6ES5 752-0AA42

Siemens 6ES5 752-0AA42 – RS422-A/RS485 Interface Submodule

6ES5 752-0AA42 is a plug-in submodule providing an RS422-A/RS485 serial interface for the CP 524 and CPU 928B in Siemens SIMATIC S5 systems. Within the S5 interface module range, it connects differential data lines through a 15-pin female D-sub connector. The specified CPU-interface limit is 19,200 bit/s, with a maximum cable length of 1,200 m under suitable installation conditions.

On CP 524 models such as 6ES5 524-3UA13 and 6ES5 524-3UA15, the installed submodule determines the electrical serial interface. For a CPU 928B application, match the interface type, CPU settings and partner device’s electrical standard.

RS422 and RS485 operating modes

RS422-A full-duplex operation uses separate transmit and receive pairs. In RS485 half-duplex operation, the R line alternates between transmitting and receiving. A Modbus/RS485 application also requires suitable driver software and parameters; installing the submodule is only one part of the setup.

Essential 15-pin connector assignments

Receive: R(A) on pin 4 and R(B) on pin 11. Transmit: T(A) on pin 2 and T(B) on pin 9. Signal GND: pin 8. Shield: pin 1. For full duplex, connect each device’s transmit pair to the other device’s receive pair. Half-duplex wiring must agree with the relevant submodule jumper setting.

The interface signals are galvanically isolated from the supply. When reviewing grounding, avoid arbitrary connections between shield and signal GND: the COM 525 manual explains that this can defeat isolation. Check the differences between RS232, RS422 and RS485 and the partner device’s A/B definitions before making a cable.

Protocol, baud rate and driver selection

In industrial communication, the electrical interface, character format and protocol are separate settings. Match the communication port’s baud rate, data bits, parity and stop bits to the partner. CP 524 half-duplex operation requires a suitable special driver; standard 3964/3964R procedures cannot be used in that mode.

For CP 524 applications, COM 525 and the loaded driver define the communication processor’s behavior. CPU 928B applications use the corresponding CPU communication settings. Preserve the existing S5 system’s cable details, program and parameters before treating an interface replacement as the complete solution.

Supply and operating conditions

The host CP/CPU supplies the submodule. The system manual specifies 0.5 A maximum from the 5 V rail, an operating temperature of 0 to +55 °C and IP00 protection for the RS422-A/485 submodule. Follow the cooling requirements of the installed host module and rack.

Important difference between 0AA42 and 0AA43

6ES5 752-0AA43 is a lower-power development of the 0AA42. Siemens’ driver notes state that jumper locations and settings changed. Do not copy jumper numbers from a 0AA43 drawing directly onto a 0AA42.

6ES5 752-0AA12 provides a 20 mA TTY interface, while 6ES5 752-0AA22 provides V.24/RS232. Their shared 752 family designation does not make them direct substitutes on an RS422/RS485 link.

The 6ES5 752-0AA53 PG submodule also serves a different interface function. When selecting a used interface module, check the complete code, connector, host CPU/CP and required electrical standard together.

Used-module inspection and communication testing

Testing a used communication module should cover transmission and reception, with the duplex mode recorded. If a communication converter is part of the test setup, verify its line direction, termination and parameters too; the 752 submodule may not be the source of the fault.

Editor’s note

Start with the last two digits. If the board is a 0AA42, use its own jumper arrangement. A drawing for the 0AA43 may look familiar while still leading to the wrong setting.

A connector that fits still needs checking. Open the 15-pin plug and verify continuity pin by pin. Pay particular attention to the receive pair on 4/11 and the transmit pair on 2/9.

Check the settings before condemning the board. Compare baud rate, parity and stop bits at both ends. In RS485 mode, also confirm that the driver controls transmit/receive direction correctly.

Keep shield and signal GND distinct. Adding an improvised link to cure interference can defeat the interface isolation. Record the existing arrangement, then follow the manual’s wiring scheme.

One successful telegram is a useful start. Continue with repeated exchanges in both directions and watch replies and error counters. Confirming that the link remains stable after warm-up gives a much better basis for assessing a used module.

OtomasyonAVM resources and PDFs

+ SIMATIC S5 interface submodules

+ SIMATIC S5 communication processors

+ Shared S5 PDF archive – manuals and files page

Related topics

+ Understanding RS422 connections

+ Modbus and RS485 communication

+ Comparing RS232, RS422 and RS485

Browse SIMATIC S5

+ Back to S5 interface modules

+ SIMATIC S5 system pages

+ Siemens S5 PLC main page

+ Used Siemens products and model pages

Siemens and external references

+ Siemens S5-135U/155U, C79000-G8576-C199-07 – interface specifications, 5-122; exact order code A-4 (English)

+ Siemens COM 525, 6ES5 998-1DB11, Volume 1 – CP 524 RS422-A/485 operation and wiring (German)

+ Siemens S5R007, 6ES5 897-2QA21 – 0AA42 RS485 operation and 0AA43 jumper changes (English)