ATV 12 Fault Codes index


The Schneider Electric Altivar 12 (ATV12) variable speed drive displays fault codes when it detects an electrical, thermal, motor-related or communication problem. The list below provides the main fault codes that may appear on the drive, together with clear and concise explanations. Recommended checks and corrective actions are included for each fault to help identify the problem quickly and return the drive to safe and reliable operation. Correctly interpreting the fault code is essential to avoid unnecessary component replacement and reduce production downtime.


CrF1 Precharge: Charging relay control fault or charging resistor damaged; switch the drive off and on, check the connections and stability of the main power supply, and contact your Schneider Electric representative if necessary. (continued >>)

InFI Unknown Drive Rating: The power board differs from the stored board; contact your Schneider Electric representative.(continued >>)

InF2 Unknown or Incompatible Power Board: The power board is not compatible with the control board; contact your Schneider Electric representative.(continued >>)

InF3 Internal Serial Link: Communication interruption between internal boards; contact your Schneider Electric representative.(continued >>)

InF4 Invalid Industrialization Zone: Inconsistent internal data; contact your Schneider Electric representative.(continued >>)

InF9 Current Measurement Circuit: Current measurement is incorrect due to a hardware circuit fault; contact your Schneider Electric representative.(continued >>)

InFb Internal Thermal Sensor Fault: The temperature sensor is faulty, or there is a short/open circuit in the drive; contact your Schneider Electric representative.(continued >>)

InFE Internal CPU: Internal microprocessor fault; switch the drive off and on, and contact your Schneider Electric representative if the fault persists.(continued >>)

OCF Overcurrent: Motor control parameters are incorrect, inertia/load is too high, or there is a mechanical blockage; check the parameters, motor/drive/load sizing, mechanism, cables and insulation; connect line chokes and reduce SFr if necessary.(continued >>)

SCF1 Motor Short Circuit: Short circuit/ground fault at the drive output or excessive motor ground leakage; check the motor cables and motor insulation.(continued >>)

SCF4 IGBT Short Circuit: Internal power component short circuit detected at power-up; contact your Schneider Electric representative.(continued >>)

SOF Overspeed: Overspeed caused by instability or high inertia; check the motor and tFr, add a braking resistor if necessary, and adjust the speed loop parameters.(continued >>)

tnF Auto-Tuning: Motor not connected, phase loss, special motor in use, or motor is rotating; check motor/drive compatibility and make sure the motor is connected and completely stopped during auto-tuning.(continued >>)

LFF1 AI Current Loss Fault: AI1 is configured as a current input, but the input current is below 2 mA; check the terminal connection.(continued >>)

ObF Overbraking: Braking is too abrupt or the load is too high; increase the deceleration time, add a braking resistor if necessary, and check the line voltage. (continued >>)

OHF Drive Overheating: Drive temperature is too high; check the motor load, ventilation and ambient temperature; allow the drive to cool before restarting.(continued >>)

OLC Process Overload: The process is overloaded; check the process and drive parameters to ensure compatibility.(continued >>)

OLF Motor Overload: Excessive motor current has been detected; check the motor thermal protection setting and motor load.(continued >>)

OPF1 1 Output Phase Loss: One phase is missing at the drive output; check the drive-to-motor connections and any contactor connections.(continued >>)

OPF2 3 Output Phase Loss: Motor is not connected, motor power is too low, output contactor is open, or motor current is unstable; check the connections, disable OPL if necessary, and check UFr, UnS and nCr parameters before performing auto-tuning.(continued >>)

OSF Mains Overvoltage: Line voltage is above the permitted level; switch the drive off, check the line voltage and restore it to the normal range; set R1 to FLt if necessary. (continued >>)

PHF Input Phase Loss: Supply fault, blown fuse, phase failure or unbalanced load; check the power connections and fuses, use a 3-phase supply, or set IPL to NO.(continued >>)

SCF5 Load Short Circuit: Short circuit at the drive output; check the motor cables and motor insulation.(continued >>)

CFF Incorrect Configuration: The HMI block belongs to a drive with a different rating, or the customer configuration is inconsistent; restore factory settings or load a valid backup configuration; contact your Schneider Electric representative if the fault persists. (continued >>)

CFI (1) Invalid Configuration: The configuration loaded into the drive is inconsistent or the download was not completed; check the previously loaded configuration and load a compatible configuration. (continued >>)

CFI2 Invalid Configuration Download: The download process using Loader or SoMove was interrupted; check the connection, restart the download, or restore the factory settings. (continued >>)

USF Undervoltage: Line supply voltage is too low or a temporary voltage drop has occurred; check the voltage and the USb- parameters. (continued >>) 