6ES5 947-3UR11

Siemens 6ES5 947-3UR11 CPU 947R — S5-155H Processor Module

Siemens 6ES5 947-3UR11 is the CPU 947R module used in the CPU 946R/947R processor assembly of an S5-155H system. Within the SIMATIC S5 range, it must be considered together with its CPU 946R partner. A single 947R module is not a complete, independently operating S5 CPU; record the other processor module when selecting a spare.

The 3UR11 suffix matters. Similar codes such as 6ES5 947-3UA11 and 6ES5 947-3UR21 do not establish direct interchangeability. Check the complete code and hardware version of the installed CPU 946R as well; do not select another revision such as 946-3UR21 solely by its family name.

Its role in the redundant S5-155H system

Siemens describes two central controllers, each containing a CPU 946R/947R assembly, operating as master and standby. Their parallel connection uses IM 304 and IM 324R equipment. Inspection should therefore cover the individual module, both central-controller configurations and their interconnections.

Before removal, photograph the rack arrangement, module codes, cables and indicator states. Check the S5 power supply against the system maintenance instructions. Operation on one side alone does not establish the condition of the redundant system; review the second controller and system diagnostic records too.

Interpreting the memory specification

Siemens’ processor comparison lists 128 Kbytes of fixed RAM for the CPU 946R/947R family, expandable to a total of 896 Kbytes using 355 memory modules. This describes the processor assembly’s memory arrangement, not 896 Kbytes fitted to a single 947R module. Make a physical inventory of the installed S5 memory equipment.

For cartridges such as 373-0AA41, 373-0AA61 and 373-0AA81, record the complete code, host memory module and known contents together. Do not transfer CPU 948R Flash Memory Card information to this assembly. Back up the PLC program and accessible parameters before replacement; memory capacity alone does not identify the correct program.

Programming access and the UR11–UR21 distinction

Select the programming interface and connection cable against the installed CPU documentation. For the PG–SINEC H1–CP–backplane–CPU route, the CP 1430 TF manual lists CPU 947R support from 6ES5 947-3UR21, version 6. Do not assume that this particular access route is supported by a 947-3UR11.

This requirement is not a blanket incompatibility statement about every CP communication function. Record the intended PG access path, CP code, software version and CPU revision separately. If access fails, distinguish cable faults, access settings and hardware support in successive checks.

Used-equipment acceptance and system testing

Record startup, program access and diagnostic states using a known working, suitable processor assembly. When checking digital inputs and digital outputs, compare the state observed in the PLC with field measurements. Plan any test that moves outputs within the machine maintenance procedure.

For an older Siemens S5 system, record both processor modules, memory equipment and connection hardware in the acceptance report. Keep the scope explicit, including supporting equipment. Visual inspection of one module, an operating test of the assembly and a redundancy switchover test provide different evidence.

Editor’s note

Start with a legible 947-3UR11 label and a photograph of the installed 946R partner. A generic “947 available” description leaves too much uncertainty when the spare reaches the machine.

The complete assembly matters here. Powering a single 947R does not demonstrate that the 946R/947R assembly or redundant system works correctly. Ask which modules and rack were used for testing, and have that scope recorded.

Record memory codes and positions before disturbing them. Do not erase or initialize equipment as an experiment while the only available program remains unprotected. Recovering an old machine program can cost far more than replacing the module.

If PG access fails, check the access path and cable before condemning the CPU. In particular, requirements documented for CP access to a UR21 should not be assumed to cover a UR11.

A used-item offer should identify whether it includes one module, the processor assembly or memory equipment. Record bent connector contacts, repair evidence and indicator states as well. Clear contents and test records make the handover easier for both parties.

OtomasyonAVM resources and PDFs

+ 6ES5 947-3UR11 product and information page, S5 CPU models and the Siemens S5 homepage.

+ OtomasyonAVM SIMATIC S5 PDF archive. The documents below separately cover the processor assembly, family-level memory comparison and requirements for the specific PG access route.

Related topics

+ CPU 946R revision review, 947-3UR21 comparison, S5 memory modules and IM 324R connection equipment.

Browse SIMATIC S5

Siemens S5 models  |  S5 CPU  |  S5 function modules  |  Siemens second-hand homepage

Siemens and external references

+ Siemens S5-155U CPU 946/947 Manual, 6ES5 998-0UM22, Release 07, English — central-controller section 1.2.2, printed page 1-6 / PDF page 72: S5-155H processor assembly and interconnection.

+ Siemens S5-155H CPU 948R Programming Guide, Volume 2/2, Edition 05, English — section 1.8, printed page 1-19 / PDF page 33: comparison with the CPU 946R/947R family’s memory arrangement.

+ Siemens CP 1430 TF with NCM COM 1430 TF, Volume 1/2, English — section 4.2.4, printed page 4-21 / PDF page 119: CPU code and version requirements for PG access through the backplane.