6ES5 324-3UR11
Siemens 6ES5 324-3UR11 – IM 324R Redundant System Coupling Module
6ES5 324-3UR11 is the IM 324R interface module for coupling two central controllers in S5-115H and S5-155H redundant control systems. Within the Siemens SIMATIC S5 family, this S5 interface module provides the parallel link between the controllers.
The IM 324R connects to an IM 304, 6ES5 304-3UB11, using a 721 connecting cable. The specified maximum cable length for this central-controller link is 100 m.
Hardware version requirement for S5-115H
For an S5-115H installation using the CPU 942H, Siemens’ English system manual requires IM 324-3UR11 hardware version 6 or later and IM 304-3UB11 or a later version. Check the version marking as well as the order number when assessing a used module.
S5-155H link and jumper settings
The CPU 948R system manual describes the IM 324R as providing a 16-bit address/data link to common dual-port RAM. For S5-155H operation, jumper X101/1–2 must be fitted; this setting distinguishes S5-115H from S5-155H use.
Cable length also affects the IM 304 settings. When selecting S5 cables and connectors, record the complete cable code, such as 6ES5 721-0BB60 or 6ES5 721-0BC00, then check the jumper arrangement against the applicable system manual.
Rack, supply and installation records
Before replacement, record the S5 rack type, module position and S5 power supply details. Photographs of the original label, version marking and jumper positions provide a useful basis for comparing the replacement.
The 3UR11 suffix matters. 6ES5 324-3UA12 is a different model; sharing the 324 designation does not establish interchangeability. Use the complete hardware list of the existing SIMATIC S5 system when selecting a replacement.
Different role of the IM 314R
The IM 314R, 6ES5 314-3UR11, serves the I/O connection of a switched expansion unit. Expansion racks such as 6ES5 701-3LH11 belong to that separate arrangement. Keep this role distinct from the IM 324R central-controller link.
Establishing the CPU link does not complete the redundancy configuration of the digital inputs and digital outputs. Review the field modules’ addressing and system parameters separately.
Used-module inspection and functional testing
When assessing a used interface module, check connectors, evidence of board repairs and version markings. As with other communication modules, an illuminated LED alone does not prove full functionality; test the board in the intended H system.
Include grounding and cable shielding in the inspection. Preserve program and parameter backups, and record the S5 memory card contents and CPU details as part of the replacement record.
Editor’s note
Start by reading the whole label. The 324 number may be familiar, but check the 3UR11 suffix too. For S5-115H, look for the hardware version marking as well; a small detail can prevent an unsuitable purchase.
Take a few photographs before removing the old board. Include the jumpers, cable connector and module position. A few minutes spent here can save a long search for the original arrangement later.
Give the cable the same attention as the board. A damaged cable or loose connector can make a working module appear faulty. Check both ends before deciding that the interface needs replacement.
Use the settings for the actual system. Do not assume the S5-115H and S5-155H share one jumper arrangement. Identify the CPU and the correct manual first, then compare the settings calmly.
Be clear about what the test established. A powered board and a board tested between two controllers have different evidence behind them. Record the CPUs, cable and observed system state so the next person has something useful to work with.
OtomasyonAVM resources and PDFs
+ Siemens S5-115H system manual – parallel link, 3-21/3-22 (English PDF)
+ Shared S5 manuals and PDF archive
Related topics
+ IM 304 partner interface module
+ S5 connecting cables and connectors
Browse SIMATIC S5
+ Back to S5 interface modules
+ Used Siemens products and models
Siemens and external references
+ Siemens product record – 6ES5 324-3UR11, IM 324R
+ Siemens S5-115H, 6ES5 998-0UH21 – section 3.4.5, version requirement and connection (English)
+ Siemens S5-155H, 6ES5 998-4SR21 Volume 1 – sections 6.2 and 11.2 (English)