6ES7314-1AE01-0AB0
Siemens 6ES7314-1AE01-0AB0 – S7-300 CPU 314, 24 KB
6ES7314-1AE01-0AB0 is a SIMATIC S7-300 CPU 314 central processing unit with 24 KB of work memory, an MPI interface and a 24 V DC supply connection. When selecting this unit from the S7-300 CPU range, check the complete order code, program memory requirements, card architecture, communications and existing module arrangement.
The 1AE01 version and field connections
This CPU has no integrated digital or analog I/O. Field connections use separate digital input modules, digital output modules and analog modules. The onboard channel specifications of CPU 314 IFM and CPU 314C models do not apply.
When replacing a CPU, compare the slot sequence, module codes, I/O addresses and parameters against the existing project. The CPU 314 name alone does not establish interchangeability. If replacing a newer processor with this model, check the 24 KB memory limit and program instruction compatibility beforehand.
MC card, memory and battery condition
The 1AE01 uses the classic Memory Card (MC) architecture, distinct from the Micro Memory Card (MMC) system of later CPUs. Internal RAM load memory allows operation without an MC. Program and data retention during power interruptions must nevertheless be assessed against the memory arrangement and battery condition.
Work memory and load memory are different; a larger MC does not increase the 24 KB work memory. For a used unit, check the card type, contents and inclusion in the delivery. Inspect the backup battery, battery compartment and contacts. An existing program does not establish suitability for the intended machine.
Back up the program, hardware configuration and required data blocks before battery or card replacement, memory reset or a new download. The recommissioning plan should cover machine settings and required retained data as well as loading the program.
MPI communication and CP selection
The onboard interface is MPI; there is no integrated PROFINET/Ethernet or separate PROFIBUS-DP port. Check MPI support, cabling and project settings for the programming adapter and HMI panel.
Ethernet CP compatibility requires particular attention with this older version. The 1AE01 row in Siemens compatibility list 26561772 is not marked compatible with the CP 343-1 models covered by that table. Do not select a communication module solely by the “S7-300 CP 343-1” designation; verify the complete CPU and CP order codes together.
Check the 24 V DC power supply and connections against the CPU and system requirements. Match the hardware catalog selection and CPU version in the STEP 7 project to the actual unit.
Assessing a used CPU
When assessing this CPU among used Siemens products, check MPI access, RUN/STOP transitions, program execution and diagnostic records. In a suitable test setup, also evaluate communication with connected modules and restart behaviour after a power interruption.
Confirm the label photograph, physical condition, test scope and delivery contents before ordering. Do not assume that the MC, battery, power connection parts and bus connector are included.
Related topics and product groups
S7-300 overview | S7-300 CPU modules | Digital input modules
Digital output modules | Function modules | Analog module range
Used Siemens products | Used equipment overview | OtomasyonAVM home
Manufacturer references
Siemens – 6ES7314-1AE01-0AB0 product data sheet (archived copy) | Siemens – S7-300 memory concepts, MC and MMC architectures | Siemens – CPU and Industrial Ethernet CP compatibility list