6ES5 581-0ED13
Siemens 6ES5 581-0ED13 CP 581/486 Basic Module
The Siemens 6ES5 581-0ED13 is a CP 581/486 basic board with an 80486DX4-100 processor. It handles communication and data-processing tasks in S5-115U, S5-135U and S5-155U installations within the SIMATIC S5 family. 6ES5 581-0ED13 provides the CP 581 processor section and works alongside the central CPU of the S5 PLC system.
Depending on the application, it supports process-data acquisition, file storage and computer-side processing. When assessing this arrangement among S5 communications modules, check actual data exchange with the CPU as well as startup. Physical connections, drivers and the STEP 5 transfer program must be considered together when reviewing S5 interface modules.
Processor frequency and model differences
Siemens specifies 75/100 MHz operation for 0ED13. On this model, S2-1 ON selects 75 MHz; OFF selects 100 MHz, with 75 MHz as the default. 6ES5 581-0ED14 is the 100/133 MHz version. Compare a replacement with the recorded settings of the existing installation; changing processor frequency is not a substitute for fault diagnosis.
Working memory and storage configuration
Check the RAM actually fitted. The 486 basic board has X205 for the RAM module and X204 for the onboard flash disk. Keep DRAM, boot media and S5 memory cards distinct when assessing memory types. The order code alone does not establish the installed memory or software contents of a used board.
6ES5 581-3LA11 and 6ES5 581-4LA11 are separate mass storage modules in the CP 581 family. When purchasing a basic board, establish whether the storage module, connecting parts and boot files are included.
S5 expansion modules such as the 6ES5 581-0RA11 slot module serve a different purpose. Record the exact code and revision of an existing AT expansion arrangement; a shared family name does not establish suitability for the 486 configuration.
Serial connections, video and power
The basic board uses combined 26-pin connections for COM 1/COM 3 and KEYB/COM 2. Suitable Y adapters are required for standard peripherals. Select cables and connectors by function and pin assignment rather than appearance. Video is provided through three coaxial RGB sockets; monitor and adapter compatibility must be checked separately.
Rack supply rails: the stated tolerances are ±5% for +5 V DC and +25%/−15% for +24 V DC. Assess the supply, combined board load and connections within the S5 rack together. Select measurement points and installation procedures from the relevant system manual.
Addressing and CPU data exchange
The SSNR base interface number is distinct from the physical slot number. The CPDHB driver allows base numbers 0, 4, 8 … 252. Four consecutive pages are used; for example, base number 4 corresponds to pages 4–7. This illustrates the addressing scheme and must be matched to the existing CPU program and CP settings before use.
Data transfer involves the CPU-side data handling blocks, or DHBs, and the CP-side CPDHB driver. Check completed startup, driver loading and CPU synchronization separately. Protect against data loss by preserving SETUP information, startup files and application backups before making changes.
Related basic boards and replacement selection
6ES5 581-0ED12, 6ES5 581-0EC12 and 6ES5 581-0EB11 are other CP 581 basic boards to compare. Alongside 0ED14, assess these models by processor, fitted memory, boot arrangement and application requirements rather than treating them as automatic replacements.
Other basic boards, including 6ES5 581-1EB12 and 6ES5 581-1EC12, also require their RAM and onboard disk arrangements to be checked. A disk booting on a different board does not, by itself, prove that the application and PLC communication will operate correctly.
Editor's Note
Before buying this board, ask to see the fitted RAM and boot arrangement. The correct label is only part of the picture: missing memory or an absent machine project can still leave the installation unusable. Get a clear list of the components supplied.
If no picture appears, check the RGB output, monitor and Y adapters before condemning the processor board. A cable fitting the socket does not establish that its electrical connections are suitable.
A 75 MHz setting does not make an 0ED13 incorrect; Siemens documents that setting. Photograph the existing S2 positions before making changes, and use the switch table for the exact model rather than another CP 581 revision.
Reaching the BIOS screen completes only the first stage of a useful test. Continue with driver loading, CPU synchronization and actual data reads and writes. When assessing memory reliability, record intermittent freezes as well; a brief startup demonstration is insufficient.
Back up SETUP information, startup files and disk contents before replacing a board in a working installation. Make the first trial with the machine in a safe condition and disconnect power before removing or fitting components. Recorded original settings make recovery much easier.
OtomasyonAVM resources and PDF documentation
Start with About Siemens S5 PLC, followed by the Siemens S5 PDF archive. For CP 581, use manual 6ES5 998-2AT22 and the tables covering 0ED13 and the 486 hardware.
Related topics
S5 communications modules · S5 cables and connectors · S5 memory cards · S5 expansion modules
Navigation: 6ES5 581-0ED13 model page | SIMATIC S5 main page | Siemens S5 PLC models | Used Siemens equipment
Siemens documents and external references
Siemens CP 581 User Manual, 6ES5 998-2AT22, August 1999 — English: preface iii–iv; sections 3.1.1, 3.1.3, 3.1.9, 4.1 and 6.2.
Siemens CP 581 Handbuch, 6ES5 998-2AT12, April 1999 — German: model coverage and processor-frequency comparison.