6ES5 395-0UA11
Siemens 6ES5 395-0UA11 – SIMATIC S5 OP395 Operator Panel
Siemens 6ES5 395-0UA11 is the German version of the OP395 operator panel for SIMATIC S5 systems. Its F1–F10 function keys, numeric keypad and display provide operator interaction with the S5 PLC. The rear markings identify a 24 V DC power supply and an AG S5 connection.
The Siemens S5-115U manual lists OP395 among the supported operator panels. That section describes panel applications including displaying current timer and counter values, entering new setpoints and showing program-controlled messages. When selecting a Siemens panel, check which functions the machine’s PLC program actually uses.
Connection and power checks
Check the rear connector marked AG S5 together with the existing S5 cable. Verify the wiring and pin assignment against the device documentation. If the installation includes interface modules or communications hardware, record their complete order numbers as well.
Before applying power, check the 24 V DC supply, polarity and terminal markings. Measure the power supply with the panel connected to help identify voltage drop across wiring or connections. Establish the correct wiring before starting fault diagnosis.
Program, data and panel replacement
Before replacement, record the working screens, operating settings and cable connections. Identify the PLC programming software and existing project files, and preserve backups associated with the S5 memory hardware. During S5 maintenance, retain the machine application alongside the hardware identification.
A PLC and HMI upgrade should account for mechanical installation, communications and the functions used by the operator. When selecting S5 supplementary hardware, review the panel label, physical condition and photographs of the existing installation together.
Comparison with other S5 operator panels
6ES5 393-0UA11, 6ES5 393-0UA12, 6ES5 393-0UA13, 6ES5 393-0UA15 and 6ES5 396-0UA11 are separate order numbers. Compare their connection arrangements, available functions and mechanical installation requirements individually. Verify compatibility before exchanging OP393, OP395 or OP396 equipment.
Editor’s Note
When buying a used Siemens panel, start with clear photographs of the rear label and front face. Read the complete 6ES5 395-0UA11 order number. Match the offered unit to the photographs before ordering.
Check display readability with different texts wherever possible, and test every key, including F1–F10. Look for incomplete characters and unreadable areas. An intermittently responding key needs investigation. Confirm that each press produces the intended response.
If communication fails, check the supply, cable and connectors first. Bent pins or loose connections can interrupt an otherwise working installation. Use measurements and inspection to guide the repair.
Record the screens and operating values before removing the working panel. Keep a separate copy of any available project or program backup. Retain the original panel until the replacement has been tested on the machine. It may still provide useful settings or wiring information.
Complete the check by reading a live value, changing an authorised setting under controlled conditions and confirming the corresponding PLC response. Record the checks in the maintenance notes. State clearly whether the test covered startup or actual machine functions.
OtomasyonAVM resources and PDFs
+ S5-115U PDF files · 6ES5 395-0UA11 model page · Siemens S5 second-hand models. Section 2.7.4 of the S5-115U system manual lists OP395 for use with that system.
Related topics
+ OP393 / 6ES5 393-0UA11 · 6ES5 393-0UA12 · 6ES5 393-0UA13 · OP396 / 6ES5 396-0UA11. These links support model comparison and do not establish replacement compatibility.
Browse SIMATIC S5
+ Siemens operator panels · S5 cables and connectors · S5 supplementary modules · SIMATIC S5 · Siemens second-hand main page.
Siemens and external references
+ Siemens S5-115U system manual, 6ES5 998-0UF23, English. Section 2.7.4, printed page 2-29: OP395 and operator-panel applications.
+ Siemens OP395 rear markings, device photograph. 24 V DC supply and AG S5 connection; photograph hosted by a third party.