6ES5 458-4UA12

Siemens 6ES5 458-4UA12 – 16-Channel Relay Output Module

6ES5 458-4UA12 is a Siemens SIMATIC S5 module providing 16 individually isolated relay-contact outputs for S5-135U/S5-155U systems. Within the S5 digital output module range, this model requires a nominal 24 V DC L+/L− supply, with an operating range of 20–30 V DC.

For resistive loads, contact capacity is 0.5 A at 60 V DC / 48 V AC with RC protection, or 70 mA at the same voltages without it. The 6ES5 498-1AB11 RC contact-protection submodule covers four outputs. Check the fitted RC submodules when assessing the relay contacts’ load capacity.

Inductive loads and contact protection

For control relays and other coil loads, use the inductive-load requirements. Siemens specifies 0.5 A maximum with both the RC submodule and external suppression circuitry. The lamp-load limit with an RC submodule is 0.1 A.

Supply, enable input and fuses

The digital section takes 5 V, typically 80 mA, from the system bus. L+/L− consumption is typically 200 mA, with 5.2 W dissipation at rated operation. Assess the board’s consumption separately from switched loads when calculating the power supply requirements.

The module has an F+/F− enable input. With jumper X35 fitted, this input is active, as supplied from the factory. Check the enable condition as well as the program command when an output fails to operate. Channel fusing is 16 × 1 A slow-blow; Siemens states that these fuses do not protect the contacts against overload.

Front connector and mechanical construction

The module uses a 42-pin, single-width front connector. Options include 6ES5 497-4UA12 with crimp terminals and 6ES5 497-4UB31 with screw terminals. Prepare the cables and connectors using the manual’s assignments for channel contacts, enable wiring and grounding.

The module occupies one slot, measures 20 × 255 × 195 mm and weighs approximately 0.45 kg. Match its position in a CC 135U/155U central unit or suitable expansion arrangement to the applicable rack layout.

Differences between 4UA11, 4UA12 and 4UA13

Siemens identifies 6ES5 458-4UA13 as the successor to 6ES5 458-4UA11 and this 4UA12. It uses solid-state relays instead of mechanical contacts. The DA 458 note describes integrated RC protection and changes to the supply function and fuse type; review these differences together before replacement.

The 6ES5 458-4UC11 is a separate relay-output model with different voltage and load ratings. Electronic DC outputs such as 6ES5 451-4UA14 and 6ES5 453-4UA12 also have a different output structure from the relay-contact 458-4UA12.

Used-module inspection and channel testing

Testing a used output module should cover all 16 channels, contact resistance and behavior under load. Compare the relevant input signals with output commands, and preserve the existing S5 system’s program and memory-card backups before replacement.

Editor’s note

Check the RC submodules first. A 0.5 A description needs its conditions checked. Without the protection submodule, the 4UA12’s permitted resistive-load current is substantially lower, so identify missing parts before testing.

A relay click is only a starting point. The contact may move while still developing excessive resistance under load. Test each channel with a suitable load and record the results individually.

Check the enable circuit when an output stays off. The program bit may be active while the F+/F− condition is missing. Photograph the existing arrangement and compare it with the drawing before changing jumpers.

A sound fuse does not prove a sound contact. An overload can damage or weld a relay contact. Measure a channel that remains on, and investigate beyond simply replacing its fuse.

Take a moment to review a 4UA13 replacement. Siemens lists it as the successor, but its switching is electronic. Compare the load, protection and supply arrangements together before putting the replacement into service.

OtomasyonAVM resources and PDFs

+ Shared SIMATIC S5 manuals and PDF archive

+ S5 digital output modules and model pages

Related topics

+ 498-1AB11 RC contact-protection submodule

+ Understanding relays and contacts

+ 42-pin screw-terminal front connector

Browse SIMATIC S5

+ Back to S5 digital output modules

+ SIMATIC S5 system pages

+ Siemens S5 PLC main page

+ Used Siemens products and models

Siemens and external references

+ Siemens S5-135U/155U, section 8.4.17 – 458-4UA12 specifications and wiring, 8-64–8-66 (English)

+ Siemens DA 458, A5E00066617-01, 04/2000 – 4UA12/4UA13 differences (German/English)

+ Siemens ST 50, 1998 – RC submodule, front connectors and mechanical data, 4/40–4/41 (English)