6ES5 306-7LA11
Siemens 6ES5 306-7LA11 — IM 306 Centralized Expansion Interface
The Siemens 6ES5 306-7LA11 is an IM 306 interface module for centralized expansion of the S5-115U within the SIMATIC S5 family. The arrangement supports up to three expansion racks, with a maximum total cable length of 2.5 metres from the central controller to the last rack. Among S5 interface modules, its key feature is variable slot addressing using DIP switches.
It connects the backplane of the central Siemens S5 PLC to ER 701-1 expansion racks. Record full rack labels, such as 6ES5 701-1LA11 or 6ES5 701-1LA12, together with the installed module positions and cable sequence.
Connection and addressing compared with the IM 305
A separate IM 306 is installed in the central controller and each expansion rack. The IM 305 arrangement supports one expansion unit with fixed slot addressing: the 6ES5 305-7LA11 has a 0.5 m fixed cable, while the 6ES5 305-7LB11 has a 1.5 m fixed cable. The IM 306 uses separate 705 cables and provides variable slot addressing.
705 cables and total cable length
The relevant S5 cables and connectors include the 705-0AF00: 0.5 m, 705-0BB20: 1.25 m, 705-0BB50: 1.5 m and 705-0BC50: 2.5 m. Add all cable segments in the S5-115U chain when checking the 2.5 m limit; that allowance does not apply separately to every rack-to-rack connection.
Setting slot addresses with DIP switches
An addressing panel beneath the right-hand cover provides switches for each slot. Check starting addresses for digital inputs, digital outputs and analog modules against the module type and occupied address range. A replacement IM 306 does not automatically have the correct settings for the machine.
Photograph the addressing panel before replacement and compare its settings with the I/O addresses in the PLC program. Digital slots also have a 16/32-input-or-output selection, so copying the starting address alone is insufficient.
Supply current and connections to other S5 systems
The module’s own current consumption from the 5 V supply is 50 mA. The maximum current supplied through the expansion connection is 2 A; this is not a separate 2 A allowance for every rack. Calculate the combined module demand and place the expansion unit with the greatest current demand closest to the central controller.
Siemens also lists the IM 300-5LB11 in a suitable S5-135U/155U central controller as a partner for an IM 306 in an ER 701-1. Check cable, supply and access conditions in the relevant central-controller instructions. Do not transfer the S5-115U cable-length limit to every S5 configuration.
Editor’s note
Before replacing this board, take a good look beneath its side cover. A clear photograph of the original settings saves trying to reconstruct them later. A small address mismatch can make a sound replacement appear faulty.
Measure the connecting cables and write down their total length, including any extra length added during cabinet alterations. Check connector fastening, shield contact and grounding connections as well. These checks give you a useful starting point.
Take a moment over the supply calculation too. The IM 306’s own consumption and the current it carries to the expansion units are different quantities. A machine that has gained extra modules may have outgrown its original power calculation.
When an expansion unit disappears, begin troubleshooting by recording which racks still work. Then inspect the cable transition, supply and address settings in turn. Changing one thing at a time makes the result much easier to understand.
When buying a used Siemens IM 306, ask for close-up photographs of the address panel and connectors as well as the label. Where possible, arrange an I/O-access test in a suitable rack with known cables and modules. Understanding the board before buying makes the decision easier.
OtomasyonAVM resources and PDFs
+ OtomasyonAVM S5 PDF archive. See the S5-115U manufacturer manual below for IM 306 centralized connections and address settings.
Related topics
+ 305-7LA11 · 305-7LB11 · 300-5LB11 · ER 701-1 rack · 705-0AF00 cable · PLC troubleshooting.
Browse SIMATIC S5
+ S5 interface modules · S5 cables · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand main page.