6ES5 700-2LB11
Siemens 6ES5 700-2LB11 SIMATIC S5-115U CR 700-2LB central rack
The 6ES5 700-2LB11 is a CR 700-2LB central rack for 19-inch cabinets. It connects a processor from the S5-115U CPU range, such as the CPU 944, to I/O and communications modules on a common backplane. The PS position takes the S5 power supply. The CPU position takes the processor. When replacing the rack, record the full order number and current rating of the installed PS 951 supply.
Slot layout and adapter casing
Figure 3-6 in the Siemens manual shows PS, CPU, numbered positions 0–6 and a separate IM position. The two compact locations in parts listings describe a feature of the rack. The starred positions 0, 1 and 2 call for the 6ES5 491-0LB11 adapter casing. The table shows block-type digital input and digital output modules in positions 3–6. Addressing analog modules in positions 4, 5 and 6 requires IM 306.
The table lists positions 2–5 for the CP 530-7LA12. The IP 246, IP 247 and certain communications processors listed in the manual require a supply other than the 3 A version. Double-width modules can also occupy the adjacent position marked in the table.
Interfaces and rack selection
Figure 3-6 shows the IM 305 and IM 306 in position 6 with an adapter casing. The IM 304, IM 307 and IM 308 are listed in the separate IM position. When replacing an interface, check the rack table and the wiring for the installed interface.
The 6ES5 700-2LA12 has a separate slot table in the manual. The 6ES5 701-2LA12 is the ER 701-2 expansion rack. When replacing the rack, record its label, backplane layout and the condition of cabinet hardware such as the mounting accessories with cable duct. The full-code parts listing gives 483 × 303 × 47 mm (W × H × D) and approximately 5 kg for the 2LB11.
Editor’s note
1. Isolate the cabinet and field power supplies and verify that power is off. Photograph each module label and slot number before removal.
2. For a used rack, ask for a clear photo of the 2LB11 label and the backplane at positions 0–2. Confirm whether the 491-0LB11 adapter casings are included.
3. If a CP or IP module fails, compare its exact order number, adapter, slot and PS current rating with Figure 3-6 before replacing the rack.
4. If only the analog modules in positions 4–6 are unreachable, check the installed IM 306 configuration and module addresses.
5. With the module removed, inspect the slot guides and backplane pins. If a pin is bent or a guide is broken, stop before seating the card.
6. During controlled recommissioning, check CPU status first, then verify local I/O and expansion-unit access separately.
Siemens documents
S5-115U manual, Figure 3-6, p. 3-6 (EN) · Siemens S5-115U declaration of conformity, rack order numbers p. 10 (EN)
Related topics
Used Siemens equipment · S5 racks · SIMATIC S5 · Siemens S5 PLC · Used Siemens main page