6ES5 422-8MA11
Siemens 6ES5 422-8MA11 – 16-Channel 24 V DC Digital Input Module
Siemens 6ES5 422-8MA11 is a 16-channel, 24 V DC, non-isolated digital input module for SIMATIC S5 PLC systems. It is used with S5-90U, S5-95U and S5-100U controllers and ET 100U/ET 200U distributed I/O applications. Within the S5 digital input module range, it provides two groups of eight input bits. Typical input delays are 4 ms for OFF-to-ON and 3 ms for ON-to-OFF.
The module reads switching signals from devices such as inductive sensors, photoelectric sensors and limit switches. Each channel reports a binary OFF or ON state; having sixteen inputs does not make it an analog measuring module. Selection must account for the common reference, front connector and slot addressing, as well as the number of signals required.
Input levels, sensor interface and supply
The nominal input voltage is 24 V DC. Siemens specifies 13–30 V for logic 1 and 0–5 V for logic 0; the region between these ranges must not be treated as a defined logic state. The inputs require a positive switching signal, so the difference between PNP and NPN outputs matters. An NPN output is not a direct equivalent. Establish the correct M reference between the sensors and power supply; the module is not galvanically isolated from the CPU side.
Typical input current at logic 1 is 4.5 mA. Two-wire BERO proximity switches may be connected, provided their OFF-state residual current does not exceed 1.5 mA. The difference between analog and digital inputs is essential here: connecting a 0–10 V or 4–20 mA measurement signal will not produce an analog process value.
Consider the input delay together with the PLC scan time. The 4 ms turn-on and 3 ms turn-off delays are typical values; they do not establish a guaranteed minimum pulse width or a high-speed counting rate. Siemens specifies 100 m for unshielded input wiring. Cable routing and the actual electromagnetic environment still need to be assessed.
Front connector and terminal assignment
Field signals connect through the module’s front connector. The S5-100U manual lists 6ES5 490-8MA13 for crimp connections and 6ES5 490-8MA03 where contacts are supplied separately. Check whether the connector and required contacts are included with a replacement module; the electronic module alone may not complete the installation.
The screw-terminal option is 6ES5 490-8MB11. Earlier S5-90U/95U and ET 100U documentation also lists 6ES5 490-8MA12. Check the actual connector version, mechanical condition and wiring before replacement. The circuit diagram assigns terminal 1 to L+ and terminal 20 to M; terminals 12–19 to n.0–n.7 and terminals 2–9 to (n+1).0–(n+1).7. Terminals 10 and 11 are not connected (NC).
The backplane connection and front field connector are separate inspection points. Check the installed bus unit, including types such as the 6ES5 700-8MA11 screw-terminal bus unit or 6ES5 700-8MA21 crimp-terminal bus unit. Wire the sixteen field signals according to the 422 module’s front-connector diagram, rather than assuming that the standard bus-unit field terminals provide its sixteen inputs.
Slot addressing: check both input bytes
Among the compact S5 modules, this version uses a different addressing arrangement from ordinary four- or eight-channel digital input cards. In an S5-95U/S5-100U installation, use slots 0–7 and the address area associated with analog modules. The input states occupy the first two bytes, n and n+1. An S5-90U has a smaller expansion limit, so the 0–7 rule must not be applied unchanged to that CPU. The signals themselves remain digital.
Address examples: slot 0 → 64.0–64.7 and 65.0–65.7; slot 1 → 72.0–72.7 and 73.0–73.7; slot 2 → 80.0–80.7 and 81.0–81.7. The S5-90U/95U manual explicitly shows a 6ES5 422-8MA11 in slot 1 with a sensor on terminal 13 at address 72.1. STEP 5 may display input operands with I or E, depending on the mnemonic language. For ET 100U/ET 200U, establish the addresses from the distributed station configuration.
Fault indication and related input modules
The red F LED indicates an interruption of L+ or M; this indication alone does not prove that the module has failed. Smaller input counts are available with the 6ES5 420-8MA11 four-input module and 6ES5 421-8MA12 eight-input module. These are comparison options, rather than replacements that preserve the 422 module’s channel count and addressing.
Siemens lists typical consumption of 50 mA from the CPU’s +9 V supply, approximately 4.5 W power loss and approximately 190 g weight. When sourcing a used digital input module, check the complete order number, label photograph, connector and individual channel test results. The Siemens S5 PLC overview provides additional system context.
Editor’s note
Start with a clear label photograph. On this module, the sixteen inputs, connector and addressing arrangement belong together. A description that only says “S5 input card” is not enough, and a working module with no suitable connector may still leave the job unfinished.
Do not condemn the card just because F is on. Measure between L+ on terminal 1 and M on terminal 20, then inspect the connector and common return. Replacing the module before correcting a broken supply connection can leave you with exactly the same fault.
Test both groups of eight. A quick check of the first eight inputs does not establish that all sixteen work. Keep terminals 12–19 separate from terminals 2–9 in your notes, and confirm that every test signal reaches the expected program bit.
If an OFF sensor still appears ON, pause and measure. Residual current from a two-wire sensor or an incorrect M reference can mislead you even when the module is sound. Compare the result using a suitable 24 V test signal on the same channel.
Treat a slot change as an address change. Save the program and photograph the original arrangement before moving the card. Establish test conditions that prevent machine movement. For a used unit, request its working or faulty status and the results of testing all sixteen inputs.
OtomasyonAVM resources and PDFs
+ S5 manuals and PDF files — shared archive
Related topics
+ PNP and NPN sensor comparison
+ Analog inputs and digital inputs
+ 490-8MB11 screw-terminal front connector
Browse SIMATIC S5
+ Siemens second-hand main page
Siemens and external references
+ Siemens S5-100U System Manual — English; 6ES5 422-8MA11 circuit and specifications, section 14-18
+ Siemens S5-90U/S5-95U System Manual — English; addressing on 6-6, module data on 15-15
+ Siemens ET 100U Manual — English; module range and distributed station application