ATV 12 fault codes 2
The Drive Does Not Start and No Fault Code Is Displayed
If the display does not light up, check the drive’s power supply, paying particular attention to the ground connection and input phase connections.
The assignment of the “Fast Stop” (FSt) or “Freewheel Stop” (nSt) functions can prevent the drive from starting until the corresponding logic inputs (LI) are energized. On the ATV12, “nSt” is displayed during a freewheel stop, “FSt” during a fast stop, and “rdY” in the freewheel stop mode. These functions are designed to be active at logic level 0, which means that the drive will stop in the event of a broken control wire. Therefore, check the LI assignments in the COnF / FULL / FUn- / Stt- menu.
Make sure that the run command input(s) are enabled according to the selected control mode. In particular, check the tCC (Control Type) and tCt (2-wire Control Type) parameters in the COnF / FULL / I_O menu.
If the reference channel or command channel is assigned to Modbus, the drive may display “nSt” (Freewheel Stop) when power is applied and remain in the stopped state until it receives a run command via the communication bus.
The RUN button is disabled by default in the factory settings. To control the drive locally, set Fr1 (Reference Channel 1) and Cd1 (Command Channel 1) appropriately in the COnF / FULL / CtL menu. Refer to the relevant instructions for the local control procedure.
Fault Detection Codes That Cannot Be Automatically Cleared
The cause of the detected fault must be corrected before the fault can be cleared. Resetting the drive without eliminating the underlying problem may cause the fault to reappear.
The SOF and tnF faults can also be reset remotely through a logic input (LI). To enable this function, assign the appropriate logic input to the rSF (Detected Fault Reset Assignment) parameter in the COnF / FULL / FLt menu.
ObF Overbraking:
- Possible Causes: Braking too sudden or driving load too high.
+ Remedies: Increase the deceleration time, install a module unit with a braking resistor if necessary, check the line supply voltage, to be sure that it is under the maximum acceptable (20% over maximum line supply during run status).
OHF Drive Overheat:
- Possible Causes: Drive temperature too high.
+ Remedy: Check the motor load, the drive ventilation, and the ambient temperature. Wait for the drive to cool down before restarting. See Mounting and temperature conditions page 13.
OLC Process Overload:
- Possible Causes: Process overload.
+ Remedy: Check the process and the parameters of the drive to be in phase.
OLF Motor Overload:
- Possible Causes: Triggered by excessive motor current.
+ Remedy: Check the setting of the motor thermal protection, check the motor load.
OPF1 1 Output Phase Loss:
- Possible Causes: Loss of one phase at drive output.
+ Remedy: Check the connections from the drive to the motor, in case of using downstream contactor, check the right connection, cable, and contactor.
OPF2 3 Output Phase Loss:
- Possible Causes: Motor not connected, motor power too low, below 6% of the drive nominal current, output contactor open, instantaneous instability in the motor current.
+ Remedies: Check the connections from the drive to the motor, test on a low-power motor or without a motor: In factory settings mode, motor phase loss detection is active. To check the drive in a test or maintenance environment, without having to use a motor with the same rating as the drive, deactivate motor phase loss detection Output Phase loss detection OPL = NO, check and optimize the following parameters: IR compensation (law U/F) UFr, Rated motor voltage UnS and Rated motor current nCr and perform an Auto-tuning tUn.
OSF Main Overvoltage:
- Possible Causes: Line voltage too high: At drive power-on only, the supply is 10% over the maximum acceptable voltage level, power with no run order, 20% over the maximum line supply.
+ Remedy: Turn Off the Drive. Check and adjust the line voltage. After the line comes back to nominal voltage (within tolerance) do power On. If intermittent OSF code appears, set Relay R1 to FLt and it can be connected to upstream protection to avoid overvoltage in the drive. In this case, LO1 can be used for other drive statuses see page 53.
PHF Input Phase Loss:
- Possible Causes: Drive incorrectly supplied or a fuse blown, failure of one phase, 3-phase ATV12 used on a 1-phase line supply, unbalanced load.
+ Remedies: Check the power connection and the fuses, use a 3-phase line supply, disable the fault by setting Input Phase loss detection IPL page 94 = NO.
SCF5 Load Short Circuit:
- Possible Causes: Short-circuit at drive output.
+ Remedy: Check the cables connecting the drive to the motor, and the motor's insulation.
CFF Incorrect Configuration:
- Possible Causes: HMI block replaced by an HMI block configured on a drive with a different rating, the current configuration of customer parameters is inconsistent.
+ Remedies: Return to factory settings or retrieve the backup configuration if it is valid. If the fault remains after reverting to the factory settings, contact your local Schneider Electric representative.
CFI (1) Invalid Configuration:
- Possible Causes: Invalid configuration. The configuration loaded in the drive via the bus or communication network is inconsistent. The configuration upload has been interrupted or is not fully finished.
+ Remedy: Check the configuration loaded previously. Load a compatible configuration.
CFI2 Download Invalid Configuration:
- Possible Causes: Interruption of the download operation with Loader or SoMove.
+ Remedy: Check the connection with Loader or SoMove. To reset the default re-start the download operation or restore the factory setting.
USF Undervoltage:
- Possible Causes: Line supply too low, transient voltage dip.
+ Remedy: Check the voltage and the parameters of Undervoltage Phase Loss Menu USb- page 95.