Siemens 6ES5 436-4UB12 – 8-Channel 115/230 V AC Digital Input Module
6ES5 436-4UB12 is an 8-channel, 115–230 V AC digital input module in the Siemens SIMATIC S5 family. This S5 input module has eight individually isolated input circuits. Each channel has its own L/N terminal pair, giving it a different connection arrangement from modules with a shared input reference.
The model is documented in the SIMATIC S5 S5-135U/155U system manual. It transfers the status of AC control circuits, contactor auxiliary contacts and relay contacts to the PLC. Match the S5 system architecture, rack and front connector against the complete order number. Older U Periphery documentation also describes this voltage class as 115–240 V AC.
Input voltage and signal thresholds
Rated input voltage is 115–230 V AC at 47–63 Hz. The specified ranges are 0–60 V AC for logic 0 and 90–264 V AC for logic 1. The 60–90 V AC region must not be used as a defined logic state. This module is not intended for 24 V DC PNP/NPN sensor signals.
Typical input current is 15 mA at 115 V AC and 25 mA at 230 V AC; typical input resistance is 10 kΩ. The manufacturer permits connection of 2-wire BERO proximity switches; check the sensor's AC voltage rating and off-state leakage separately. For signals switched through a relay contact, measure directly across the relevant input pair.
Input frequency and delays
Maximum input frequency as a pulse train is 20 Hz. Positive-going delay is typically 5 ms, with a 2–15 ms range. Negative-going delay is typically 20 ms, with a 10–25 ms range. Consider CPU scan time alongside module delay when assessing short pulses.
Under the permitted operating conditions, all eight inputs may be active simultaneously (100% coincidence factor). The digital section draws typically 80 mA from the 5 V system bus. In power supply and PLC supply calculations, assess this separately from AC field-input current.
Isolation, wiring and cable length
The isolation arrangement is 8 × 1 channel. When checking S5 connection parts and the front connector, follow each input's own L/N pair. Any shared-neutral arrangement must follow the machine diagram; external common connections affect the independence of the input circuits.
The manufacturer's cable limits are 600 m unshielded and 1000 m shielded. Assess cable routing, electromagnetic interference, earthing and field-circuit fuse protection together. The manual's CE notes require a SIFI C or equivalent filter in the 230 V AC field supply for this model.
Enable circuit and addressing
The F+/F− enable circuit is completed by a jumper in the front connector. This circuit is separate from the AC field inputs. If all inputs fail to read, check front-connector seating, the enable arrangement and the module address setting.
The eight inputs occupy one input byte. Match the addressing switch to the CPU project and PLC program. For example, byte address 32 (20h) gives inputs I32.0–I32.7; German notation uses E. During troubleshooting, compare field voltage, channel LED and the input state in the program.
Mechanical data and related modules
Dimensions are 40 × 255 × 195 mm (W × H × D), with an approximate weight of 0.5 kg. Allow for the 40 mm width when selecting an S5 rack and rack/slot arrangement.
6ES5 436-4UA11 and 6ES5 436-4UA12 are 16-input AC models. 6ES5 435-4UA12 accepts 24–60 V AC, while 6ES5 431-4UA12 accepts 24–60 V DC. Verify input count, voltage type, isolation and wiring before selecting a replacement.
On used Siemens equipment, inspect the label, front connector, insulation areas and signs of overheating. Check all eight channels in both on and off states using a suitable AC test arrangement.
Editor’s note
Start by confirming the UB12 order code and eight-input arrangement. A similar-looking UA12 can lead to an easy mistake. A clear label photograph and connector comparison take less effort than sorting out the wrong spare.
If one input does not respond, measure across that channel's own L/N pair. Using another channel's neutral can send the diagnosis in the wrong direction. Keep the machine diagram beside you and work from it.
If an input remains active with the contact open, give the board a fair check first. Inspect 2-wire sensor leakage, the cable and the actual input voltage. On long cable runs, assess any measured voltage against the input thresholds.
For fast pulses, remember the 20 Hz limit and negative-going delay. A visibly flashing LED does not prove that every pulse reaches the program. Check pulse duration together with CPU scan time.
With a used board, check every channel rather than stopping after a few LEDs light up. Have 230 V AC testing performed by qualified personnel with a suitably protected setup. Isolate field and rack power before removal, and photograph the wiring and address setting; those records make fitting the spare easier.
OtomasyonAVM resources and PDFs
Start with the OtomasyonAVM Siemens S5 PDF archive, About Siemens S5 and S5 digital input modules.
Specifications appear in Siemens S5-135U/155U System Manual, C79000-G8576-C199-07, section 8.4.8. PDF pages 360–361, printed pages 8-46 and 8-47, contain the technical table and connection diagram. The filter requirement appears on printed page 1-5.
Related topics
+ 6ES5 436-4UA11 · 6ES5 436-4UA12 · 6ES5 435-4UA12 · 6ES5 431-4UA12.
+ PLC troubleshooting · Electromagnetic interference · Connectors.
Browse SIMATIC S5
Siemens S5 home · S5 digital input modules · S5 PDF archive · Used Siemens equipment
Siemens and external references
+ Siemens S5-135U/155U system manual – English PDF: 6ES5 436-4UB12 specifications, connection diagram, addressing and CE installation notes.