6ES7 193-4FL00-0AA0
Siemens automation › SIMATIC S7 › Siemens ET 200 › 6ES7193-4FL00-0AA0
Siemens 6ES7 193-4FL00-0AA0 — ET 200S Spring-Type Add-On Terminal
6ES7 193-4FL00-0AA0 is the TE-U120C4x10 spring-type add-on terminal for ET 200S and ET 200S COMPACT applications in the Siemens ET 200 family. It provides additional potential connections for sensor and actuator wiring. The catalogue description 32 channels / 3-wire connection refers to the application arrangement; this component is not an electronic I/O module. Siemens specifies two add-on terminals for the four-wire arrangement.
Connection layout and technical data
40 connection points form four potential groups. Three inserted jumpers create one common potential; removing jumpers allows up to four groups. Dimensions: 120 × 38 × 30 mm; with mounting bracket, 120 × 79 × 30 mm. Weight: approximately 160 g. Siemens specifies 10 A current-carrying capacity for the terminal and jumpers, with connectable potentials up to 230 V AC.
These ratings do not change the operating voltage or channel-current limits of the connected electronics. When reviewing ET 200 power distribution components, calculate the shared supply-path load and individual circuit protection separately. Do not interpret 10 A as an output rating per channel.
Mounting compatibility
The terminal fits beneath a COMPACT TM-C base or a suitable TM-P/TM-E arrangement totalling 120 mm in width. For TM-P/TM-E installations, the outer bases must have equal heights, with no taller base between them. Select ET 200 terminal blocks accordingly; visual similarity between ET 200 connection modules alone does not establish compatibility.
4FL00 versus 4FL10
6ES7193-4FL00-0AA0: TE-U120C4x10, spring terminals. 6ES7193-4FL10-0AA0: TE-U120S4x10, screw terminals. For replacement, check the complete order number, conductor preparation and existing connection method together.
Reviewing the surrounding station
When documenting the ET 200 station layout, identify which field circuits the ET 200 power supply module serves. Match sensor wiring to the ET 200 digital input modules and actuator wiring to the ET 200 digital output modules. Where ET 200 analog input modules are present, record signal commons and shielding separately. Include the station's PROFIBUS and PROFINET interface details in the maintenance record; the physical base and potential arrangement determine add-on terminal selection.
Five checks before selection or replacement
1. Product identity: Verify the full label code and spring-type connections.
2. Mechanical space: Measure the base arrangement, cable clearance underneath and any required bracket space.
3. Jumper map: Photograph jumper positions before removal. Do not assume that the replacement arrives configured for the existing circuit.
4. Potentials and loads: Compare each group's voltage, source, combined load and protective device against the wiring diagram.
5. Replacement checks: Isolate the relevant supplies before removal and wiring. Check group separation and connections before restoring power.
Editor's note: Record jumper positions and each group's purpose alongside the part number. Two terminals with the same order code can perform different wiring roles because their jumper arrangements differ.
Manuals and PDF documents
Visit the Siemens ET 200 PDF and user manuals page for relevant documentation. Terminal modules — A5E01120034-01, section 1.15 covers the terminal design; ET 200S Operating Instructions — A5E00515771-06, sections 4.5–4.6 covers installation and jumper handling.