Series: Siemens SIMATIC SC / Smart Connect. Category: Supplementary terminal block for TB 16SC and TB 16IM-SC in the ET 200 family.

6ES7 120-2BH00-0AA0 is a two-tier supplementary terminal with spring connections for Smart Connect field wiring. It provides additional connection points for extending a two-wire arrangement to three- or four-wire wiring. Its purpose is to bring common-potential connections together beside the station.

Internal connections and purpose

All terminals within each tier are internally connected. Conductors attached to the same tier share a common potential. Independent sensor signals or different supply potentials must therefore not be assigned to that same tier. Identify each tier’s intended potential clearly in both the cabinet diagram and terminal labeling.

This accessory adds no digital input or digital output channels. It creates no electronics slots or additional I/O addresses; it supports the wiring of existing field devices. Assess power supply selection separately from potential distribution. Additional connection points do not increase the current capacity of the existing supply group.

Compatible terminal blocks and related order numbers

Siemens specifies this supplementary terminal for TB 16SC and TB 16IM-SC. Examples of spring-terminal base blocks are 6ES7 120-0BH01-0AA0 and 6ES7 120-0BH50-0AA0. The supplementary terminal does not replace either base block. Check the base label and its underside mounting arrangement when selecting the accessory.

Within the same accessory range, 6ES7 120-1BH00-0AA0 is the single-tier spring version, while 6ES7 120-2AH00-0AA0 is the two-tier screw version. 6ES7 120-1AH00-0AA0 is the single-tier screw type. Compare the number of tiers and conductor clamping method alongside the complete order number.

Dimensions and mounting

The manual’s two-tier accessory drawing specifies 115 mm width, 38 mm height and 40 mm installation depth. These dimensions describe the supplementary terminal, not the complete station’s cabinet space requirements. Allow additional room for cable bends and access to the terminals.

The accessory engages with guides underneath the base terminal block and locks into position. Check that it seats fully and that wiring does not pull on the assembly. When inspecting connection components, examine conductor retention, plastic guides and locking features together.

Distinguishing M, PE and shield connections

The manual describes the upper tier as a distribution point for M or another designated common potential, and the lower tier for suitable sensor grounding and shield connections. Labeling must match the selected use. M, PE and cable shielding serve different purposes; check the actual connections against the installation diagram.

Siemens specifies a particular selection requirement: protective conductor connections associated with AC modules or a relay module switching circuits without safe electrical isolation require a screw-type supplementary terminal. The spring-connected 2BH00 version should therefore not be treated as interchangeable with the screw version for that application. The metal shield terminal is also a separate accessory.

Editor’s note: Inspect more than the housing. With the part de-energized and disconnected from the installation, check continuity within each tier, conductor retention and mounting locks. An old M or PE label does not prove that the wiring still matches it; compare it with the cabinet diagram first. Because each tier is internally connected, one incorrect connection can affect several field devices.

PDF documentation and manuals

In the ET 200L, ET 200L-SC and ET 200L-SC IM-SC manual, Section 2.7 covers mounting, Sections 3.8–3.9 cover use and shielding, and Section 7.7 provides order numbers and dimensions. Visit the Siemens ET 200 PDF and user manuals page for documentation.