6ES7 138-7EC00-0AA0 is the PS 120/230 V AC power supply for ET 200iSP stations within the Siemens ET 200 family. Its galvanically isolated outputs supply the power bus, interface module and backplane bus. Within the ET 200 power supply range, it provides the supply and voltage limitation functions required by the ET 200iSP system.

Input voltage and available current

Rated input: 120/230 V AC. Permissible input range: 85–264 V AC. Line frequency range: 47–63 Hz. When reviewing industrial power supply options, distinguish these input ratings from the output current available to the station.

Output current depends on temperature and mounting position. The Siemens 10/2019 manual specifies up to 5 A at −20…+60 °C with horizontal installation in the 230 V AC operating range, reducing to 4 A up to +70 °C. In the 120 V AC operating range, horizontal installation permits 5 A only up to +50 °C. Include these limits when planning ET 200 power distribution.

Terminal bases and redundant supply

Compatible bases are TM-PS-A UC / 6ES7193-7DA20-0AA0 and TM-PS-B UC / 6ES7193-7DB20-0AA0. Match the complete order number when selecting ET 200 terminal blocks. When checking module connections and mounting bases, remember that the power supply and its terminal module are separate components.

Redundant operation requires suitable A and B bases, two power supplies and an interface meeting the manual’s version requirements. Record the IM 152 version when reviewing ET 200 communication interfaces. Adding a second supply does not justify doubling the station load: the remaining supply must support operation after a failure.

Five checks before selection

1. System family: Compare the station label with the ET 200 system architecture and confirm that the application uses ET 200iSP.

2. Incoming supply: Check voltage, frequency, protective devices and grounding against the cabinet schematic. Follow the connection markings on the terminal module.

3. Load calculation: Include the consumption of installed digital input modules and digital output modules together with all other electronics. Recalculate the thermal allowance when adding modules.

4. Redundancy: Record both supply paths, terminal base types and interface version. Assess operation on a single remaining supply against the project limits.

5. Diagnostics and maintenance: Review IM 152 diagnostics in the SIMATIC S7 control system. Distinguish a supply fault from a communication fault before deciding to replace hardware.

Editor’s Note

Assess this supply together with its terminal base and station load. In a potentially explosive atmosphere, wait at least two minutes after unlocking the power supply before removing it. This delay does not replace the other Ex installation and maintenance requirements. Qualified personnel should follow the applicable Siemens instructions.

PDF manuals and connection documents: Visit the Siemens ET 200 manuals and PDF documents page. Refer to ET 200iSP, A5E00247483-AH, 10/2019, section 3.11 for redundancy and section 10.2, pages 237–239 for this supply. Check the product information document against the actual device label and version as well.