6ES7 132-4BB30-0AB0
Siemens automation › SIMATIC S7 › Siemens ET 200 › 6ES7132-4BB30-0AB0
Siemens 6ES7 132-4BB30-0AB0 — ET 200S 2 DO High Feature
The 6ES7 132-4BB30-0AB0 is an ET 200S, 2 DO High Feature, 24 V DC / 2 A digital output module in the Siemens ET 200 family. Select ET 200 digital output modules by their complete order number; matching channel counts do not establish matching functionality.
Key specifications
Outputs: 2 channels, 2 A per channel; 4 A total. Width: 15 mm. Diagnostics: wire break and short circuit to M; red SF fault LED. Clocked operation: supported. Do not parallel outputs to increase current capacity.
Terminal base and wiring
Base examples in the manual include TM-E15S24-A1, TM-E15S24-01, TM-E15S23-01 and TM-E15S26-A1. DO0 uses terminal 1; DO1 uses terminal 5. Read the complete base number when selecting ET 200 terminal blocks; do not match ET 200 connection modules by appearance alone. Check supply, M return and auxiliary terminals against the diagram for the installed base.
Distinguish similar order numbers
6ES7132-4BB30-0AA0 Standard and the 6ES7132-4BB30-0AB0 High Feature covered here are different versions. Also assess 6ES7132-4BB31-0AB0 separately. Before replacement, compare the project hardware selection and configured parameters as well as the physical label.
Review the complete station
When assessing ET 200 power supply modules, include every load in the same group. Mark the connections made through ET 200 power distribution components on the panel drawing. Consider starting current and simultaneous operation as well as steady-state consumption.
When recording the ET 200 station configuration, retain the complete model numbers of the PROFIBUS and PROFINET interfaces, their firmware versions and the engineering project together. Review feedback connected to ET 200 digital input modules to compare an output command with the actual field response. For applications with timing requirements, also examine signal exchange with ET 200 function modules.
Five checks before selection or replacement
1. Identity: Read the entire order number and record the distinction between AA0 and AB0.
2. Load: Compare the voltage, steady-state current and starting requirements of the valve, contactor or other connected device.
3. Wiring: Match the terminal base, output addresses and field cable numbers to the existing project.
4. Parameters: Record diagnostic settings and the intended output behaviour when the CPU stops before making changes.
5. Testing: Operate each output separately under controlled conditions; verify the software command, terminal voltage and actual load response together.
Editor's note: An inactive output does not by itself establish a module fault. Checking the supply group, cable and load separately helps avoid unnecessary replacement. Record each diagnostic message with its channel number before clearing it, providing a useful reference for comparison after maintenance.
Manuals and PDF documents
For Siemens ET 200 PDF and user manuals, consult ET 200S — EWA-4NEB780602402-09, section 12.16. Match the wiring diagram and technical limits to the complete order number; do not apply documentation for a different version without checking it.
Related topics
Power and connections: Power supply modules · Terminal blocks · Connection modules · Power distribution modules
Explore the station: About ET 200 · Communication interfaces · ET 200 manuals
Otomasyon AVM | Siemens:
Siemens main menu | Siemens S7 PLC | SIMATIC S7 | ET 200 modules