6ES5 308-3UC11
Siemens 6ES5 308-3UC11 — IM 308-C PROFIBUS-DP Master Interface
Siemens 6ES5 308-3UC11 is the IM 308-C PROFIBUS-DP master interface module for SIMATIC S5. It connects S5-115U, S5-135U and S5-155U controllers to distributed I/O stations. Supported communication rates range from 9.6 kbit/s to 12 Mbit/s, with addressing for up to 122 DP slaves. The PROFIBUS-DP network exchanges data between field equipment and the central PLC.
This S5 interface module can operate as a DP master and/or DP slave, depending on configuration, and supports FREEZE and SYNC commands. X3 provides the PROFIBUS-DP interface. Assess the RS-485 electrical arrangement and suitable PROFIBUS connector against the network’s cable and baud-rate requirements.
Supply and rack installation
The module receives 5 V through the S5 I/O bus. Siemens specifies consumption of 0.7 A, typically 0.4 A. There is galvanic isolation between the logic and PROFIBUS-DP. Check the power supply load and permitted rack slot against the installation table for the relevant CPU system.
COM PROFIBUS and memory card
The network configuration generated with COM PROFIBUS is stored on the installed memory card. Siemens’ ordering table lists the 256 KB Flash EPROM 6ES5 374-1KH21 for IM 308-C. Match the complete card number and programming method to the installed hardware. For a used module, confirm whether the memory card is included in the actual delivery.
Compare the addresses in the STEP 5 program with the station and module sequence configured in COM PROFIBUS. Verify that digital input, digital output and analog I/O data reaches the intended addresses. Check the FB IM308C — FB 192 parameters where required by the application’s access method.
Indicators and troubleshooting
The front panel has an RN/ST/OFF mode selector and RN, OF, BF and IF indicators. BF is used for bus-fault assessment, while IF indicates module error conditions. During PLC troubleshooting, record whether an LED is steady or flashing together with the states of the other indicators.
Check PROFIBUS A/B wiring, termination at the line ends, station addresses and configuration. Inspect grounding, shield connections and potential sources of electromagnetic interference. If IF is on, investigate the memory card, its contents and parameter activation as well. An illuminated indicator alone does not prove that the interface hardware has failed.
Revision and model identification
The referenced ET 200 manual applies to 6ES5 308-3UC11 release 6 and later. Record the module revision. 6ES5 308-3UC21, IM 308-B — 6ES5 308-3UB11 and 6ES5 308-3UA12 are separate order numbers. Assess the installed communications hardware, configuration and manufacturer compatibility information together when selecting a spare.
Editor’s note
Find the COM PROFIBUS project before replacing the interface. On an older Siemens S5 system, the working configuration may survive on just one computer. Having the replacement board is only part of getting the network running again.
Treat the memory card as part of the installation. Record its label, capacity and saved configuration. A blank card and a configured card removed from a working system require different preparation.
When BF lights up, check the connector’s termination switch, cable and missing station’s supply before looking for another master. A serviceable master may simply be reporting a small problem elsewhere on the network.
Avoid moving RN/ST/OFF merely to see what happens; it affects data exchange. Photograph its position and record the application state before intervention. Change the interface or memory card with the equipment appropriately de-energized.
For a used module, ask which CPU, memory card and slave were used for testing. A power-up check provides limited information. Loading the configuration, identifying a station and exchanging actual I/O data give a much more useful picture.
OtomasyonAVM resources and PDFs
+ OtomasyonAVM Siemens ET 200 manuals
+ Siemens PROFIBUS connectors and cables
Related topics
+ 6ES5 374-1KH21 — IM 308-C memory card
+ 6ES5 308-3UC21 — different order number
+ 6ES5 308-3UA12 — different IM 308 arrangement
Browse SIMATIC S5
Siemens and external references
+ Siemens ET 200, 2806161–0002 — English; pp. 3-4–3-6: BF/IF and other indicator meanings