6ES7326-1RF00-0AB0
Siemens 6ES7326-1RF00-0AB0 – S7-300 SM 326, 8 NAMUR Fail-safe Digital Inputs
6ES7326-1RF00-0AB0 is an SM 326 fail-safe NAMUR digital input module in the Siemens SIMATIC S7-300 family. It supports NAMUR sensors and mechanical contacts wired with the manufacturer’s specified resistor arrangement.
Channel arrangement: The module provides 8 single-channel or 4 two-channel inputs. With 1oo2 evaluation, each process signal uses two physical inputs. When choosing a digital input module, determine the usable signal count from the project’s evaluation method.
Supply and connections: The L+ module supply is 24 V DC; the NAMUR sensor supply is 8.2 V DC. A 40-pin front connector is required. Keep the panel power supply connection distinct from the sensor input circuit and check the terminal diagram for the exact model.
Safety level: With an appropriate system design, single-channel evaluation can achieve SIL 2, while two-channel evaluation can achieve SIL 3 / Category 4 / PL e. Installing the module alone does not establish these levels: sensor suitability, wiring and the safety program must be assessed together. Verify compatibility of the selected S7-300 CPU and safety architecture.
Diagnostics and parameters: Wire-break and short-circuit diagnostics are supported. “Group diagnostics” must be enabled on every used channel in safety mode. Enabling diagnostic interrupts is a separate setting. Do not treat these two options as interchangeable in the PLC project; also review the settings for unused channels.
Hazardous-area signals: Suitable intrinsically safe signals from hazardous areas can be connected. The sensor’s permitted zone must not be assumed to match the module’s installation zone. Check the device label, applicable Ex certificate, enclosure and circuit separation requirements together. The manufacturer’s supplementary information for product state 05 onwards describes installation and cable separation conditions.
Project compatibility and used units: Compare the complete order number, hardware revision, STEP 7 hardware definition, F-address and existing station configuration. As with other used automation products, inspect the label, terminals and intervention history. Confirm whether the front connector is included. A test report should identify the sensor or simulator used, channels assessed and diagnostic checks performed; an illuminated input LED alone does not verify the safety function.
PDF files and manuals: Consult the S7-300 files section for wiring and parameter information. Use the SM 326; DI 8 x NAMUR chapter in the S7-300 Fail-safe Signal Modules manual and verify coverage of 6ES7326-1RF00-0AB0 and the actual device revision.
Related topics and categories
S7-300 main page |
S7-300 digital input modules |
S7-300 digital output modules |
S7-300 CPU modules
PLCs and modules |
DIN rail power supplies |
S7-300 files |
Second-hand main page |
OtomasyonAVM home
Manufacturer references: Siemens – S7-300 fail-safe signal modules manual | SM 326 NAMUR product and hazardous-area connection information