6ES5 943-7UA21
Siemens 6ES5 943-7UA21 CPU 943A — S5-115U, Two Programming Connections
Siemens 6ES5 943-7UA21 is a CPU 943A central processing unit for the S5-115U, with 16 KB of internal RAM and two serial programming connections. It executes the STEP 5 program in a SIMATIC S5 system and manages data exchange with the installed peripherals. Use the A-series documentation when assessing this S5 CPU.
943-7UA11 is the single-connection A-series option. 943-7UA22 is another revision requiring its own review. 943-7UB11 and 943-7UB21 are B-series codes; a shared “CPU 943” name does not establish equivalent memory, operating-system or interface functions.
Memory arrangement and program backup
On the CPU 943A, the memory submodule is distinct from internal RAM and forms part of the memory arrangement. Record its complete code, type and program contents. Do not transfer the Flash-card-to-RAM loading description for a CPU 945 to this model; select backup and recovery procedures from the applicable CPU documentation.
Changed data blocks in RAM may differ from the external memory image. Preserve the installed program and accessible operating data before removing power. Record the backup condition at the PS 951 power supply, the rack arrangement and any supporting equipment used for testing.
SI1 and SI2 have different operating scopes
Select the serial interface and PG cable for the appropriate TTY connection. Two sockets do not establish identical support for every PG operation. If a panel or communication connection uses the second port, record which device is connected to each port before testing.
Siemens’ A-series table permits program loading, overall reset and compression through SI2 from 943-7UA22, hardware revision 5 and PLC software Z06. Do not assume these functions are available through SI2 on a 943-7UA21. Plan program transfer around SI1 and the applicable PG instructions.
The same manual’s CPU 943 SI2 table does not provide an ASCII driver, 3964(R) connection or integrated clock. Check the source CPU before reusing another controller’s communication example or clock-reading program. Define the intended operation when assessing the second port.
Supply and CPU 943A family features
The CPU operates within the S5-115U backplane’s internal 5 V supply arrangement. Keep the power supply’s mains input rating separate from the CPU operating voltage. The CPU 943A family table lists 128 timers and 128 counters; review their use and retention settings in the installed program separately.
Used-equipment acceptance and application checks
When testing digital inputs and digital outputs, compare PLC states with field signals. A RUN indication alone does not demonstrate that all connections and machine functions work correctly. Record the program, memory submodule and port used alongside each test result.
Record addressing, data format and scaling for analog modules, and the FB versions used by function modules. Compare the original and replacement configurations before attributing a problem observed after replacement to a processor fault.
Acceptance testing on an older Siemens S5 system should include access to the installed application as well as startup. Keep separate records for SI1 and SI2. Successful reading through one port does not establish that every function of the other port has been checked. Distinguish connection faults from expected program behavior.
Editor’s note
Start with a legible 943-7UA21 marking and keep it distinct from UB21. Two connections on both units do not establish the same memory or operating-system features.
If reading succeeds through the second port but loading fails, check the documented SI2 limits before condemning the connector or CPU. Confirm the port and revision requirements first.
Back up the installed program before disturbing the battery, memory or CPU. Current data blocks deserve particular attention. Check whether the external memory actually contains the machine’s latest working version.
When one port works, assess the other using the same known working cable and device with an appropriate operation. A record saying “both ports tested” should identify what was done, rather than merely describe the connector condition.
A used-unit offer should identify included memory and cables, the test rack, label condition and repair evidence. Clear photographs and a useful test record reduce uncertainty when the spare reaches the machine.
OtomasyonAVM resources and PDFs
+ 6ES5 943-7UA21 product and information page, S5 CPU series pages and Siemens S5 models.
+ OtomasyonAVM SIMATIC S5 PDF archive. Use the A-series CPU 941/942/943/944 manual for this model. Do not treat the English B-series manual as an exact 7UA21 document.
Related topics
+ 943-7UA11, 943-7UA22, 943-7UB21 comparison, S5 memory submodules and S5 programming cables.
Browse SIMATIC S5
S5 CPU | SIMATIC S5 | S5 interfaces | Siemens second-hand homepage