6ES5 925-3SA11
Siemens 6ES5 925-3SA11 — S5-150S / S5-150U Central Processor Board
Siemens 6ES5 925-3SA11 is the second central board in the four-board processor assembly used in S5-150S and S5-150U systems. Siemens identifies it as “Zentralbaugruppe 2”. It forms part of the central processing assembly in a SIMATIC S5 installation; STEP 5 program execution must be assessed with the complete processor group.
The assembly lists 924-3SA11 as board one, 925-3SA11 as board two, 926-3SA11 as board three and 927-3SA11 as board four. These are not four interchangeable CPUs. 925-3KA12 is also a different order code; “925” alone is insufficient for replacement selection.
Placement and system compatibility
Siemens’ S5-150U manual assigns 924 S, 925 S, 926 S and 927 S to fixed slots 35, 43, 51 and 59, respectively. Therefore, 925 S occupies slot 43 in that arrangement. Do not apply this numbering to other S5 housings. Check the installed rack and central controller’s layout drawing.
Record the complete code, board revision and labels of the other three central boards before selecting a spare. Photograph additional hardware and cable connections. Preserve the existing hardware arrangement when changing one processor board so that a new compatibility issue does not obscure the original fault.
Supply and memory assessment
The S5-150U manual specifies an internal supply of 5 V ±5% for the CPU boards. Distinguish this internal rail from the power supply’s mains input. Do not present the system’s total current as the consumption of the individual 925-3SA11 board; assess the supply against the relevant controller documentation.
Check program memory, data blocks and retention at system level. The central controller’s total memory capacity should not be described as internal RAM fitted to this board. Preserve the accessible program, data blocks and current fault information before removing power or a board.
PG connection and fault tracing
The PG connection described in the S5-150U manual uses a separate AS 511 programming interface. Check the interface board, PG cable and software settings together. Failed programmer access alone does not establish a defective 925-3SA11; examine the installed communication arrangement as well.
Read operating and fault indications on the relevant central board. Capture fault information before repeatedly exchanging boards in a stopped controller. Compare supply condition, connector contact, memory and processor-group operation with a known working system.
Installation checks and acceptance testing
Compare digital inputs, digital outputs and analog modules with actual field signals. Record separate test results for function modules, position-control equipment and special modules. Replacing a central board does not remove the need to check peripheral addressing and parameters.
For an older Siemens S5 installation, go beyond visual inspection when accepting used equipment. Identify the controller, companion boards, program read and functions actually tested. Successful initial operation and stable operation after warming up are separate observations.
Editor’s note
Check what you are buying: 925-3SA11 is the second board of a four-board central processor assembly. A meaningful operating test requires suitable companion boards, memory and supply equipment.
Read the 3SA11 suffix and revision, rather than relying on “925”. Installing 3KA12 because it looks similar can introduce a compatibility problem alongside the original fault.
Photograph placement and bridges before removing the original board. Siemens’ 925-3SA11 drawing includes an A–B bridge position. Establish the purpose of an existing solder or bridge modification before changing it.
For failed PG access, check AS 511, the correct cable and the supply first. Treating every connection problem as a 925 fault can lead to rejecting a working board.
Ask which central controller and companion processor boards were used for testing. The report should distinguish a cold start, program access and operation after warming up, so the stated condition reflects the test actually performed.
OtomasyonAVM resources and PDFs
+ 6ES5 925-3SA11 product and information page, Siemens S5 CPU pages and SIMATIC S5 models.
+ OtomasyonAVM SIMATIC S5 PDF archive. Use the S5-150S/S5-150U central-controller documentation for this board.
Related topics
+ 924-3SA11, 926-3SA11, 927-3SA11, 925-3KA12 and S5 interface modules. Membership of the same central assembly does not make these boards interchangeable.
Browse SIMATIC S5
S5 CPU | SIMATIC S5 | S5 memory | Siemens second-hand homepage
Siemens and external references
+ Siemens ST 53 · 1985, May 1985 amendment, German — third-party archive copy — printed page 9/9 / PDF page 127: complete S5-150S central-board order codes.
+ Siemens Zentralgerät AG 150 U Betriebsanleitung, German document with C79000-B8500-C346-04 cover — third-party archive copy — page 2: fixed slots; 12: internal supply; 20: AS 511; 24: board and bridge drawings; 33: exact-code spare-parts list. Internal pages carry the /3 issue marking.
+ Siemens Zentralgerät 150 S / Zentralerweiterungsgerät 150 S, C79000-B8500-C246-3, German — section 4.4, page 15: 925-3SA11 listed as “Zentralbaugruppe 2”.