S7 300 Memory

Siemens S7-300 Memory Cards — MC and Micro Memory Card

Siemens S7-300 memory cards store the user program and load data in compatible S7-300 CPUs. The SIMATIC S7-300 family includes earlier Memory Card (MC) and later Micro Memory Card (MMC) architectures. Select the card by the CPU’s complete order number and supported card type as well as its capacity.

MC and MMC are different card types. Their physical formats and operating requirements differ. “MMC required” in a CPU description does not identify that CPU order number as a memory card; the card is a separate product.

SIMATIC Micro Memory Card — 6ES7953 family

The following SIMATIC MMC order numbers represent different capacities. Check CPU and firmware compatibility when comparing earlier and later revisions with the same capacity.

6ES7953-8LF31-0AA0 — SIMATIC Micro Memory Card (MMC), 64 kB.

6ES7953-8LG31-0AA0 — SIMATIC Micro Memory Card (MMC), 128 kB.

6ES7953-8LJ31-0AA0 — SIMATIC Micro Memory Card (MMC), 512 kB.

6ES7953-8LL31-0AA0 — SIMATIC Micro Memory Card (MMC), 2 MB.

6ES7953-8LM32-0AA0 — SIMATIC Micro Memory Card (MMC), 4 MB.

6ES7953-8LP31-0AA0 — SIMATIC Micro Memory Card (MMC), 8 MB.

Code identification: the 6ES7953-8LF, 8LG, 8LJ, 8LL, 8LM and 8LP families correspond to 64 kB, 128 kB, 512 kB, 2 MB, 4 MB and 8 MB respectively. Use the complete order number, including its revision, when specifying a replacement.

Earlier S7-300 Memory Card — 6ES7951 family

6ES7951 Memory Cards for earlier CPU generations form a different family from 6ES7953 MMCs. For example, 6ES7951-0KE00-0AA0 is a 32 kB, short-design, 5 V Flash EPROM card. An MC cannot be replaced directly by an MMC simply because its capacity is equal or greater.

Card capacity and CPU work memory

Load memory is different from work memory. On compatible MMC-based CPUs, the card provides load memory. A larger card does not increase the PLC processor’s work memory, processing speed or physical I/O count.

Select capacity for the program’s load-memory requirement, hardware configuration and any additional data stored on the card. The CPU’s stated work-memory size alone does not determine the required card capacity.

Program operation and firmware updates have different storage requirements. A card sufficient for the application program may be too small for firmware-update files. Check the CPU and update-package documentation for the minimum capacity instead of applying one value to every S7-300 model.

Card replacement and program backup

Back up the existing project and required data before replacing, erasing or formatting a card. Follow the CPU manual’s operating-state and power-supply requirements. An existing program on a used card may belong to a different machine.

Card replacement involves more than copying files. Match the CPU hardware configuration, HMI connections, field-sensor addresses and output behaviour to the existing project. A stable 24 V DC panel supply is also necessary for reliable CPU operation.

PDF files and compatibility documentation

Visit S7-300 PDF files and manuals for CPU memory architecture, card replacement and program-loading documentation. Check the complete card code, CPU order number and firmware version together.

Related topics and categories

S7-300 main page  |  CPU modules  |  Digital input modules