurrent: Motor control parameters are incorrect, inertia/load is too high, or there is a mechanical blockage; check the parameters, motor/drive/load sizing, mechanism, cables and insulation; connect line chokes and reduce SFr if necessary.(continued >>)
SCF1 Motor Short Circuit: Short circuit/ground fault at the drive output or excessive motor ground leakage; check the motor cables and motor insulation.(continued >>)
SCF4 IGBT Short Circuit: Internal power component short circuit detected at power-up; contact your Schneider Electric representative.(continued >>)
SOF Overspeed: Overspeed caused by instability or high inertia; check the motor and tFr, add a braking resistor if necessary, and adjust the speed loop parameters.(continued >>)
tnF Auto-Tuning: Motor not connected, phase loss, special motor in use, or motor is rotating; check motor/drive compatibility and make sure the motor is connected and completely stopped during auto-tuning.(continued >>)
LFF1 AI Current Loss Fault: AI1 is configured as a current input, but the input current is below 2 mA; check the terminal connection.(continued >>)
ObF Overbraking: Braking is too abrupt or the load is too high; increase the deceleration time, add a braking resistor if necessary, and check the line voltage. (continued >>)
OHF Drive Overheating: Drive temperature is too high; check the motor load, ventilation and ambient temperature; allow the drive to cool before restarting.(continued >>)
OLC Process Overload: The process is overloaded; check the process and drive parameters to ensure compatibility.(continued >>)
OLF Motor Overload: Excessive motor current has been detected; check the motor thermal protection setting and motor load.(continued >>)
OPF1 1 Output Phase Loss: One phase is missing at the drive output; check the drive-to-motor connections and any contactor connections.(continued >>)
OPF2 3 Output Phase Loss: Motor is not connected, motor power is too low, output contactor is open, or motor current is unstable; check the connections, disable OPL if necessary, and check UFr, UnS and nCr parameters before performing auto-tuning.(continued >>)
OSF Mains Overvoltage: Line voltage is above the permitted level; switch the drive off, check the line voltage and restore it to the normal range; set R1 to FLt if necessary. (continued >>)
PHF Input Phase Loss: Supply fault, blown fuse, phase failure or unbalanced load; check the power connections and fuses, use a 3-phase supply, or set IPL to NO.(continued >>)
SCF5 Load Short Circuit: Short circuit at the drive output; check the motor cables and motor insulation.(continued >>)
CFF Incorrect Configuration: The HMI block belongs to a drive with a different rating, or the customer configuration is inconsistent; restore factory settings or load a valid backup configuration; contact your Schneider Electric representative if the fault persists. (continued >>)
CFI (1) Invalid Configuration: The configuration loaded into the drive is inconsistent or the download was not completed; check the previously loaded configuration and load a compatible configuration. (continued >>)
CFI2 Invalid Configuration Download: The download process using Loader or SoMove was interrupted; check the connection, restart the download, or restore the factory settings. (continued >>)
USF Undervoltage: Line supply voltage is too low or a temporary voltage drop has occurred; check the voltage and the USb- parameters. (continued >>)