6ES5 420-7LA11

Siemens 6ES5 420-7LA11 – S5-115U Non-Isolated Digital Input Module, 32 × 24 V DC

Siemens 6ES5 420-7LA11 is a non-isolated digital input module with 32 inputs rated at 24 V DC for S5-115U, within the SIMATIC S5 family. It transfers switch, contact and sensor states to the CPU. The exact order number also appears in the S5-115H manual; check the intended CPU and system arrangement against the installed project's hardware requirements.

Typical field devices include inductive sensors, photoelectric sensors and mechanical switches. Non-floating / non-isolated means that the field inputs are not galvanically separated from the control electronics. Consider the PNP or NPN output type when selecting a sensor, and use an output suitable for the positive-voltage input arrangement. Dry relay contacts switch a suitable 24 V source to the input.

Input thresholds, current and response time

The nominal signal is 24 V DC. Siemens specifies −30 to +5 V for logic 0 and 13 to 30 V for logic 1. Do not use the 5–13 V interval as a defined operating state. Measure DC voltage between the input and its M reference; measuring only at the power supply will not reveal a drop along the field wiring.

Input current at logic 1 is typically 8.5 mA; input response time is 1.4–5 ms in either direction. This is separate from the CPU scan time. When assessing short pulses, check pulse width and program scanning together. The specified quiescent leakage-current limit for two-wire BERO proximity switches is 1.5 mA.

Common reference and front connector

The Siemens wiring arrangement requires an external reference connection between Mext and Mint. Review the power supply return, PELV supply arrangement and grounding/reference connections against the panel drawings. The manual limits the voltage drop along the reference connection to 1 V. If several inputs become unstable together, inspect this connection and measure its voltage under load first.

The front connection is 46-pole; 6ES5 490-7LB21 is the screw-terminal version. When selecting S5 cables and connectors, match the connection method already used. The diagram assigns inputs to 3–10, 15–22, 27–34 and 39–46, with M terminals 11, 23, 35 and 47 respectively. These four wiring clusters are not four galvanically isolated groups.

Addressing: four input bytes

The 32 channels occupy four input bytes. In an arrangement addressed through IM 306, the channel-selection switch is OFF for 32 channels, and the starting byte must be divisible by four. This setting belongs to the addressing panel of the relevant interface module; do not assume it is a DIP switch on the input card itself.

For an example start address of 32 = 20h, the inputs cover I32.0–I35.7; the next non-overlapping four-byte start could be 36 = 24h. Compare the PLC program addresses with the field labels. Apply a test signal and confirm that the expected PLC bit changes; the example does not establish the actual address of an existing machine.

Cable limits and module comparison

The manufacturer's maximum cable lengths are 1000 m shielded and 600 m unshielded, subject to the installation and interference conditions. Consumption from the internal 5 V supply is 5 mA, typical module power loss is 6.5 W, and approximate weight is 0.7 kg. This digital input card has a different task from an analog measurement module.

6ES5 430-7LA12 also has 32 inputs at 24 V DC, but uses optocoupler isolation. When selecting a replacement from the S5 digital input range, compare isolation, wiring and addressing as well as channel count. For a used input module, review photographs of both the label and front connector; a description such as “32-channel S5 card” is insufficient.

Editor’s Note

Start with the 420-7LA11 label and the common reference connection. A similar-looking isolated 430 card does not establish the same wiring requirements. Record the original module's complete order number and connections before changing anything.

If several inputs come and go together, give the wiring a fair check before blaming the card. Inspect the M connections, loose screws and oxidised contacts. Measure at the module under load; a healthy 24 V reading elsewhere in the cabinet does not tell the whole story.

Test all 32 inputs individually and watch both the LED and PLC bit. If an input with a two-wire sensor stays on, check the sensor's off-state leakage current as part of the investigation.

Photograph the IM 306 address settings before fitting the replacement. A sound card can appear faulty when the starting byte is wrong. Change one thing at a time so you can see which action resolves the problem.

For a used unit, specify the complete model, quantity, label photograph, working/faulty condition and price. Sales require an invoice; returns are not accepted, and workshop testing is available. To offer a card for sale, send its details to otomasyonavm@gmail.com.

OtomasyonAVM resources and PDFs

+ 6ES5 420-7LA11 model page and About Siemens S5 PLCs.

+ S5-115 and shared S5 PDF files.

+ Siemens S5-115H system manual – English: exact-code technical data and wiring diagram on printed page 17-13 / PDF page 445.

Related topics

+ 6ES5 430-7LA12 isolated digital input module and 6ES5 490-7LB21 front connector.

+ IM 306 addressing interface and S5 digital output modules.

Browse SIMATIC S5

+ S5 CPU and system range · S5 digital input modules · SIMATIC S5.

+ Siemens second-hand range · Used digital input modules.

Siemens and external references

+ Siemens S5-115U Manual, EWA 4NEB 811 6130-02b, Edition 04, English: technical data and diagram 15-20; reference connections 3-30 and 3-40; IM 306 addressing 6-5.

+ Siemens S5-115H Manual, EWA 4NEB 811 6111-02b, Edition 03, English: exact-code technical data on page 17-13.

+ Siemens 6ES5420-7LA11 product data sheet, 28 April 2018, English.