6ES7 132-4BB31-0AB0

Siemens Main Menu › SIMATIC S7 › ET 200 Modules

Siemens 6ES7 132-4BB31-0AB0 — ET 200S 2DO 24 V DC / 2 A High Feature

6ES7 132-4BB31-0AB0 is a two-channel High Feature digital output module for ET 200S within the Siemens ET 200 distributed I/O family. It provides 24 V DC / 2 A per channel and measures 15 mm wide. When comparing ET 200 digital output modules, check the complete order number: 0AB0 identifies the HF version; 0AA0 identifies the Standard version.

Using High Feature diagnostics

Wire-break and short-circuit-to-M diagnostics can be enabled per channel; both default to disabled. Wire breaks are detected only while the output is on. An inactive output without an alarm therefore does not prove wiring continuity. Record the output command, actual load response and diagnostic message together to make recurring faults easier to compare.

Current capacity and load selection

The total output current is 4 A per module, not 4 A from either channel. Paralleling outputs to increase current capacity is prohibited. When reviewing ET 200 power supply modules and power distribution and potential groups, include other loads sharing the group.

The outputs have short-circuit protection. Maximum lamp load is 5 W; maximum switching frequency is 100 Hz for resistive loads and 2 Hz for 0.5 H inductive loads. Compare coil inrush and operating frequency as well as steady current when selecting a contactor or valve.

Terminals, communication and fast signals

Match the exact base code against the manual when selecting ET 200 terminal blocks. Review connection modules and wiring arrangements alongside the panel drawing. Similar appearance alone does not establish compatibility. The module supports isochronous operation; verify the selected PROFIBUS and PROFINET interfaces and controller configuration support the intended operating mode.

Applying 24 V load power through a mechanical contact can, depending on the circuit, produce an approximately 50 µs “1” pulse. Include power-up testing when connecting fast inputs such as ET 200 counter modules.

Five checks before selection

1. Exact identification: Confirm 6ES7132-4BB31-0AB0 on the label. Review the ET 200 system and product families to confirm the installed station is ET 200S.

2. Load details: Record voltage, channel current, inrush and switching frequency. Evaluate simultaneous operation of both channels.

3. Project settings: Select the correct module in the SIMATIC S7 hardware configuration. Check whether retaining the last value or applying a substitute value at CPU/master STOP suits the process.

4. Field verification: Compare the output command with actual movement. Where available, check position or running feedback from ET 200 digital input modules.

5. Supply scope: Siemens lists a five-module pack. For individual or used purchases, confirm quantity, terminal-base inclusion and product condition.

Editor's Note

Keep the load label, wiring photographs, supply measurements and project settings in one maintenance record. This provides a stronger basis for deciding whether the module needs replacement.

PDF manuals and wiring diagrams: Visit the Siemens ET 200 manuals and PDF documents page. Manual A5E01077255-01, 04/2007 covers wiring on pages 7–9, electrical limits on 10, parameters on 11 and diagnostics on 13–14.