6ES5 442-3AA11
Siemens 6ES5 442-3AA11 — 32-Channel 24 V DC / 10 mA Digital Output Module
The Siemens 6ES5 442-3AA11 is a non-isolated compact K-type module with thirty-two 24 V DC / 10 mA digital outputs in the SIMATIC S5 family. Within the S5 digital output range, it serves as a low-current signal output. Permitted channel current is 0.1–10 mA, with a maximum combined output current of 320 mA.
It belongs to the S5-130K, S5-130W and S5-150K I/O family. Match the complete order number, front connections and addressing to the existing Siemens S5 PLC and suitable S5 rack arrangement. Having 32 outputs does not give it the load capability of a 0.5 A or 2 A output module.
10 mA channel limit and signal levels
10 mA equals 0.01 A. A connected relay coil or other load drawing more than this requires a suitable interface stage. Check the interface input current and thresholds against the module’s output voltages; a “24 V” label alone is insufficient.
The manufacturer specifies a logic-1 output voltage of at least Up − 4.8 V and a logic-0 voltage of at most 3 V. Maximum switching frequency is 100 Hz for resistive loads and 2 Hz for inductive loads. These figures do not increase the channel-current limit.
Supply, common reference and protection
The external supply is nominally 24 V DC, with a permissible range of 20–30 V DC. There is no galvanic isolation. Assess the S5 power supply, load supply and common reference connections against the manufacturer’s drawing. Inspect S5 cables and connectors, supply returns and protective grounding.
The outputs are specified as short-circuit and overload protected. The listed fuse is T1.0 A, a time-delay 1 A type; this is not the channel-current rating. Supply connections have reverse-polarity protection through diodes. Isolate power before working on fuses or connections.
Consumption from the external 24 V supply, excluding output loads and including indication, is approximately 280 mA. Internal 5 V consumption is approximately 300 mA. Account for these separately from the combined output-load current. Operating temperature is 0–55 °C.
Four-byte addressing and jumper settings
The 32 channels occupy a four-byte output area. The byte address is coded using the module’s addressing socket; the manufacturer’s table gives multiples of four as starting addresses for 32-channel boards. For example, a starting byte of 20 gives A20.0–A23.7 in German STEP 5 notation. Match the PLC program’s output addresses to the physical coding.
During troubleshooting, check more than the individual channel command. Jumpers affecting RDY/MEMW behavior and the BASP output-inhibit function also matter. Record the existing address coding and jumper positions before replacing the board; do not change BASP settings casually to make an output operate.
Differences between related compact K-type modules
The 444-3AA11 has sixteen 24 V DC / 2 A outputs; the 445-3AA11 has thirty-two 24 V DC / 0.5 A outputs. The 445-3AA12 is also listed as a 32-output 0.5 A module. Do not apply their higher current ratings to the 442-3AA11; check revision and connection details separately.
The 450-3AA11 is a 32-channel 0.12 A type, while the 451-3AA11 has sixteen 24 V DC / 0.5 A outputs. Similar housings do not establish interchangeability; check channel count, isolation, voltage and addressing together.
Adapter and wiring checks for S7 migration
Siemens’ interface-adapter table pairs the 442-3AA11 with adapter 6EZ2041-8UG03-0DA0 and the 6ES7 322-1BL00-0AA0 S7-300 module. This is not a direct plug-in replacement. Existing wiring, the M connection, load conditions and program addresses must be verified as part of the migration project.
Editor’s note
Start by underlining the 10 mA rating. This board has a different job from the familiar half-amp output module. Trying it without knowing the connected device’s input current can mean asking a sound board to carry a load it was never designed for.
If the machine has a small interface board between this output and the load, include it in the investigation. It may have been removed or changed over the years. Following the circuit beyond the output is just as useful as measuring the board itself.
Even with an identical order number, take photographs of the addressing socket and jumpers before fitting a spare. The correct board at the wrong address can leave the program issuing commands while you search for a hardware fault.
Measure at the output and at the receiving input. A poor contact or common-return problem between them can put the fault outside the board. Follow the signal to where it disappears instead of deciding from the component’s name.
When buying a used Siemens 442-3AA11, ask for all 32 channels to be checked with loads suitable for the 10 mA limit. Inspect front-connector contacts, the addressing socket and signs of previous repair too. A few working outputs cannot establish the condition of the whole board.