6ES5 921-1AA21
Siemens 6ES5 921-1AA21 CPU 921 – S5-130A / S5-130K
Siemens 6ES5 921-1AA21 is a CPU 921 / 921-1 central processor board for S5-130A and S5-130K central controllers in the SIMATIC S5 family. Its 1-bit processor architecture focuses on binary logic. The user program resides in a type 370 EPROM submodule fitted to the CPU; the system supports up to 4096 instructions of 16 bits, equivalent to 8 KB.
This Siemens S5 PLC architecture serves sequencing, interlocking and digital machine-control applications. Siemens specifies 4 ms for 1024 binary instructions; this is not a fixed total scan time for every application. The bit-processor design of S5-130A/130K must be distinguished from other CPU 921 models used in 130W and 135U systems.
EPROM program storage and internal RAM
When selecting S5 memory submodules, verify the 370 EPROM type and the existing program's capacity. EPROM memory and battery-backed RAM serve different purposes. RAM in this CPU stores internal flags and the output process image; its presence does not mean that the user program normally runs from onboard program RAM.
The S5-130A/130K catalogue lists 512 retentive and 128 non-retentive flag bits. Timing and counting use separate boards, including the 390 timer/counter module and 392 timer modules. Integrated timer and counter totals from later S5 CPUs must not be assigned to this model.
Programming connection and field signals
A PG 631 or PG 670 connects through a separate 6ES5 501-5AA11 PG interface. Siemens describes parallel data transfer with a 3.2 m connecting cable. Select S5 cables and connectors and interface modules for the 501 arrangement; serial PG-interface specifications from other S5 models do not apply here.
Field signals are handled by suitable digital input modules and digital output modules. The S5-130A/130K system supports 256 digital inputs and 256 digital outputs; these are system limits rather than physical terminals on the CPU. Determine signal voltage and output-current ratings from each installed I/O module's complete order code.
Supply, construction and expansion
The CPU operates from the system's internal 5 V supply. When checking an S5 power supply, distinguish its input rating from the CPU supply. For example, 6ES5 950-3AA51 used with S5-130A converts a 24 V DC input to the 5 V system rail; its current rating is not the consumption of this CPU alone.
S5-130A Robustbauform installations use 740 metal enclosures, while S5-130K uses a compact central housing. Expansion arrangements include 300-5AA12 for the A construction, 300-5CA11 for compact construction and 301-5CA12 in suitable distributed configurations. Select the connection arrangement to match both the central and expansion-unit construction.
6ES5 921-3UA12 belongs to S5-135U, while 6ES5 921-3WB11 belongs to a different processor arrangement in the 130W family. The shared “CPU 921” name does not establish identical program memory, instruction support, interfaces or rack compatibility.
Editor's Note
When buying used Siemens equipment, check more than the “CPU 921” description. Confirm the 6ES5 921-1AA21 order code, board revision and intended 130A/130K housing together. A similarly named 130W board belongs to a different arrangement.
Is the 370 EPROM included, and which program does it contain? Establish this first. A working CPU with a blank EPROM or another machine's program will not solve the replacement task. Keep a readable EPROM backup, its label information and the program version.
Do not confuse a weak backup battery with an erased EPROM program. When investigating memory data loss, check retention of flags and RAM state separately. A stopped program and lost machine-state data may point to different faults.
Prepare the correct 501 parallel interface and cable for PG access. Testing is limited without suitable programming hardware. Powering the board and observing an LED does not establish that the program can be read or executed correctly.
For timing or counting problems, examine the 390/392 boards and any operator settings before replacing the CPU. During replacement, check EPROM orientation, connectors and the 5 V supply; remove or insert the board with power switched off. Include actual input/output behaviour in the test.
OtomasyonAVM resources and PDFs
See About Siemens S5 PLC for general information and our S5 PDF files section for available documents. The main reference is the Siemens ST 53 / 1985 catalogue for S5-130 and S5-150. Pages 1/4, 1/8–1/9, 2/11, 3/1, 3/19 and 9/9 cover the processor, memory, PG connection and complete order code. The document is in German.
Related topics
501-5AA11 PG interface · 390-5AA22 timer/counter · 300-5AA12 expansion interface · 921-3WB11 processor comparison. These components and models must not be treated as direct substitutes performing the same role.
Browse SIMATIC S5: 6ES5 921-1AA21 main page · SIMATIC S5 · Siemens S5 PLC · Used Siemens models.
Siemens and external references
Siemens ST 53 / 1985 – exact 921-1AA21 order code and S5-130A/130K scope (German, archived copy)
Siemens ST 53 – bit processor, EPROM programming and system architecture (German)