6ES5 491-0LA12

Siemens 6ES5 491-0LA12 adapter casing

The 6ES5 491-0LA12 is an adapter casing for fitting a compatible SIMATIC S5 circuit board into an S5-115U mounting rack. Siemens lists this order number as an accessory for the IM 314 and 313 watchdog module and as the casing for the CP 544 in its serial communication example.

IM 314 and the expansion rack

The Siemens manual lists this casing for the IM 314 / 6ES5 314-3UA11, one of the S5 interface modules. In the S5-115U distributed configuration, the IM 304 is at the central controller and the IM 314 is in the ER 701-2 or ER 701-3 expansion rack.

Choose the appropriate 721-series lead from the S5 connecting cables. The 6ES5 721-0BC00 is one example. The Siemens diagram places the 6ES5 760-1AA11 terminator in the lower front connector (X4) on the last IM 314. Check the order numbers of the casing, card, cable and terminator separately.

CP 544 and related casing codes

In Siemens’ S5-to-S7-1500 serial communication example, the CP 544 communications processor uses this casing. The example also lists a 6ES5 944-7UA22 CPU and a 6ES5 951-7LD12 power supply. Check the installed power supply against the requirements of the actual card.

Check the full label on each casing, including the similar 491-0LA11. ST 50 lists the 491-0LB11, 491-0LD11 and 491-0LC11 for up to two, four and six compact cards, respectively. The Siemens manual specifies the 491-0LC11 for CP 551 mass storage. For central racks such as the CR 700-2 and CR 700-3, verify the card’s permitted slot and casing type together.

Editor’s note

+ Before buying, ask for separate photos of the casing and card labels. Confirm whether the offer includes the casing alone or the card as well.

+ Before removal, record the rack code, slot number and card orientation. Mark the IM 314 link cable and the location of the terminator.

+ After safely isolating power, inspect the card guides, retaining screws and rear connector. If the card binds, recheck its orientation and the casing code.

+ If central I/O works but the whole expansion link is missing, check the IM 304 and IM 314 labels. Then check the 721 cable and the X4 terminator on the last IM 314.

+ If CP 544 communication fails, start with the card’s seating in the casing and backplane. Once the physical connection is sound, compare the serial cable and settings with the project record.

+ After installation, keep actuator power circuits isolated while checking expansion inputs in STEP 5. Where a CP 544 is fitted, verify communication on a controlled test link.

To offer a casing for sale, send photos of its label, card guides and rear connector to otomasyonavm@gmail.com.

PDFs and Siemens references

S5-115U manual, IM 314 accessories p. 15-61 (EN) · 313 watchdog module, p. 15-64 (EN) · CP 544 serial communication example, Table 1-3 (EN) · CP 551 casing reference, p. 15-65 (EN) · ST 50, related adapter casings p. 3/98 (EN).

Siemens S5 PDF archive

Related topics

About Siemens S5 PLCs · CP 544 communications processor · 491-0LC11 adapter casing