6ES5 410-0AA41

Siemens 6ES5 410-0AA41 — S5-010W 16-Channel 24 V DC / 2 A Digital Output Module

The Siemens 6ES5 410-0AA41 is a digital output module with sixteen 24 V DC / 2 A solid-state outputs for the S5-010W in the SIMATIC S5 family. Within the S5 digital output range, it uses semiconductor switching. The manufacturer’s 50% simultaneity factor is a key load-selection condition.

Use the complete order number and the S5-010W hardware arrangement when assessing an existing Siemens S5 PLC. When selecting an S5 rack, do not assume that boards from different S5 families are compatible because their connectors or appearance seem similar.

2 A per channel and 50% simultaneity

Nominal channel current is 2 A. At that nominal load, a 50% simultaneity factor means calculating for 16 × 50% = eight outputs operating together, giving 8 × 2 A = 16 A of output-load current. This calculation does not permit all sixteen outputs to carry 2 A simultaneously.

Establish the current drawn by connected relays and valve coils, which loads operate together and their operating sequence. Supply conductors and connections must suit that load pattern too. Assess a single operating channel separately from several channels operating together.

24 V supply and electrical output limits

Nominal load voltage is 24 V DC, with a permissible range of 20–30 V DC. The specified logic-1 output level is U − 2 V, with a maximum off-state residual current of 1 mA. Check the S5 power supply, load supply, cables and connectors and protective grounding against the manufacturer’s drawing.

The manufacturer’s table gives maximum switching frequencies of 100 Hz for resistive loads, 11 Hz for lamp loads and 2 Hz for inductive loads. Internal suppression limits inductive interruption voltage to −15 V. Where a freewheeling diode is fitted, assess coil release time too; the diode changes the load’s turn-off behavior.

Individual channel fuses and fault checks

Each output has an integral extra-fast FF2.5/250G fuse. Do not confuse the fuse value with the channel’s 2 A nominal rating. For a failed output, inspect the load and possible short circuit, then check that channel’s fuse, connection and output stage. Isolate power before working on the board or fuses.

During troubleshooting, compare the program’s output command with the board’s actual address. Measure voltage at the load with a suitable load connected. Replacing a blown fuse without removing the cause can repeat the same failure.

Address-coding jumpers and four address options

The output area is selected using the board’s coding jumpers. The manufacturer’s table gives four decimal output ranges: 1.0–2.7, 9.0–10.7, 17.0–18.7 or 25.0–26.7. Each selection covers 16 outputs. For example, 09.0–0A.7 in hexadecimal represents 9.0–10.7 in decimal.

Photograph existing jumper positions before fitting a spare and match the selected range to the project. Track the system’s 400-0AA11 input/timer module and other digital inputs within their own address areas. Input, timer and output addresses have different functions in the S5-010W.

Differences from the 0AA12 and other 410 modules

The 410-0AA12 combines four 2 A outputs and twenty-four 0.8 A outputs. The 410-0AA41 has sixteen 2 A outputs. Sharing the 410 designation does not make their channel arrangements or address usage identical.

The 410-7AA11 has eight 24 V DC / 2 A outputs; the 410-7FA11 has eight 24 V DC / 1.8 A outputs for the S5-110F. The 415-7AB11 belongs to the AC output range, while the 417-7AA21 uses relay outputs. Check system family, channel count and switching type together.

Editor’s note

Seeing sixteen 2 A outputs can tempt you to jump straight to a 32 A total. This board has a 50% simultaneity condition. First write down which loads operate together; that is the most useful place to start the calculation.

Do not write off the whole board because one channel has stopped. Each output on this model has its own fuse. Find the cause on the load side before checking the relevant fuse, and give a sound output stage a fair chance.

A photograph of the old board’s address jumpers is a small but valuable record. If the spare is set to another address, the program can issue commands while the load stays still. That can waste time looking for a fault in working hardware.

If someone has added a diode across a coil, watch the machine’s release timing too. A circuit can work electrically while changing the machine’s sequence. Check when the load releases as carefully as when it operates.

When buying a used Siemens 410-0AA41, ask for all 16 channels to be checked with suitable loads. Request clear views of fuse holders, heat sinks, front connections and the jumper area. Keep the simultaneity limit during testing too; inspecting the board should not mean overloading it.

OtomasyonAVM resources and PDFs

+ OtomasyonAVM general S5 PDF archive. Use the S5-010W manual below for this product’s system and board details; connection tables for other S5 families should not be applied directly.

Related topics

+ 410-0AA12 · 410-7AA11 · 410-7FA11 · 400-0AA11 input/timer module · 417-7AA21 · PLC troubleshooting.

Browse SIMATIC S5

+ S5 digital output modules · S5 digital input modules · S5 cables and connectors · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand main page.

Siemens and external references

+ Siemens S5-010W operating instructions — English; GWA 4NEB 807 1021-02; printed page 6: 0AA41 and channel fuses; page 10: technical table; pages 18–19: jumpers, fuses and addressing.

+ Siemens S5-010W/K programming instructions — German; GWA 4NEB 807 1071-01; printed page 4: S5-010W module address areas; externally archived copy of the Siemens publication.