6ES7331-1KF02-0AB0
Siemens 6ES7331-1KF02-0AB0 — SM 331 8-Channel Analog Input Module
6ES7331-1KF02-0AB0 is an S7-300 SM 331 module with 8 analog inputs and 13-bit resolution for Siemens SIMATIC S7 PLC systems. It uses a 40-pin front connector. This model measures voltage, current, resistance and temperature. When comparing S7-300 analog modules, check sensor type, input range, wiring and response time together.
Voltage and current inputs
Voltage ranges are ±50 mV, ±500 mV, ±1 V, ±5 V, ±10 V, 1–5 V and 0–10 V; current ranges are ±20 mA, 0–20 mA and 4–20 mA. The measurement type and range can be selected individually for all eight channels. The output of the field device or analog signal converter must match the STEP 7 settings and program scaling.
Resistance, temperature and motor monitoring
The module supports 0–600 Ω and 0–6 kΩ resistance measurement, plus Pt100, Ni100, Ni1000 and LG-Ni1000 temperature sensors. It also supports motor temperature monitoring using PTC, KTY83/110 and KTY84/130 sensors. For thermocouple applications, select a suitable temperature transmitter and match its output range.
PTC mode does not provide a continuous temperature reading in °C. It supplies normal, prewarning and trip status to the PLC. Program evaluation and the control circuit required to stop the motor must be designed for the application. KTY temperature measurement differs from the threshold monitoring provided by PTC mode.
Power supply, isolation and wiring
The module uses the 5 V backplane supply, drawing up to 90 mA. Two-wire current transmitters require an external supply. Plan transmitter power and signal wiring together, and check the manual for the correct voltage and current input terminals.
There is galvanic isolation between the inputs and backplane; the channels are not isolated from one another. The permitted common-mode voltage between inputs is 2 V DC. For voltage and current measurement, interconnect the relevant M− terminals as specified in the manual. Assess devices with different reference potentials against this limit.
Conversion time and diagnostic limitations
Basic conversion time per channel is 66 ms with 50 Hz interference suppression or 55 ms at 60 Hz. Resistance measurement requires additional conversion time. These figures should not be treated as a fixed update time for the entire module.
Module diagnostics, diagnostic interrupts and limit-value interrupts are not supported. Compare this limitation with the application's fault detection and alarm requirements before purchasing. Measurement plausibility checks can be planned separately in the PLC program.
Replacing 1KF01 and configuring the module
Siemens identifies 6ES7331-1KF02-0AB0 as a compatible spare for 6ES7331-1KF01-0AB0. To use the added PTC/KTY features, check the applicable STEP 7 hardware support / HSP 2067 or the relevant GSD support in an ET200M configuration. When replacing other PLC modules, compare the complete order number, connector and existing channel settings.
PDF files and technical reference
For wiring diagrams and parameters, visit the S7-300 PDF files page. Manufacturer reference: Siemens S7-300 Module Data — Section 6.6.
Related topics and product groups
S7-300 analog modules · Siemens S7 PLC products · What is a thermocouple? · Siemens ET200 · Analog signal converters · PLCs and accessories · Second-hand products · OtomasyonAVM home