6ES5 103-8MA03
Siemens 6ES5 103-8MA03 – SIMATIC S5-100U CPU 103
Siemens 6ES5 103-8MA03 is the CPU 103 central processor module for SIMATIC S5-100U. It provides internal RAM for 10,240 statements, an approximate binary instruction execution time of 0.8 µs and a 24 V DC supply. When maintaining Siemens, Siemens S5 and SIMATIC S5 equipment, verify the complete 8MA03 reference and hardware revision.
Memory, Timers and Real-Time Clock
CPU 103 provides 2048 flag bits, 128 timers and 128 counters. Of these, 512 flag bits and 8 counters are retentive. A suitable EPROM/EEPROM memory submodule can be used for program backup. An integral real-time clock is provided; assess the program, data blocks, clock settings and backup battery together in the maintenance records.
Power Supply and Installation Temperature
The permitted supply range is 18–34 V DC; the technical table lists a 24 V input current of 1 A. Permitted ambient temperature is 0–55 °C for horizontal installation and 0–40 °C for vertical installation. Check the S5 power supply under load and review the CPU supply and field load circuit against the wiring diagram.
Bus Arrangement and I/O Capacity
I/O modules connect through suitable bus units such as 6ES5 700-8MA11. Within the installed S5 mounting arrangement, the specified limit is 256 digital channels in total for digital inputs and digital outputs, and 32 analog channels in total for analog inputs/outputs. Mixed configurations must also comply with the limits of 704 total bus data bits and a maximum of 512 analog data bits.
Analog modules occupy slots 0–7. Analog byte addresses 64–71 are assigned to slot 0 and 72–79 to slot 1. On systems using the 6ES5 316-8MA12 expansion interface, record module order, connections and program addresses together.
STEP 5 Connection and DB1 Checks
Use suitable S5 cables and connectors for programmer access, and record the roles of installed interface modules and communication modules. Back up the STEP 5 program, data blocks and DB1 parameters before PLC programming or an overall reset. During debugging, remember that a DB1 parameter error can keep the CPU in STOP.
Comparison with 8MA01, 8MA02 and CPU 102
6ES5 103-8MA01, 6ES5 103-8MA02 and 6ES5 102-8MA02 are separate order numbers. Compare instruction support, memory capacity, DB1 configuration and application timing before replacement. The 0.8 µs figure describes a single binary instruction; assess bus cycles, input delay and program structure when determining the machine’s overall response time. Consult the Siemens S5 PLC overview for further background.
Editor’s Note
Read the full 103-8MA03 label. Do not assume every behavior of an older 8MA01 or 8MA02 carries over; check counting and sequence transitions in the application.
Back up the program, data blocks and DB1 together. If RUN cannot be reached, inspect DB1 parameters and ISTACK information before replacing hardware.
The 256 digital and 32 analog figures are combined input/output limits. Check the bus data budget separately for mixed configurations.
Check the battery indication and memory submodule label. Establish that the RAM program has a restorable backup, and follow the manual’s sequence for COPY operations.
0.8 µs is not the response time of the entire machine. Sensor delay, bus cycles and program structure also matter. Verify real input/output behavior as well as the RUN indication.
Documentation and PDF Archive
Our S5-115 PDF archive also includes S5-100U documentation. The exact-reference technical table for this model appears on printed page 14-9 of the manufacturer’s manual below.
Related Topics and Nearby Models
6ES5 103-8MA01 · 6ES5 103-8MA02 · 6ES5 102-8MA02 · 6ES5 100-8MA02. These links support CPU version comparisons; direct replacement suitability requires separate verification.
Siemens S5 Navigation
Used Siemens products · Siemens S5 main page · S5 function modules · Memory cards · Analog modules · Cables and connectors
External References
Siemens S5-100U System Manual – 6ES5 998-0UB23, English: EWA 4NEB 812 6120-02b; 14-9 CPU 103 8MA03 technical table; 2-8–2-9 bus limits; 6-5 analog addressing; Chapter 9 DB1; Chapter 12 real-time clock.