6ES5 757-0AA11
Siemens 6ES5 757-0AA11 – PG-MUX 757 Programmer Multiplexer
Siemens 6ES5 757-0AA11 is a PG-MUX 757 programmer multiplexer for SIMATIC S5. It allows one PG to select the programming interfaces of up to eight S5 modules. Access to S5 CPUs and associated modules is provided by electronically switching TTY current-loop interfaces.
It provides a central programming point for selecting different targets. During PLC programming, a connection is established to the selected destination; eight targets are not programmed simultaneously. Record the existing Siemens S5 system arrangement and target module order numbers before commissioning.
Ports and connections
The PG side has one 15-pin female input; the target side has eight 25-pin female outputs. The specified serial interface speed is 9,600 baud. Check the pin assignments when selecting S5 cables and connectors, and identify the interface type independently of the connector’s appearance.
For an installation using a PG 615, PG 675, PG 685 or PG 695, check the actual PG interface and software release together. The programmer’s model name alone does not establish that an installed cable is correct. Establish a known good direct connection before repeating the test through the MUX.
S1, S2 and the STEP 5 connection path
S1 sets the base address, while S2 enables the required interfaces. The relevant STEP 5 release defines the connection through a KOR/MUX path. Check path support when selecting programming software. Older software, including the STEP 5 basic package for PG 685, should be operated using the instructions supplied for its installed release.
Example: With base address 5, IF1=5, IF2=6, IF3=7, IF4=8, IF5=9, IF6=10, IF7=11 and IF8=12. Record this mapping alongside the rack arrangement and labels of connected communications modules. Power-cycle the PG-MUX after changing S1 for the new setting to take effect.
The programming language and connection path are separate settings. Match the PG, MUX channel and target module before opening the project. Preserve the program held on the S5 memory module and in the project files; avoid changing a working program while investigating a connection fault.
Indicators and communication checks
The ON indicator shows mains power, while IF1–IF8 indicate the selected interface. During PLC troubleshooting, compare the target selected in software with the illuminated channel indicator. Alongside general PLC maintenance checks, record the communication result for each output used.
Power and used-unit inspection
The manual describes the unit’s own 230 V / 120 V AC mains supply. Check the actual label and voltage configuration before energising it. Keep S5 power supply connections distinct from the MUX mains input. Include previous repairs and cable changes when inspecting S5 supplementary hardware.
Editor’s Note
First connect the PG directly to the target using a known good cable. Once that works, insert the MUX and test the same target again. With used Siemens equipment, this comparison helps avoid replacing a sound component after an incorrect diagnosis.
One working output is insufficient evidence for an eight-output unit. Select each required channel in turn and observe real communication. Record the channel number and connected device so the next inspection has a useful reference.
Photograph the old unit’s S1 and S2 settings before removal. A replacement may arrive with different settings. Compare the original address plan with the software path before moving switches.
Confirm the identity of the connected CPU again before writing a program. Channel numbers are easy to confuse when several similar machines are involved. Identify the destination before starting a write operation.
Inspect the mains lead, rear label, connector screws and pins. Any voltage reconfiguration requiring the housing to be opened should be performed by qualified service personnel. Combine the physical inspection with recorded channel tests.
OtomasyonAVM resources and PDFs
+ PG 685 programmer, PG 675 programmer and S5 programming cables.
+ Shared SIMATIC S5 PDF archive. Use the Siemens device manual below for the PG-MUX 757’s own connections and settings.
Related topics
+ PLC programming · PLC troubleshooting · S5 interface modules.
Browse SIMATIC S5
+ S5 supplementary modules and accessories · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page.
Siemens and external references
+ Siemens PG-MUX 757 device manual, C79000-Z8577-C367-04, French; online copy of the manufacturer’s document. Application and ports: pages 6–8; addressing: pages 12–14; power: page 15; technical data: page 19.
+ Siemens STEP 5/ST V7.1, C79000-G8576-C920-04, English; chapter 13, KOR/MUX connection path. Check the permitted software address range in the manual for the installed release.