Siemens 6ES5 948-3UR21 is the CPU 948R-2 central processing unit for S5-155H in the SIMATIC S5 family. It provides 1664 KB of internal user RAM and executes STEP 5 programs. When selecting a processor for an S5 system, match the complete order number, hardware version and installed redundancy configuration.
For this revision, the Siemens hardware table specifies a 5 V DC ±5% supply and typical consumption of 3.6 A. Check the supply through the S5-155H power-supply and central-rack arrangement. Measure under load and investigate power, backplane and contact problems before attributing a fault to the CPU.
Internal RAM and memory-card functions
1664 KB is the CPU’s internal user RAM capacity. The Siemens programming guide identifies 3UR21 as CPU 948R-2 and the 640 KB 3UR11 as CPU 948R-1. Treat the SIMATIC memory card separately as a program-storage and loading medium. For cards such as 6ES5 374-2KH21, check capacity against the actual project size.
The documented Flash EPROM card contents are copied into internal RAM following an overall reset. Check the card version separately from the backup read from RAM. A machine’s current program and an older archive card should not be assumed identical.
Distinguishing 948 and 948R references
Do not automatically treat 6ES5 948-3UA21, 6ES5 948-3UR13, 6ES5 948-3UR22 or 6ES5 948-3UR23 as interchangeable with 3UR21. Record the full reference and version label, then establish replacement suitability from the applicable system documentation.
Moving from a system using CPU 946R or CPU 947R to CPU 948R requires more assessment than physical insertion. Review the program, system software, redundancy parameters and installed hardware for the proposed change.
Installation and programmer connection
The manual specifies a 40 mm frontplate and two rack slots. Switch off power before insertion or removal. SI1 is the 15-pin programmer port; the SI2 receptacle is not used in S5-155H operation. Match the programmer cable and connection type to the documented pin assignment rather than connector appearance alone.
PG access over SINEC H1 requires a suitable communications processor and configuration. The Siemens CP 1430 TF documentation lists 3UR21, version 01 onwards, among CPUs supporting PG communication over the backplane path. Verify the installed CP, programmer software and project settings together.
Redundancy and peripheral equipment
Record expansion components such as IM 314R and the installed interface modules against the system drawing. Investigate differences in hardware, wiring and configuration between the two sides, and establish the system’s operating condition before replacing a CPU.
Trace digital inputs, digital outputs and analog modules through the project’s addressing and redundancy configuration. A CPU indication does not by itself identify every peripheral as faulty. Read the diagnostic record before examining the relevant module and its connections.
Editor’s Note
Obtain a clear photograph of the complete order number and version label. With used Siemens CPUs, a “948R” description alone is insufficient; compare the actual assembly with the installed system’s requirements.
Back up RAM first, then inspect the memory-card contents. Do not use overall reset as a casual test. Recent machine changes may exist only in RAM, while the card holds an older program.
During redundant cyclic operation, steady RUN can indicate the master and flashing RUN the standby. Assess STOP, SYS FAULT and the system state together before diagnosing a fault from one LED.
A weak supply can make a healthy CPU appear faulty. Check supply voltage, connections and seating. Do not separate the coupled boards or change jumpers speculatively.
In Siemens S5 maintenance, powering up and seeing LEDs is only a limited check. Ask what was actually tested for rack operation, program loading, diagnostics and redundancy behaviour; distinguish completed checks from assumptions.
OtomasyonAVM resources and PDFs
Start with the 6ES5 948-3UR21 product page, S5 memory cards and the SIMATIC S5 overview. Use the OtomasyonAVM S5 PDF archive to locate relevant documents. The English S5-155H Volume 1 covers hardware and diagnostics; the CPU 948R Programming Guide, Volume 2 covers programming and memory organization. Consult printed pages I/3-2–I/3-10 in the hardware manual.
Related topics
+ CPU 948, 3UA21 · CPU 948R, 3UR22 · CPU 948R, 3UR23 · CPU 946R · CPU 947R
Browse SIMATIC S5
+ SIMATIC S5 · Siemens S5 PLC · S5 racks · Used Siemens overview
Siemens and external references
Siemens S5-155H Manual, Volume 1 — C79000-G8576-C197, Edition 06, English · Siemens CPU 948R Programming Guide, Volume 2 — C79000-G8576-C136, Edition 05, English · Siemens CP 1430 TF / NCM COM 1430 TF, Volume 1 — C79000-G8976-C056, Release 01, English