6ES7 131-4RD00-0AB0
6ES7 131-4RD00-0AB0 is a Siemens 4-channel NAMUR digital input module for the SIMATIC ET 200S distributed I/O system. It evaluates signals from NAMUR sensors and suitably connected mechanical contacts. Channel indicators and group-fault reporting help monitor field signals. Related products are available in our ET200 digital input modules section.
Device Description
The module evaluates sensor states and transfers them through the ET 200S station to the PLC. Suitable NAMUR sensors can monitor position, proximity or mechanical conditions. For switches and relay contacts, select the sensor-type parameter to match the actual wiring arrangement.
The 24 V DC designation refers to the module's load supply. Its Vs sensor supply is 8.2 V DC. This distinction matters when replacing an existing input module: identify the sensor's electrical output characteristics from its documentation, rather than relying on appearance or conductor count.
Technical Data
Manufacturer: Siemens
Order Number: 6ES7 131-4RD00-0AB0
Designation: 4DI NAMUR
System: SIMATIC ET 200S
Inputs: 4
Module Supply: 24 V DC
Sensor Supply: 8.2 V DC — Vs
NAMUR Signal “0”: 0.35–1.2 mA
NAMUR Signal “1”: 2.1–7 mA
Input Delay: Maximum 4.6 ms in either transition direction
Shielded Cable Length: Maximum 200 m
Typical Power Loss: 1.6 W
Process Input Data: 2 bytes; input signals and validity information
Dimensions: 15 × 81 × 52 mm — width × height × depth
Approximate Weight: 35 g
Indicators: Green status LED per channel and red SF LED
NAMUR Sensors and Mechanical Contacts
NAMUR connection: The module determines the input state from the sensor current. Check NAMUR compatibility and connection polarity in the sensor documentation. Do not assume that a standard 24 V sensor output is suitable for this input.
Mechanical contacts: Supported arrangements include contacts without a resistor network, contacts monitored through a 10 kΩ circuit and changeover contacts. The configured sensor type must match the physical circuit. Selecting a circuit with or without a resistor is a different matter from the contact's current open or closed state.
Changeover contacts: One NO/NC contact set uses two input channels. The module evaluates the contact transitions together; the documented permitted changeover time is 300 ms. Account for paired channels when calculating the number of connected devices.
Terminal Module and Connections
The electronic module plugs into a suitable TM-E terminal base. The manufacturer's compatible options include TM-E15C24-A1 — 6ES7 193-4CA30-0AA0. Select a terminal base with the connection method and auxiliary-potential arrangement required by the installation.
Basic terminal functions:
1: DI0 — channel 0
5: DI1 — channel 1
2: DI2 — channel 2
6: DI3 — channel 3
3 and 7: Vs — sensor supply
Some bases provide additional Vs and AUX terminals. Compare the selected sensor wiring diagram with the markings on the actual base. Recording the complete part numbers of connection components makes future replacement easier.
Configuration and Input Validity
The module transmits value-status information alongside the input states. A validity value of 1 means valid, while 0 means invalid. Evaluating this information in the application helps distinguish a usable process signal from a faulty input circuit.
Check the selected device entry, sensor type and diagnostic settings in STEP 7 hardware configuration. Configure unused channels appropriately. If pulse extension is required, assess its effect on machine response and decide how long the event needs to remain visible to the application.
Addressing note: In the IM151-8 PN/DP CPU's default address assignment, this module is handled differently from standard digital modules. Read the assigned input address from hardware configuration rather than estimating it from the slot number. Include the installed communication interface and PROFIBUS/PROFINET arrangement in the project record.
LED Indicators and Troubleshooting
Green channel LEDs: Indicate the corresponding input states.
Red SF LED: Indicates a group fault; read online diagnostics for details.
Wire-break and short-circuit monitoring are available for NAMUR sensors and suitably resistor-wired contacts. Their applicability depends on the configured sensor type. An incorrect contact setting can therefore produce unexpected diagnostics even when the field circuit is physically intact.
For a single-channel fault: Examine the sensor's mechanical position, channel parameters, and cables and connectors together. Establish whether the fault follows the sensor, wiring or module channel before deciding which component to replace.
When several channels are affected: Check the common Vs connection, terminal seating and the station's PM-E supply group. Comparing the power supply output with the voltage reaching the module during operation can reveal connection-related voltage drops.
Installation and Commissioning Recommendations
Record the installation before replacement: Keep the module label, terminal-base identification, sensor model and working project backup together. Clearly identify circuits where different input types share the same cabinet. Organized cabinet connections reduce the chance of working on the wrong channel during maintenance.
Verify each channel through actual operation: Observe the channel LED, PLC input and validity information in both sensor states. For changeover contacts, check both contact paths during switching. Established communication alone does not confirm correct field-signal mapping.
Document the supply groups: Mark which PM-E group is supplied by each DIN rail power supply. This helps identify useful measurement points when several inputs disappear together.
Editor's Recommendations and Related Topics
Use the complete 4RD00 order code and existing project configuration when selecting a spare. Assess revisions such as 4RD02 against their wiring, parameter and compatibility documentation. Confirm separately whether a terminal base shown in a product photograph is included.
For other station components, browse our digital output modules, analog input modules and Siemens ET200 products. For fast-pulse applications, assess the input delay alongside the capabilities of dedicated counter modules.
The NAMUR designation alone does not establish explosion-protection or functional-safety approval. Applications requiring a safety function should use the applicable documentation for ET200 safety modules and PROFIsafe products.
Manuals and Technical Documents
+ Siemens ET200 User Manuals — PDF archive page
+ Siemens 6ES7 131-4RD00-0AB0 Operating Information — ET 200S manual, section 12.8; English PDF
+ ET 200S Module Manual — 4DI NAMUR — December 2005 edition, section 3.9; English PDF
+ Siemens ET200 Archive Catalogue — Digital Modules — catalogue section
Additional technical source: IM151-8 PN/DP CPU addressing information. The EandM and RGB links above are Siemens documents hosted externally.
++ Siemens Automation Main Page >
++ Siemens Automation Contact — for Otomasyon AVM
++ About Siemens ET200 PLC >
Reminder: Please confirm current availability, condition and delivery scope for Siemens 6ES7 131-4RD00-0AB0 and other SIMATIC products with Otomasyon AVM. Some devices are used products; take this into account when purchasing. Products will not be restocked once sold out. This page provides general information; the product label, hardware revision and applicable manufacturer documentation should govern your application.
Note: Manuals, commissioning recommendations and troubleshooting explanations are non-binding and may be updated or improved. The Otomasyon AVM Community welcomes practical experience. You can share your operating and maintenance recommendations with us.