6ES5 700-8FA11
Siemens 6ES5 700-8FA11 – SIMATIC S5 Screw-Terminal Bus Unit
The Siemens 6ES5 700-8FA11 is a two-slot bus unit with SIGUT screw terminals and enhanced EMC immunity for SIMATIC S5 I/O modules. Field wiring connects to the base terminals. A flat ribbon cable connects adjacent bus units.
Technical specifications
Appendix A.1.4 of the Siemens S5-95F manual lists 10 terminals per slot, a weight of about 300 g, and dimensions of 91.5 × 168 × 39 mm (W × H × D). Typical current draw from the internal +9 V bus is 1 mA. Each terminal takes up to two conductors. The specified cross-section per conductor is 0.5–1.5 mm² for stranded wire with ferrules and 0.5–2.5 mm² for solid wire. Section 5.4 specifies 10 mm DIN 46228 ferrules for stranded conductors.
Compatibility and variant selection
The Siemens data sheet lists S5-90U, S5-95U/F, S5-100U, ET 100U and ET 200U. External I/O on the S5-90U connects through IM 90. Check the installed slot layout against the applicable manual for the S5-95U, S5-100U CPU 100 or CPU 103. On a remote station, also record the exact head module, such as the ET 100U IM 318-8 or ET 200U IM 318-B.
The 8MA11 is the standard screw-terminal version, the 8MA21 is the standard crimp version, and the 8MA22 is the enhanced-EMC crimp version. Catalogue ST 50 lists the 8MB11 (screw) and 8MB21 (crimp) as interrupt-capable versions. When a CPU 103 uses OB2 for process interrupts, check the required position of the interrupt-capable base in the CPU manual.
For an S5-95F safety circuit with a 431-8FA11 digital input, 450-8FA11 digital output or 464-8MG11 analog input, check the bus unit code, any IM 316F interface and the wiring against the Siemens drawing for that station.
Installation and fault checks
Record the position of each module before removal, including I/O such as the 431-8MA11 digital input, 451-8MA11 digital output or 464-8MB11 analog input. If two adjacent slots or the modules to their right become inaccessible together, isolate power and inspect the ribbon cable at that base and the preceding connection. Also check the tier interface connection, such as IM 315 in a two-tier layout or IM 316 with multiple expansion tiers.
When buying used, check the label, both terminal groups, the rail latch and the ribbon cable on the same unit. To offer a bus unit for sale, send its full part number and photos to otomasyonavm@gmail.com.
Editor’s note
Isolate power. Photograph both slot numbers and the terminal order before removing the base.
Read 8FA11 on the label. Check that both terminal groups are complete and that the screws clamp the conductors.
Look for crushing or cracks where the ribbon cable bends into the housing. Check the plug guide and rail latch for damage.
After fitting the base, compare the mechanical coding and module order with your photos. Seat each module and ribbon plug without force.
During commissioning, check both slots and the next bus unit separately. On S5-95F, carry out the site’s safety function test before returning the circuit to service.
PDFs and Siemens references
- Siemens 6ES5700-8FA11 data sheet (DE)
- S5-95F manual (EN), technical data for the exact part on p. A-11
- Siemens ST 50 (EN), bus unit variants and ordering data on p. 2/75
- S5-90U/95U manual (EN), IM 90 and external I/O on pp. 3-5–3-6
- S5-100U manual (EN), CPU 103 process interrupts on p. 10-1