6ES7 193-4CA40-0AA0
6ES7 193-4CA40-0AA0 – Siemens ET 200S TM-E15S26-A1 terminal module
6ES7 193-4CA40-0AA0 is the TM-E15S26-A1 screw-terminal base used in the Siemens ET 200S system. This 15 mm wide base with 2×6 connection points carries the electronic module’s field wiring and AUX1 connections. The fitted electronic module determines the signal type and channel count. When selecting a replacement, check the full order number, screw termination, terminal markings and intended electronic module together. See the ET 200 system overview for the general arrangement.
Terminals 1–8 and the common AUX1 bus
The base has eight numbered terminals, 1–8, plus auxiliary terminals A3, A4, A7 and A8. The numbered terminals connect to the electronic module; the four A-labelled terminals join the same AUX1 bus. The 2×6 designation therefore describes twelve physical connection points, not twelve independent I/O channels or four separate auxiliary supplies.
AUX1 continues through the base and is accessible at all four auxiliary terminals. The supply buses from the power module also pass through the base. Check the potential carried by AUX1 against the power supply module and station diagram. Do not assume the A-labelled terminals are PE or M without checking the existing wiring.
Comparison with 4CA50, 4CA80 and 4CB20
6ES7 193-4CA50-0AA0 is the TM-E15C26-A1 spring-terminal version, while 6ES7 193-4CA80-0AA0 is the TM-E15N26-A1 Fast Connect version. Both provide a 2×6 connection arrangement. 6ES7 193-4CB20-0AA0 is the TM-E15S24-01 screw-terminal base with 2×4 connections; AUX1 passes through internally without accessible AUX1 terminals on the front. Account for this difference where A3/A4/A7/A8 are used. When comparing other ET 200 terminal bases, matching width alone does not establish compatibility.
Electronic-module examples
The Siemens manuals for the 6ES7 134-4MB02-0AB0 current input module and 6ES7 134-4JB01-0AB0 thermocouple input module list 4CA40 among the usable bases. For example, terminals 4 and 8 on the 4MB02 are L−, while A4 and A8 connect to AUX1. This assignment applies to the 4MB02; use the specific terminal table when wiring another analog input module. For thermocouple applications, also select the compensation method according to the electronic module’s manual.
Two-, three- and four-wire RTD connections
The Siemens system manual shows TM-E15S26-A1 with the 6ES7 134-4NB50-0AB0 RTD High Feature for two-, three- and four-wire sensor connections. Measurement and constant-current terminals are used according to the selected wiring method. Check the sensor’s wire count, terminal arrangement and channel parameter together; replacing the base alone does not change the measurement setting.
Dimensions and packaging
The dimensions are 15 × 157 × 43 mm, in width × height × depth order. One base weighs approximately 83 g, and the manufacturer’s packing unit contains five pieces. Check the advertised quantity separately when buying used equipment, distinguishing an individual base from the manufacturer’s five-piece pack.
Screw termination and mounting
The base mounts on a 35 mm rail. Siemens specifies a 3 mm screwdriver, an 11 mm stripping length and a 0.4–0.7 Nm tightening torque for screw-terminal wiring. Select conductor size and ferrule use from the system manual’s wiring table. Wire with the relevant supply and load voltages switched off, then check wire numbers and mechanical retention.
During commissioning, compare field-wire numbers with the channel definitions in the PLC project. See ET 200 PROFIBUS and PROFINET for the station’s communication side.
Editor’s Note: Terminal condition matters as much as the label when selecting a replacement screw-terminal base. Request clear photographs of the screw heads, wire entries, side contacts and rail latch. Examine any cracked housing, worn screw head or discoloured contact closely. When recording existing wires, distinguish 4 from A4 and 8 from A8.
Manuals and PDF documents
Use the documents in the Siemens ET 200 manuals section. Section 1.7, pages 17–18 of the 04/2007 Terminal Modules manual explains the base arrangement. In the 12/2004 system manual, page 5-8 covers screw wiring and page 12-84 shows RTD connections. Usable bases for the 4MB02 and 4JB01 appear on page 8 of their respective manuals.
Related topics
Browse industrial communication, PLC and HMI and Siemens S7-300 for other components and applications.
Navigation
Siemens ET 200 | Siemens SIMATIC S7 | Siemens automation | OtomasyonAVM home