6ES5 263-8MA13
Siemens 6ES5 263-8MA13 IP 263 positioning module
The 6ES5 263-8MA13 is the IP 263 module for positioning two independent axes in a SIMATIC S5 system. It is one of the S5 positioning modules designed for rapid traverse and creep speed. Once the target is set, the axis travels quickly, slows at the changeover point and reports to the PLC when it reaches the target range.
Encoder signals, supply and control
The encoder inputs accept 5 V differential RS-422, 24 V single-ended incremental signals or an absolute SSI encoder. When selecting an incremental encoder or an absolute encoder, check the signal type and supply voltage separately. For a 5 V RS-422 incremental signal, Siemens specifies up to 200 kHz with shielded cable up to 32 m at a 5 V encoder supply or up to 100 m at a 24 V encoder supply.
The module runs on 24 V DC. For power supply sizing, the typical current is 120 mA excluding the output and encoder loads. Choose the appropriate 703-series lead when selecting cables and connectors. The reference cam is read through a digital input. Rapid traverse, creep speed and direction commands use digital outputs. Siemens specifies a maximum output current of 500 mA.
PLC compatibility, installation and addressing
Siemens documents the S5-90U, S5-95U and S5-100U applications. The exact order entry in the Russian edition of ST 50 also lists ET 100U and ET 200U. The module occupies two mounting positions. With a bus unit such as the 6ES5 700-8MA11, check the installed arrangement and terminal wiring. On the S5-100U, the IP 263 is addressed like a four-channel analogue module. For remote I/O, use the address table for the installed station.
Before buying a spare, compare the label suffix, STEP 5 block and wiring with the 263-8MA11 and 263-8MA12 variants. The IP 265 is for high-speed counting, the IP 266 for closed-loop positioning and the IP 267 for stepper motor control.
Editor’s note
+ Before buying, ask for photos of the 8MA13 label and both ENCODER connectors. Check separately whether encoder cables are included.
+ Back up the STEP 5 program and axis data blocks before removal. Record each axis address, resolution, reference input and rapid-to-creep changeover value.
+ After safely isolating power, inspect the encoder plugs, shield connections and bus contacts. Label the two encoder plugs separately before moving them.
+ If an axis position stays fixed, verify that you are monitoring the correct channel. Then check encoder power and signal type. For SSI, compare the clock and data wiring with the original drawing.
+ If the axis overshoots its target, check the rapid-to-creep changeover and cutoff differences before replacing the module. Check whether the reference position is repeatable.
+ With actuator power circuits isolated, verify the actual position and reference input for each channel in STEP 5. Run the motion test at low speed under the site commissioning procedure.
For a used module, ask for separate test results for both encoder channels. To offer a module for sale, send photos of the label and connectors to otomasyonavm@gmail.com.
PDFs and Siemens references
+ S5-90U / S5-95U system manual, IP 263 section (EN)
+ S5-100U system manual, pp. 15-45–15-48 (EN)
+ Siemens ST 50, IP 263 technical and ordering data, pp. 2/51–2/52 (EN)
+ Siemens ST 50, ET 100U and ET 200U order entry (RU)