6ES5 421-8MA12
Siemens 6ES5 421-8MA12 – 8-Channel, 24 V DC Digital Input Module
6ES5 421-8MA12 is a non-isolated digital input module providing eight 24 V DC inputs in the SIMATIC S5 range. Siemens lists it for S5-90U, S5-95U, S5-100U, ET 100U and ET 200U. Logic 0 is 0–5 V and logic 1 is 13–33 V; typical input current at 24 V is 7 mA per channel.
The module reads suitably connected inductive sensors, photoelectric sensors and limit switches. It passes binary signals such as part detected, position reached or contact closed to the program. The inputs share the M reference; the eight channels are not individually isolated.
Signal levels and sensor selection
Check the PNP/NPN output arrangement before wiring. The Siemens diagram shows positive voltage switched onto the input. A relay contact test switches L+ to the selected input and requires the correct M return. Do not treat the region between 5 V and 13 V as a defined logic state.
Two-wire BERO proximity switches are supported, with a specified residual-current limit of 1.5 mA. When selecting a sensor, check its off-state leakage as well as its 24 V rating. Excessive leakage can complicate assessment of the input’s turn-off behaviour.
Terminal assignment, power and the F indicator
In the S5 wiring diagram, terminal 1 is L+ and terminal 2 is M. Channel terminals are not in numerical order: .0 → 4, .1 → 3, .2 → 6, .3 → 5, followed by .4 → 8, .5 → 7, .6 → 10, .7 → 9. Trace each cable from its sensor connector using this assignment.
Typical consumption from the internal +9 V system supply is 34 mA; this is not a 9 V field-input rating. Check the S5 power supply separately from the 24 V field connection. The red F LED indicates missing L+/M input voltage. Typical module power loss is 1.6 W and approximate weight is 190 g.
S5-100U addressing and distributed stations
On an S5-100U, the digital module’s byte address follows its slot number. The eight channels occupy bits .0–.7 of one input byte. For example, in slot 3, terminal 4 corresponds to I3.0 and terminal 3 to I3.1. During PLC programming, compare the monitored address with the physical channel marking. Review the addressing rules when changing PLC families.
The ET 200U DP Standard table identifies this module as 8DI / 016 with a one-byte address scope. 016 is a module identification value, not its CPU input address. Obtain the distributed station’s start address from its configuration and use the relevant CPU manual for S5-90U/95U addressing.
Delay times, operating conditions and nearby models
The S5-100U and S5-90U/95U manuals specify typical delays of 2.3 ms for 0→1 and 3.5 ms for 1→0. The older ET 100U manual gives 4.5 ms for 1→0, while the ET 200U table lists 2.3–4.5 ms. Use the documentation applicable to the installed system when assessing short pulses; CPU scan and communication time also contribute to response time.
The S5-100U specification page permits up to 100 m of unshielded cable and ambient temperatures of 0–60 °C for horizontal installation or 0–40 °C for vertical installation. Consider cable routing, cabinet temperature and the common M connection together.
6ES5 420-8MA11 provides four inputs; 6ES5 422-8MA11 provides 16 inputs. 6ES5 431-8MA11 has eight 24 V DC inputs with galvanic isolation. Check channel count, isolation, terminals and address allocation before considering a replacement.
Editor’s note
Start with the complete label. Listings for 6ES5 421-8MA11 may appear alongside this 8MA12 revision, but a similar front panel is not enough to select a spare. Photograph the full order number, installed slot and cable labels before removal. That small preparation makes replacement much easier.
The terminal order deserves a careful second look: channel .0 is on terminal 4, not terminal 3. Operate the field sensors individually and record both the changing LED and the corresponding program bit. This helps distinguish crossed wiring from a defective input.
If the red F indicator is on, check the supply before replacing the board. Measure L+/M between terminals 1 and 2, then inspect loose terminals, a broken M return and the field supply. A serviceable module cannot provide reliable input information when its supply connection is missing.
If the input LED changes but the machine does not respond, begin PLC troubleshooting at the correct address. Check the slot-derived address on an S5-100U or the configuration of a distributed station. Review program conditions and address allocation before working on the electronics.
When checking a used module, exercise all eight inputs in both directions. Confirm that the CPU bit clears when the signal is removed, as well as setting when it is applied. Prevent machine movement during the test. Inspect the base and connections for oxidation or looseness too; another board will not repair a poor connection.
OtomasyonAVM resources and PDFs
See About Siemens S5 PLC and the S5-90U system pages for the relevant system group.
+ OtomasyonAVM S5-90U PDF archive · Shared PDF and manual archive for other S5 systems. The manufacturer references below are in English.
Related topics
+ 6ES5 421-8MA11: a different eight-input revision; compare the exact suffix and wiring.
+ 6ES5 420-8MA11: four-input, 24 V DC module.
+ 6ES5 422-8MA11: 16-input, 24 V DC module with different wiring and address requirements.
+ 6ES5 431-8MA11: eight-input, 24 V DC isolated module.