6ES7 138-4CA01-0AA0
Siemens 6ES7 138-4CA01-0AA0 – ET 200S PM-E DC24V Power Module
6ES7 138-4CA01-0AA0 is a PM-E DC24V power module for the ET 200S distributed I/O system within the Siemens SIMATIC ET200 family. It monitors the load supply for the electronic modules in its potential group and makes supply-status information available to the control system. It is one of the standard ET 200S power supply modules used in 24 V DC stations.
The compact article number is 6ES7138-4CA01-0AA0. An external 24 V DC source feeds the station through a suitable TM-P terminal base. The PM-E forms part of the arrangement that distributes and monitors this supply for the relevant module group.
Function within a potential group
ET 200S power distribution is organized through potential groups formed by the terminal bases. A new TM-P base establishes the supply section for the following group. Different loads within one station can therefore be arranged in separate groups according to the project requirements.
If only one module group stops operating on an automation line, the entire station may still be communicating. Reviewing the load voltage monitored by the PM-E together with the PLC diagnostics helps identify the affected supply section.
Main technical characteristics
Product designation: PM-E DC24V
Article number: 6ES7 138-4CA01-0AA0
System family: SIMATIC ET 200S
Rated load voltage: 24 V DC
Maximum current-carrying capacity: 10 A
Consumption from L+ without load: Maximum 4 mA
Typical power loss: 0.1 W
Dimensions, width × height × depth: 15 × 81 × 52 mm
Approximate weight: 35 g
Load-voltage indication: Green PWR LED
Group-error indication: Red SF LED
Internal short-circuit protection: Not provided; external protection is required.
Understanding the 10 A capacity
10 A is the total current limit for the relevant supply group. It does not establish a 10 A rating for each output channel. Individual channel capacity is determined by the output module's own technical specifications.
When assessing the group's digital input modules, digital output modules and analog input modules, account for electronics consumption and the supply arrangements of connected sensors and loads. Simultaneous operation and initial energization also influence power-supply selection.
Compatible terminal bases
The manufacturer's manual lists the screw-terminal options TM-P15S23-A1 / 6ES7 193-4CC20-0AA0 and TM-P15S23-A0 / 6ES7 193-4CD20-0AA0. Spring-terminal options include TM-P15C23-A1 / 6ES7 193-4CC30-0AA0 and TM-P15C23-A0 / 6ES7 193-4CD30-0AA0.
The PM-E electronic module and its terminal block are separate components. Check the AUX1 arrangement as well as the connection method when selecting a base. Other connection modules of the same width may have different electrical arrangements.
The AUX1 difference between A0 and A1 bases
A1 bases provide a continuous AUX1 bus; A0 bases interrupt AUX1. This affects how the auxiliary potential, or the connection assigned to that bus in the project, is carried between groups.
Before replacing an installed base, examine the purpose of AUX1 in the wiring diagram and the grounding arrangement. Selecting solely by screw or spring terminals can overlook the station's existing potential structure.
PWR, SF and load-voltage diagnostics
The PWR indicator provides load-voltage information, while SF indicates an error condition. The “No load voltage” diagnostic function can be parameterized in STEP 7. Its default setting in the manufacturer's manual is disabled, so check the project setting where remote fault reporting is expected.
If the status byte is configured, the module's supply status is updated independently of this diagnostic parameter. Monitoring the power supply and enabling a diagnostic message are therefore separate functions. When voltage is lost, inspect terminal contacts, field supply wiring and connectors as well.
Status byte and address space
Address usage depends on the configured module entry. The S option assigns one input byte to status information. The O option uses eight input bytes and eight output bytes for option handling. With SO, nine input bytes and nine output bytes are allocated, although the ninth output byte is unused.
When replacing the power module or transferring a project, compare the selected catalog entry and address layout as well as the article number. The station's PROFIBUS or PROFINET connection is assessed through its installed interface module.
Module selection and safety applications
This PM-E can supply suitable F-modules. However, the standard PM-E supply function and the PM-E F safety shutdown function are different. The presence of safety modules or PROFIsafe in a station does not give the CA01 a fail-safe output function.
Check the supply type of every card assigned to the 24 V DC group. The manual excludes the 2DI AC120V ST, 2DI AC230V ST and 2DO AC24..230V/1A modules from this power module's group. The specified ambient range for vertical installation of the CA01 is 0 to 55 °C; mounting limits for the other station components must be assessed separately.
PDF manual and technical documentation
Browse our Siemens ET200 manuals and PDF documentation page for related documents. The dedicated manual is titled “Power module PM-E DC24V (6ES7138-4CA01-0AA0)”, document number A5E01119952-02. Use it alongside the ET 200S system documentation for terminal-base selection and the overall station arrangement.
Editor's note: Three details are particularly useful when selecting this module: total group load current, the terminal base's A0/A1 arrangement and whether the project uses a status byte. Recording the electronic-module label together with the base article number helps avoid unnecessary replacement during maintenance.
Related topics and product groups
For other station components, explore ET200 additional modules. Confirm ET 200S compatibility, supply voltage and terminal type together when selecting a component.
Explore: About ET200 | SIMATIC S7 | Siemens S7 PLC products