Teco L510 fault codes

TECO L510 Fault Codes and Troubleshooting

Below are common TECO L510 fault codes, stop messages and basic troubleshooting checks. Before working through a fault, check the incoming supply, motor wiring, grounding, mechanical load and run command.

Basic Operating Problems

Motor Runs in the Wrong Direction

- Check the Forward and Reverse input wiring.
- If an analog frequency reference is being used, check the signal wiring.
- Make sure the correct operating mode has been selected.

Motor Speed Cannot Be Adjusted

- Reduce the mechanical load if it is too high.
- Check the motor data, including pole count and rated voltage.
- Check the machine gear ratio.

Motor Speed Is Too High or Too Low

- Check the maximum output frequency setting.
- Reduce the load if necessary.
- Check for large changes in the mechanical load and make sure the motor and inverter are correctly sized.
- On an unstable single-phase supply, an AC input reactor may help.

Motor Speed Changes Erratically

- Check the incoming supply for voltage fluctuations or phase loss.
- Check that power is connected to the correct L1, L2 and L3 terminals.
- Make sure the input voltage is correct and the power terminals are tight.
- Check the voltage at T1, T2 and T3.
- Check for excessive mechanical load or a stalled motor.
- Confirm that a Forward or Reverse RUN command is present.
- If analog speed control is used, check both the signal voltage and wiring.

Motor Will Not Run

- Check the selected operating mode.
- Try running the drive from the keypad to see whether the problem is in the external control circuit.

TECO L510 Fault Codes

-oV- – Overvoltage While Stopped

Possible cause: Voltage detection circuit fault.

Check: Measure the incoming supply voltage. If the supply is normal and the fault remains, the voltage detection circuit should be inspected.

-LV- – Undervoltage While Stopped

Possible causes:
- Incoming voltage too low.
- Pre-charge resistor or fuse fault.
- Voltage detection circuit fault.

Check: Verify the supply voltage, pre-charge resistor and fuse. If these are normal, the detection circuit may need inspection.

-oH- – Overtemperature While Stopped

Possible causes:
- Temperature detection circuit fault.
- High ambient temperature.
- Poor ventilation.

Check: Check the ambient temperature and panel ventilation. If cooling conditions are normal, inspect the temperature detection circuit.

CtEr – Current Sensor Detection Error

Cause: Current sensor or current measurement circuit fault.

Check: The drive's current sensing circuit should be inspected.

EPr – EEPROM Error

Cause: EEPROM memory or related control circuit fault.

Check: If the fault cannot be cleared with a normal power cycle, the EEPROM or control board may need inspection.

Cot – Communication Error

Cause: Loss of communication or incorrect communication settings.

Check: Check the communication wiring, terminals and related parameters.

Faults During Operation

oC-A – Overcurrent During Acceleration

Possible causes:
- Acceleration time too short.
- Motor rating higher than the inverter rating.
- Short circuit between the motor winding and frame.
- Ground fault in the motor cable.
- IGBT power module fault.

Check: Increase the acceleration time. Check that the motor and inverter ratings match, and test the motor and cable insulation.

oC-C – Overcurrent at Constant Speed

Possible causes:
- Sudden load change.
- Disturbance on the incoming supply.

Check: Check the mechanical load and incoming supply. If the drive is operating close to its limit, check whether a larger inverter is required. An input reactor may help on an unstable supply.

oC-d – Overcurrent During Deceleration

Cause: Deceleration time is too short for the load.

Check: Increase the deceleration time.

oC-S – Overcurrent at Start

Possible causes:
- Short circuit between the motor winding and frame.
- Ground fault in the motor or motor cable.
- IGBT power module fault.

Check: Test the motor and motor cable insulation. If both are good, the inverter power stage may need inspection.

oV-C – Overvoltage During Operation / Deceleration

Possible causes:
- Deceleration time too short.
- High load inertia.
- Unstable incoming voltage.

Check: Increase the deceleration time. If the application produces regenerative energy, use a braking resistor or braking unit. An input reactor may also help where the supply is unstable.

oC – Overcurrent While Stopped

Cause: Current detection circuit fault.

Check: Check the motor and power wiring. If the fault remains, the current sensing circuit should be inspected.

oL1 – Motor Overload

Cause: The mechanical load may be too high for the motor.

Check: Check the mechanical load and motor sizing.

oL2 – Inverter Overload

Cause: The load is above the inverter's continuous capacity.

Check: Reduce the load or use an inverter with a suitable current and overload rating.

LV-C – Undervoltage During Operation

Possible causes:
- Incoming voltage too low.
- Supply voltage fluctuating.

Check: Measure the supply voltage under load. If the supply is unstable, an input reactor may help.

Keypad and Parameter Messages

LoC – Parameter / Direction Lock

This message can appear when parameter editing, motor direction or password protection is locked.

Check: According to the source documentation, check parameters 13-06 and 11-00, or enter the correct password.

Err1 – Keypad Operation Error

This can occur when ▲ / ▼ is used while a preset speed is active, or when a parameter that cannot be changed during RUN is edited.

Check: Stop the drive and, where required, confirm 00-05 / 00-06 = 0.

Err2 – Parameter Setting Error

The entered parameter values do not meet the required relationship. The source documentation refers to 00-13 and the condition 00-12 ≤ 00-13.

Check: Review the related parameters and set them within the permitted range.

Err5 – Parameter Cannot Be Changed During Communication

A parameter change is being attempted while communication is active.

Check: Issue the required enable command before communication and set parameters 09-02 to 09-05 beforehand.

Err6 – Communication Error

Possible causes:
- Incorrect communication wiring.
- Incorrect communication parameters.
- Communication protocol mismatch.

Check: Check the communication hardware, wiring and parameter settings.

Err7 – Parameter Conflict / Detection Circuit Error

This may occur while changing functions 13-00 / 13-08, or if the voltage/current detection circuit is not operating correctly.

Check: Reset the inverter. If the fault returns, the detection circuit should be inspected.

Stop Messages

StP0 – Zero Speed at Stop

This message can appear when the frequency reference is below 0.1 Hz. It does not always indicate an actual fault.

StP1 – Direct Start at Power-up Disabled

This can occur when the inverter is in external terminal control (00-02 / 00-03 = 1) and direct start is disabled (07-04 = 1).

Check: If automatic start is required by the application, check the setting and description of parameter 07-04.

StP2 – Keypad STOP

This message appears when the keypad STOP key is pressed while the inverter is operating in external control mode.

Check: Release and reapply the external RUN command.

E.S. – External Rapid Stop

The inverter decelerates to a stop when an external rapid-stop signal is received through a multifunction input.

b.b. – External Base Block

When the Base Block input becomes active, inverter output is disabled and the motor normally coasts to a stop.

PdEr – PID Feedback Loss

The inverter has detected loss of the PID feedback signal.

Check: Check the feedback sensor, analog input and related wiring.