6ES5 942-7UF15

Siemens 6ES5 942-7UF15 CPU 942F – SIMATIC S5-115F Processor

Siemens 6ES5 942-7UF15 is the CPU 942F processor for SIMATIC S5-115F. It has 5 KB of internal RAM, a 375 memory submodule receptacle and a PG/SINEC L1 serial connection. Within the SIMATIC S5 family, it forms part of the two-subunit F architecture. Do not select a standard Siemens S5 PLC processor as a replacement from the CPU number alone.

Two subunits and matching versions

S5-115F uses a two-channel 2oo2 architecture with two CPU 942F modules. The manual requires CPUs of the same version; both subunits must have identical operating systems and user programs. A parallel connection provides synchronization and data exchange.

Assess connection components such as 6ES5 304-3UB11, 6ES5 324-3UA12 and 6ES5 306-7LA11 against the existing F system layout. When selecting S5 interface modules, connector compatibility alone is insufficient; preserve the specified interconnection between subunits.

Internal RAM and program memory

Distinguish the 5 KB internal RAM from external program memory. In safety mode, the user program must reside in a suitable EPROM or EEPROM submodule. A RAM submodule causes the system to enter test mode. Check type, capacity and programming number when selecting S5 memory modules.

The manual lists 6ES5 375-0LA41 as a 32 KB EPROM, 6ES5 375-0LC31 as an 8 KB EEPROM and 6ES5 375-0LC41 as a 16 KB EEPROM. Verify the program and configuration records, memory signatures and A/B identifiers of both subunits through COM 115F.

STEP 5, COM 115F and the PG connection

The user program is written in STEP 5. COM 115F handles safety configuration, signature functions and detailed error display. Select appropriate S5 cables and connectors and a programming adapter for the front 15-pin TTY serial interface.

The isolation and supply arrangement of the PG/SINEC L1 interface differs from that of a standard CPU 942. Select S5 communication modules against the permitted F system hardware configuration; do not assume every S5 communication card can be installed directly.

Instruction times and software resources

Binary operation execution takes approximately 1.6 µs. The CPU provides 128 timers and 128 counters, which are reset during RESTART. Overall system response also depends on synchronization, tests and project settings. Scan monitoring is configurable.

Power supply and field modules

The exact-code technical table in manual EWA 4NEB 811 6148-02 specifies 0.8 A from the internal 5 V rail, typical power loss of 4 W and a weight of approximately 1.5 kg. Assess the loads of both subunits separately when checking the S5 power supply. Record the complete codes and battery condition of installed units such as 6ES5 951-7ND41 PS 951.

Evaluate S5 digital input and S5 digital output modules together with the channel arrangement and test connections specified in the F project. Installing the processor alone does not establish that the field I/O arrangement is suitable; compare addresses and configuration records with the existing project.

Differences from related codes

6ES5 942-7UF12 and 6ES5 942-7UF14 are earlier F versions with different manual coverage from UF15. 6ES5 942-7UH11 is CPU 942H for S5-115H. Do not approve direct substitution while overlooking the F/H distinction or order-number suffix.

Editor’s Note

Consider this module together with its partner. Record the CPU labels and system software versions in both subunits. Matching “942F” designations do not establish that the versions have been checked.

The backup involves more than the STEP 5 program. Retain the COM 115F configuration, memory signatures and A/B subunit identifiers. Clarify whether the supply includes the CPU alone or the CPU with its memory submodule.

Keep RAM and EPROM roles separate. Testing with a RAM submodule does not replace testing in safety mode. Check battery condition and review causes of memory data loss; back up the working installation before removing its memory.

Use the correct PG connection equipment. Check the TTY adapter, cable and interface isolation/supply arrangement. Inspect communication and synchronization between both subunits; a RUN indication on one CPU is insufficient.

Read the fault records before clearing them. Save DB2/DB3 error information and RN/ST, QVZ, ZYK and BASP indications. An overall reset also removes error information. Complete the existing project’s safety function tests after replacement before returning the system to service.

OtomasyonAVM resources and PDFs

See About Siemens S5 PLC and the S5 PDF archive for series information and documents. For this code, use the hardware manual S5-115F Volume 1/2, EWA 4NEB 811 6148-02 together with the software manual Volume 2/2, EWA 4NEB 811 6149-02. The exact-code technical table is on printed page 8-9, PDF page 236 of Volume 1.

Related topics

CPU 942-7UF12 · CPU 942-7UF14 · CPU 942H-7UH11 · PS 951-7ND41 · S5 memory modules. These links support comparison and system review; they do not confirm direct interchangeability.

Navigation: 6ES5 942-7UF15 main page | Used Siemens models | Siemens S5 PLC | SIMATIC S5

Siemens and external references

Siemens S5-115F hardware manual – EWA 4NEB 811 6148-02 (English). The two-CPU requirement is on printed page 2-11, memory selection on 2-12 and overall reset on 4-13.

Siemens S5-115F software and COM 115F manual – EWA 4NEB 811 6149-02 (English). Memory signature and subunit identifier functions are described on printed page 1-27.