6ES5 512-5BC12

Siemens 6ES5 512-5BC12 — AS 512 Basic Interface Board

The Siemens 6ES5 512-5BC12 is an AS 512 basic interface board for SIMATIC S5. Its single serial TTY channel and dedicated processor handle a computer or suitable peripheral connection. Within the S5 interface module range, this is the basic board; the expansion board has a different part number.

It serves S5-130W and S5-150A/K/S applications. When assessing an existing Siemens S5 PLC, identify the CPU, rack and communications partner together. Select S5 communications modules by their function and system requirements as well as their front connectors.

TTY channel and active current loop

The basic board has a passive TTY interface. Active current-loop operation requires 24 V DC at the front supply connection. When checking S5 cables and connectors, establish transmit/receive directions, which device supplies the loop current, and the shield connection.

TTY and RS232 use different electrical interfaces. Before choosing an adapter, review the differences between RS232, RS422 and RS485 and the equipment wiring diagram. The pin count of a communications port alone does not establish its signal levels or protocol.

Each channel has its own transmission-rate selector on the board. The sum of the rates of all AS 512 channels in use must not exceed 9600 baud. With the basic and expansion boards operating together, treat this as their combined limit rather than a separate 9600-baud allowance for every port.

Basic board, expansion board and PG interface

The 512-5BC12 is the basic board. The 6ES5 512-5BC21 expansion adds three channels, one switchable to V.24. Do not assign that expansion-board function to the basic board’s single TTY channel.

Keep the 512-5AA12, 512-5AA21 and 512-5BU12 as separate entries in a spare-parts list. Before substitution, compare the complete part number, hardware revision, jumpers and existing software. A shared “512” designation is insufficient.

Assess the 511-5AA12 and 511-5AA14 PG interfaces separately. Distinguish the AS 512 computer link from the AS 511 programming connection. First establish which device communicates through each port.

DUST 3964 and application software

The Siemens catalogue specifies DUST 3964 for computer linking. In the PLC program, inspect the communications blocks, data areas and partner settings together. Completing the cable connection does not establish that application data will reach the intended address.

When reviewing an RK 512 installation, you may encounter solutions such as the CP 524 — 6ES5 524-3UA13, CP 525 — 6ES5 525-3UA11 or CPU 928B — 6ES5 928-3UB11. The manufacturer’s manual lists the IM 512 family among RK 512 communications partners. This does not make those boards interchangeable in the same slot. Match the electrical interface and message requirements separately.

Rack and supply checks

The catalogue lists a basic-board current consumption of 1.6 A at 5 V. Assess its internal supply separately from the 24 V connection used for an active TTY loop. Establish the correct slot from the complete board number and the system connection plan.

Isolating a communications fault

During PLC troubleshooting, first check that the partner is powered and connected to the intended port, then inspect the cable, current loop and rate setting. Next examine communications-block calls and data areas. Record existing settings before adjusting them, and change one variable at a time.

Editor’s note

With these older installations, a little patience before changing boards often saves time. Follow both ends of the cable and establish what is connected. A clear wiring sketch gives you a much firmer starting point for the diagnosis.

On a TTY link, take particular care to establish which end supplies the current. Two passive devices will leave you looking for a board fault when the connection itself needs attention. Check the diagram and measurements before setting aside a serviceable part.

Photograph the jumpers and switches clearly before removing the old board. A spare may carry settings from a completely different machine. Keeping the original arrangement on record makes it much easier to return to a known starting point.

If the machine runs but data no longer reaches the computer, keep the working PLC program intact while you investigate the communications path. Preserving what already works is a valuable workshop habit, especially with equipment of this age.

When buying a used Siemens board, inspect its label, connectors and repair history, and seek a real data-exchange test on a suitable system where possible. A lit indicator is a starting point; stable communications provide much more useful evidence.

OtomasyonAVM resources and PDFs

+ S5 interface modules · S5 communications modules · S5 cables and connectors.

+ OtomasyonAVM S5 PDF archive. For this model’s basic/expansion distinction and system compatibility, consult pages 3/21 and 9/3 of the Siemens ST 53 catalogue below.

Related topics

+ 512-5BC21 expansion board · 511-5AA12 PG interface · Serial interface differences · PLC troubleshooting.

Browse SIMATIC S5

+ S5 interface modules · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand main page.

Siemens and external references

+ Siemens ST 53, 1985 — German; AS 512: 3/21, specifications: 8/2, exact part number: 9/3; third-party archive copy.

+ Siemens SINUMERIK System 8 commissioning document — German; AS 512 jumpers and combined rate limit: 5-16–5-18; third-party archive copy.

+ Siemens CPU 928B/CPU 948 Communication — English; section 4.1.1, IM 512 family in RK 512 installations.