6ES7334-0CE01-0AA0

Siemens 6ES7334-0CE01-0AA0 — SM 334 Analog Input/Output Module

The 6ES7334-0CE01-0AA0 is an S7-300 SM 334 signal module for the Siemens SIMATIC S7 PLC family, combining 4 analog inputs and 2 analog outputs. Both inputs and outputs operate with 8-bit resolution and support 0–10 V voltage and 0–20 mA current signals. Within the S7-300 analog module range, this model is designated as a non-isolated analog I/O module.

Signal ranges and wiring selection

The four input channels accept voltage or current measurements, while the two output channels provide voltage or current references. Voltage/current selection is determined by terminal wiring; this model does not provide software parameters for changing its signal type or measuring range. During commissioning, the terminal connections and PLC program scaling must match the selected signal.

A 4–20 mA signal can be read within the 0–20 mA input range when the electrical conditions are suitable, but the program must account for the 4 mA starting value when scaling the measurement. This does not provide a separate native 4–20 mA measuring mode or automatic wire-break diagnostics. Suitable analog signal converters may be considered where different signal levels or additional isolation are required.

The module cannot read a Pt100 or thermocouple directly; resistance and direct temperature measurement are not supported. To use temperature sensors, convert the sensor signal through a suitable transmitter or select an input module designed for that sensor type.

Supply, isolation and resolution

The nominal supply is 24 V DC, and field wiring uses a 20-pin front connector. Consider the 8-bit resolution when the application requires fine measurements or small changes in its output reference; displaying additional decimal places in the PLC program does not improve the actual measurement resolution. The voltage outputs require a minimum load resistance of 5 kΩ; the current outputs allow a maximum load resistance of 300 Ω.

There is no galvanic isolation between the analog channels and the backplane bus, or between individual channels; isolation from the load supply is provided. The Siemens manual requires a connection between MANA and the CPU/IM ground M, using a conductor cross-section of at least 1 mm². A missing connection can cause invalid readings, module shutdown and damage during prolonged operation.

Replacement and model comparison

The 6ES7334-0CE01-0AA0 should not be treated as a direct equivalent of the 6ES7334-0KE00-0AB0. The 0CE01 version handles voltage/current signals with 8-bit resolution; the 0KE00 version has 12-bit resolution, Pt100/resistance measurement and a different isolation arrangement. Before replacement, compare the complete order number, addresses, field wiring and program scaling. Explore other PLCs and modules where a different specification is needed.

The manufacturer's removal/insertion with an active backplane bus feature depends on compatible hardware and system conditions. It should not be interpreted as general permission to replace the module under power in a standard S7-300 installation.

PDF files and technical reference

For wiring diagrams, addressing and technical manuals, visit the S7-300 PDF files page. Manufacturer reference: Siemens 6ES7334-0CE01-0AA0 product information.

Related topics and product groups

S7-300 analog modules · Siemens S7 PLC products · What is Pt100? · Temperature sensors · Analog signal converters · PLCs and modules · Second-hand equipment · OtomasyonAVM home